Installation Guide

12
Plastics Technical Manual
Product Specifications
System: PVC Schedule 40 Solid Wall Pipe and PVC DWV Fitting System
Scope: ThisspecicationcoversPVCSchedule40solidwallpipeandPVCDWVttingsusedinsanitarydrain,
waste,andvent(DWV),sewer,andstormdrainageapplications.Thissystemisintendedforuseinnon-
pressure applications where the operating temperature will not exceed 140°F.
Specification: Pipe and fittings shall be manufactured from virgin rigid PVC (polyvinyl chloride) vinyl compounds with
aCellClassof12454asidentiedinASTMD1784.
PVCSchedule40pipeshallbeIronPipeSize(IPS)conformingtoASTMD1785andASTMD2665.
InjectionmoldedPVCDWVttingsshallconformtoASTMD2665.FabricatedPVCDWVttingsshall
conformtoASTMF1866.Pipeandttingsshallbemanufacturedasasystemandbetheproductofone
manufacturer.AllpipeandttingsshallbemanufacturedintheUnitedStates.Allsystemsshallutilize
aseparatewasteandventsystem.PipeandttingsshallconformtoNSFInternationalStandard14.
Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry
and shall conform to all applicable plumbing, building, and fire code requirements. Buried pipe shall be
installedinaccordancewithASTMD2321andASTMF1668.Solventcementjointsshallbemadein
atwostepprocesswithprimerconformingtoASTMF656andsolventcementconformingtoASTM
D 2564. The system shall be protected from chemical agents, fire stopping materials, thread sealant,
plasticizedvinyl products,orotheraggressivechemical agentsnotcompatiblewith PVCcompounds.
Systems shall be hydrostatically tested after installation. WARNING! Nevertestwithortransport/store
compressed air or gas in PVC pipe or fittings.
Referenced Standards*:
ASTMD1784 RigidVinylCompounds
ASTMD1785 PVCPlasticPipe,Schedule40
ASTMD2665 PVCDrain,Waste,andVentPipe&Fittings
ASTMD2564 SolventCementsforPVCPipeandFittings
ASTMD2321 UndergroundInstallationofThermoplasticPipe(non-pressureapplications)
ASTMF656 PrimersforPVCPipeandFittings
ASTMF1668 ProceduresforBuriedPlasticPipe
ASTMF1866 FabricatedPVCDWVFittings
NSFStandard14 PlasticPipingComponentsandRelatedMaterials
*Note:Latestrevisionofeachstandardapplies.
Short Specification:
PipeandttingsshallbemanufacturedfromPVCcompoundwithacellclassof12454perASTMD1784
andconformwithNSFInternationalStandard14.Pipeshallbeironpipesize(IPS)conformingtoASTM
D1785andASTMD2665.InjectionmoldedttingsshallconformtoASTMD2665.Fabricatedttings
shallconformtoASTMF1866.
All pipe and fittings shall be produced by a single manufacturer and shall be installed in accordance with
manufacturer’s recommendations and applicable code requirements. Buried pipe shall be installed in
accordancewithASTMD2321andASTMF1668.SolventcementsshallconformtoASTMD2564,primer
shallconformtoASTMF656.ThesystemistobemanufacturedbyCharlottePipeandFoundryCompany
and is intended for non-pressure drainage applications where the temperature will not exceed 140°F.
GENERAL INFORMATION