Dimensions Guide
4
Pipe Data
M
A
D
E
I
N
U
.
S
.
A
.
Note: Full pallets are polyethylene wrapped for cleanliness and UV protection.
NSF Listed. Meets All Requirements of
ASTM D 1784 and ASTM D 1785.
PVC 10005B
1
⁄
2
” x 20’ 04924 6880’ 0.840 .147 850 PSI 20.3
PVC 10007B
3
⁄
4
” x 20’ 04925 4200’ 1.050 .154 690 PSI 27.0
PVC 10010B 1” x 20’ 04926 3540’ 1.315 .179 630 PSI 40.5
PVC 10012B 1
1
⁄
4
” x 20’ 04927 4240’ 1.660 .191 520 PSI 55.9
PVC 10015B 1
1
⁄
2
” x 20’ 04928 3300’ 1.900 .200 470 PSI 67.7
PVC 10020B 2” x 20’ 04764 1980’ 2.375 .218 400 PSI 93.6
PVC 10025B 2
1
⁄
2
” x 20’ 04875 1360’ 2.875 .276 420 PSI 142.8
PVC 10030B 3” x 20’ 04776 1000’ 3.500 .300 370 PSI 191.1
PVC 10040B 4” x 20’ 04774 1140’ 4.500 .337 320 PSI 279.3
PVC 10060B 6” x 20’ 04763 520’ 6.625 .432 280 PSI 532.7
PVC 10080B 8” x 20’ 04766 300’ 8.625 .500 250 PSI 808.9
PVC 10100B 10” x 20’ 04769 160’ 10.750 .593 230 PSI 1199.3
PVC 10120B 12” x 20’ 04771 120’ 12.750 .687 230 PSI 1650.1
PVC 10140B 14” x 20’ 04832 60’ 14.000 .750 220 PSI 1930.0
PVC 10160B 16” x 20’ 09372 60’ 16.000 .843 220 PSI 2544.1
PVC Schedule 80 Pipe, Type 1, Grade 1 - Belled End
PVC SCHEDULE 40 (WHITE) PLAIN END PVC 1120 ASTM D 2665
PVC SCHEDULE 80 (GRAY) BELLED-END PVC 1120
PVC Schedule 80 Pipe
Testing with or use of compressed air or gas in PVC / ABS
/ CPVC pipe or fittings can result in explosive failures and
cause severe injury or death.
• NEVER test with or transport/store
compressed air or gas in PVC / ABS / CPVC
pipe or fittings.
• NEVER test PVC / ABS / CPVC pipe or
fittings with compressed air or gas, or air
over water boosters.
• ONLY use PVC / ABS / CPVC pipe or
fittings for water or approved chemicals.
• Refer to warnings on PPFA’s website and
ASTM D 1785.
MAX WORK
PART NO. NOM. SIZE UPC # QTY. PER AVG. OD MIN. WALL PRESSURE AT WT. PER
611942- SKID (IN.) (IN.) 23° C OR 73° F 100 FT. (LBS.)