Installation Guide

34
>> Cure Times
Minimum Cure Time to Test at 180 PSI
Cure times shown are sufficient to complete
a hydrostatic test at 100 PSI with 60%
humidity and cold water. Full cure may take
significantly longer.
Cure times are a function of air temperature,
water temperature, humidity and pipe size.
Increase the cure time for more demanding
conditions. For more specific information,
contact the cement manufacturer.
>> Special Considerations
Do NOT air test.
Chemical Compatibility. See Charlotte
Pipe and Foundry's Plastics Technical and
Installation Manual.
UV sensitivity.
Do NOT install permanently in direct
sunlight without painting with water-based
latex paint, or covering with insulation.
Teflon
®
tape should be used for 1-inch
or smaller and paste-type, non-hardening
thread sealant on 1
1
/
4
inch or larger.
PVC Schedule 40 Pipe & Fittings For Pressure Applications
Size 60˚- 100˚F 40˚- 60˚F - 40˚F
Notices, Cautions and Warnings Please refer to www.charlottepipe.com for all applicable notices, cautions and warnings for this
product group. You may also contact us at (800) 438-6091 for additional safety, installation or application information.
Notices: N-2; N-3; N-4; N-5; N-6; N-7; N-8; N-9; N-10; N-11; N-12; N-14; N-15; N-17; N-19; N-22; N-27; N-32; N-34;
N-38 Cautions: C-2, C-4, C-6, C-8 Warnings: W-2; W-3; W-4; W-5; W-6; W-9; W-12; W-13; W-14; W-15; W-17; W-18;
W-21; W-22; W-23; W-24; W-26; W-28; W-29; W-35; W-37
1
/
2
" to 1
1
/
4
"
1
/
2
" to 3"
4" to 8"
10" to 16"
1 Hour
2 Hours
6 Hours
24 Hours
2 Hours
4 Hours
12 Hours
48 Hours
8 Hours
16 Hours
48 Hours
8 Days
PVC Schedule 40 Pressure Installation
PVC Schedule 40 Pipe & Fittings