Technical Specifications

19
GENERAL INFORMATION
Scope:
This specication covers Copper Tube Size (CTS) CPVC manufactured to standard dimensional ratio (SDR) 11 for
non-potable water distribution. This system is intended for pressure applications where the operating temperature will
not exceed 180° F at 100 psi.
Specication:
Pipe shall be manufactured from virgin rigid CPVC (chlorinated polyvinyl chloride) vinyl compounds with a cell class
of 24448 as identied in ASTM D 1784. Fittings shall be manufactured from virgin rigid CPVC (chlorinated polyvinyl
chloride) vinyl compounds with a cell class of 23447 as identied in ASTM D 1784.
ReUze CTS CPVC pipe and ttings shall conform to ASTM D 2846. Pipe and ttings shall be manufactured as a
system and be the product of one manufacturer. All pipe and ttings shall be manufactured in the United States.
Pipe and ttings shall conform to NSF International Standard 14. The pipe shall be listed by NSF International for
reclaimed water and bear the mark “NSF-rw.”
Installation:
Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry and shall
conform to all applicable plumbing, re, and building code requirements. Buried pipe shall be installed in accordance
with ASTM F 1668 and ASTM D 2774. Solvent cement joints shall be made using CPVC cement conforming to ASTM
F 493. If a primer is required by local plumbing or building codes, then a primer conforming to ASTM F 656 should
be used. The system shall be protected from chemical agents, re-stopping materials, thread sealant, plasticized-
vinyl products or other aggressive chemical agents not compatible with CPVC compounds. The system shall be
hydrostatically tested after installation WARNING! Never test with or transport/store compressed air or gas in CPVC
pipe or ttings. Doing so can result in explosive failures and cause severe injury or death.
Referenced Standards:
ASTM D 1784: Rigid Vinyl Compounds
ASTM D 2774 Underground Installation of Thermoplastic Pressure Piping
ASTM D 2846: CPVC Plastic Hot and Cold Water Distribution System
ASTM F 493: Solvent Cements for CPVC Pipe and Fittings
ASTM F 1668: Procedures for Buried Plastic Pipe
NSF Standard 14: Plastic Piping Components & Related Materials
SUBMITTAL FOR CHARLOTTE PIPE
®
REUZE
®
CPVC COPPER
TUBE SIZE (CTS) NON-POTABLE WATER DISTRIBUTION SYSTEM
Charlotte Pipe, ReUze and Charlotte Pipe and Foundry Company are registered trademarks of Charlotte Pipe and Foundry Company.
FO-SUB-CPVC-REUZE (11-10-17)
Date: ________________
Job Name: ______________________________ Location: _______________________________
Engineer: _______________________________ Contractor: ______________________________
Not all tting patterns shown
Bushing
Cap
Street Quarter
Bend
Eighth Bend
Quarter Bend
Male Adapter
Charlotte Pipe and Foundry Company • P.O. Box 35430 Charlotte, NC 28235 • (800) 438-6091 • www.charlottepipe.com
Tee Coupling
Sizes Available
Product
1
2
3
4
1
1
1
4
1
1
2
2
ReUze
®
CPVC CTS SDR 11
PIPE REFERENCE GUIDE
Brass Male Adapter
1
2
0.382 (9.70) 0.183 (4.65) 0.102 (2.59)
3
4
0.507 (12.88) 0.235 (5.97) 0.102 (2.59)
1 0.633 (16.08) 0.287 (7.29) 0.102 (2.59)
1
1
4
0.758 (19.25) 0.339 (8.61) 0.102 (2.59)
1
1
2
0.884 (22.45) 0.391 (9.93) 0.102 (2.59)
2 1.134 (28.83) 0.495 (12.57) 0.102 (2.59)
NOMINAL G MINIMUM J MINIMUM N MINIMUM
SIZE (IN.) IN. (mm) IN. (mm) IN. (mm)
MINIMUM DIMENSIONS FROM CENTER TO END OF SOCKET
(LAYING LENGTH) FOR CPVC 41, SDR 11 FITTINGS
M
A
D
E
I
N
U
.
S
.
A
.