Technical Specifications

63
Flame Spread Index (FSI) and Smoke Developed Index (SDI)
Rating for ABS, PVC, and CPVC
The ASTM E 84/UL 723 test protocol is specified by the Uniform and International Mechanical Codes to evaluate a material’s
suitability for inclusion within unducted return air plenum spaces.
Charlotte Pipe manufactures all of our CPVC CTS pipe and fittings from FlowGuard Gold
®
CPVC pipe and fittings compounds
which are purchased directly from Lubrizol. These are the same compounds used by their other customers/converters to the
best of our knowledge. Further, Charlotte Pipe and other converters have provided our customers (contractors, engineers, code
officials, and distributors) in the past with copies of the Lubrizol test reports indicating that Lubrizol products conform to
ASTM E 84. In this listing (ICC-ES Report PMG-1264), which is available upon request, Lubrizol and ICC Evaluation Service
represent that the Lubrizol pipe and fitting systems are plenum compliant. Charlotte Pipe defers to this listing report.
Flame Spread and Smoke Developed Rating for FlowGuard Gold
®
CTS CPVC Piping Systems
FlowGuard Gold
®
CTS CPVC piping systems are listed and labeled as E84 25/50 Rated for use in plenums per ICC Evaluation
Service Report PMG 1264.
FlowGuard Gold
®
CTS CPVC piping systems comply with self-extinguishing requirements of ASTM D635.
FlowGuard Gold
®
CTS CPVC piping systems meet the V-0 burning class requirements of UL 94.
Flame Spread and Smoke Developed Rating for ABS
Per ASTM E 84, ABS does not meet the 25/50 flame and smoke requirement for plenum application.
Flame Spread and Smoke Developed Rating for PVC
Per ASTM E 84, PVC does not meet the 25/50 flame and smoke requirement for plenum application.
PVC piping systems are self extinguishing and will not support combustion.
PVC piping systems comply with self extinguishing requirements of ASTM D 635.
PVC piping systems meet the V-0 burning class requirements of UL 94.
DESIGN & ENGINEERING DATA
Pipe or fittings may be damaged by contact with
products containing incompatible chemicals resulting in
property damage or personal injury.
Verify that paints, thread sealants, lubricants, plasticized
PVC products, foam insulations, caulks, leak detectors,
insecticides, termiticides, antifreeze solutions, pipe
sleeve, firestop materials or other materials are
chemically compatible with CPVC.
Do not use edible oils such as Crisco
®
for lubricant.
Read and follow chemical manufacturer's literature
before using with piping materials.