Installation Guide

59
DESIGN & ENGINEERING DATA
FlowGuard Gold
®
pipe is inherently ductile allowing it to be deflected around or away from obstructions during installation.
This allows for greater freedom of design and ease of installation.
NOTICE:DONOTinstallttingsunderstress.Pipeortubemustbeproperlyrestrainedsothatstressfromdeectedpipeisnot
transmitted to the fitting. The maximum installed deflection for FlowGuard Gold
®
CTS CPVC pipe is as follows:
FlowGuard Gold Pipe, Length in Feet, SDR 11 (ASTM D 2846)
Nominal
Pipe
Pipe Length in Feet (L)
Size
2 5 7 10 12 15 17 20 25 30 35 40 45 50
(in) Permissible Bending Deflections (73°F) in inches - One End Restrained (d)
1
2 2.1 13.2 25.8 52.6 75.8 118.4 152.1 210.6 329.0 473.8 644.8
3
4 1.5 9.4 18.4 37.6 54.1 84.6 108.7 150.4 235.0 338.4 460.6 601.6
1 1.2 7.3 14.3 29.2 42.1 65.8 84.5 117.0 182.8 263.2 358.2 467.9 592.2
1
1
4 1.0 6.0 11.7 23.9 34.5 53.8 69.1 95.7 149.5 215.3 293.1 382.8 484.5 598.2
1
1
2 0.8 5.1 9.9 20.2 29.2 45.6 58.5 81.0 126.5 182.2 248.0 323.9 410.0 506.2
2 0.6 3.9 7.6 15.5 22.3 34.8 44.7 61.9 96.8 139.3 189.7 247.7 313.5 387.1
Maximum Installed Deflections (One End Restrained)
FlowGuard Gold Pipe, Length in Feet, SDR 11 (ASTM D 2846)
Nominal
Pipe
Pipe Length in Feet (L)
Size
2 5 7 10 12 15 17 20 25 30 35 40 45 50
(in) Permissible Bending Deflections (73°F) in inches - Both Ends Restrained (d)
1
2 0.5 3.3 6.4 13.2 19.0 29.6 38.0 52.7 82.3 118.5 161.2 210.6 266.6 329.1
3
4 0.4 2.4 4.6 9.4 13.5 21.2 27.2 37.6 58.8 84.6 115.2 150.4 190.4 235.1
1 0.3 1.8 3.6 7.3 10.5 16.5 21.1 29.3 45.7 65.8 89.6 117.0 148.1 182.8
1
1
4 0.2 1.5 2.9 6.0 8.6 13.5 17.3 23.9 37.4 53.8 73.3 95.7 121.2 149.6
1
1
2 0.2 1.3 2.5 5.1 7.3 11.4 14.6 20.3 31.6 45.6 62.0 81.0 102.5 126.6
2 0.2 1.0 1.9 3.9 5.6 8.7 11.2 15.5 24.2 34.8 47.4 61.9 78.4 96.8
Maximum Installed Deflections (Both Ends Restrained)
Permissible Bending Deflections for FlowGuard Gold
®
Pipe
DO NOT install fittings under stress. Pipe or tube must be
restrained so that stress from deflected pipe is not
transmitted to the fitting. Installing fittings under stress
may result in system failure and property damage.
L (ft.)
d (in.)
L (ft.)
d (in.)