SUBMITTAL FOR CHARLOTTE PIPE
®
PVC SCHEDULE 40 SOLID WALL PIPE AND PVC DWV FITTING SYSTEM
Charlotte Pipe and Charlotte Pipe and Foundry Company are registered trademarks of Charlotte Pipe and Foundry Company.
FO-SUB-PVC-DWV (6-25-18)
Date: ________________
Job Name: ______________________________ Location: _______________________________
Engineer: _______________________________ Contractor: ______________________________
Scope:
This specication covers PVC Schedule 40 solid wall pipe and PVC DWV ttings used in sanitary drain, waste and
vent (DWV), sewer and storm drainage applications. This system is intended for use in non-pressure applications
where the operating temperature will not exceed 140° F.
Specication:
Pipe shall be manufactured from virgin rigid PVC (polyvinyl chloride) vinyl compounds with a cell class of 12454 as
identied in ASTM D 1784. PVC Schedule 40 pipe shall be Iron Pipe Size (IPS) conforming to ASTM D 1785 and
ASTM D 2665. Injection molded PVC DWV ttings shall conform to ASTM D 2665. Fabricated PVC DWV ttings shall
conform to ASTM F 1866. All pipe and ttings shall be manufactured in the United States. All systems shall utilize a
separate waste and vent system. Pipe and ttings shall conform to NSF International Standard 14.
Installation:
Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry and shall
conform to all applicable plumbing, re, and building code requirements. Buried pipe shall be installed in accordance
with ASTM D 2321 and ASTM F 1668. Solvent cement joints shall be made in a two-step process with primer
conforming to ASTM F 656 and solvent cement conforming to ASTM D 2564. The system shall be protected from
chemical agents, re-stopping materials, thread sealant, plasticized-vinyl products or other aggressive chemical
agents not compatible with PVC compounds. The system shall be hydrostatically tested after installation.
WARNING! Never test with or transport/store compressed air or gas in PVC pipe or ttings. Doing so can result in
explosive failures and cause severe injury or death.
Referenced Standards:
ASTM D 1784: Rigid Vinyl Compounds
ASTM D 1785: PVC Plastic Pipe, Schedule 40
ASTM D 2665: PVC Drain, Waste and Vent Pipe and Fittings
ASTM D 2564: Solvent Cements for PVC Pipe and Fittings
ASTM D 2321: Underground Installation of Thermoplastic
Pipe (non-pressure applications)
ASTM F 656: Primers for PVC Pipe and Fittings
ASTM F 1668: Procedures for Buried Plastic Pipe
ASTM F 1866: Fabricated PVC DWV Fittings
NSF Standard 14: Plastic Piping Components and
Related Materials
Not all tting patterns shown
Combination Wye
& Eighth Bend
Closet FlangeP-Trap
Double
Sanitary Tee
Eighth Bend
Quarter Bend
Coupling
Cleanout Tee
w/Plug
PVC Schedule 40 DWV Pipe
Charlotte Pipe and Foundry Company • P.O. Box 35430 Charlotte, NC 28235 • (800) 438-6091 • www.charlottepipe.com
PVC Schedule 40 DWV Pipe
PVC 7100* 1
1
⁄
4
”x10’ 03945 2120’ 1.660 .140 42.4
PVC 7100* 1
1
⁄
4
”x20’ 03946 4240’ 1.660 .140 42.4
PVC 7112* 1
1
⁄
2
”x10’ 03947 1650’ 1.900 .145 51.8
PVC 7112* 1
1
⁄
2
”x20’ 03948 3300’ 1.900 .145 51.8
PVC 7200* 2”x10’ 03949 1110’ 2.375 .154 69.5
PVC 7200* 2”x20’ 03950 2220’ 2.375 .154 69.5
PVC 7300* 3”x10’ 03951 1040’ 3.500 .216 144.2
PVC 7300* 3”x20’ 03952 920’ 3.500 .216 144.2
PVC 7400
†
4”x10’ 03953 600’ 4.500 .237 205.5
PVC 7400
†
4”x20’ 03954 1200’ 4.500 .237 205.5
PVC 7500
†
5”x20’ 04837 760’ 5.563 .258 272.5
PVC 7600
†
6”x10’ 03955 330’ 6.625 .280 361.2
PVC 7600
†
6”x20’ 03956 660’ 6.625 .280 361.2
PVC 7800
†
8”x10’ 13087 180’ 8.625 .322 543.6
PVC 7800
†
8”x20’ 03958 360’ 8.625 .322 543.6
PVC 7910
†
10”x20’ 03959 220’ 10.750 .365 770.7
PVC 7912
†
12”x20’ 03961 120’ 12.750 .406 1019.0
PVC 7914
†
14”x20’ 04862 60’ 14.000 .437 1205.0
PVC 7916
†
16”x20’ 04918 60’ 16.000 .500 1575.7
PVC SCHEDULE 40 (WHITE) PLAIN END PVC 1120 ASTM D 2665
PVC SCHEDULE 40 (WHITE) PLAIN END PVC 1120 ASTM D 2665
PART NO. NOM. SIZE UPC # QTY. PER AVG. OD MIN. WALL WT. PER 100 FT.
611942- SKID (IN.) (IN.) (LBS.)
* Dual Marked ASTM D 1785 & ASTM D 2665.
†
Triple Marked ASTM D 1785 & ASTM D 2665 & ASTM F 480.