Schedule 80 and Schedule 40 Socket Diameter Schedule 80 Schedule 40
Nominal Entrance Bottom Tolerance Socket Length Socket Length
Size A B C (Minimum) C (Minimum)
1
⁄
2
0.848 0.836 ±0.004 0.875 0.688
3
⁄
4
1.058 1.046 ±0.004 1.000 0.719
1 1.325 1.310 ±0.005 1.125 0.875
1
1
⁄
4
1.670 1.655 ±0.005 1.250 0.938
1
1
⁄
2
1.912 1.894 ±0.006 1.375 1.094
2 2.387 2.369 ±0.006 1.500 1.156
2
1
⁄
2
2.889 2.868 ±0.007 1.750 1.750
3 3.516 3.492 ±0.008 1.875 1.875
4 4.518 4.491 ±0.009 2.250 2.000
6 6.647 6.614 ±0.011 3.000 3.000
8 8.655 8.610 ±0.015 4.000 4.000
10 10.780 10.735 ±0.015 5.000 5.000
12 12.780 12.735 ±0.015 6.000 6.000
Scope:
This specication covers PVC Schedule 40 pipe and ttings for pressure applications. This system is intended for
pressure applications where the operating temperature will not exceed 140° F.
Specication:
Pipe and ttings shall be manufactured from virgin rigid PVC (polyvinyl chloride) vinyl compounds with a cell class of
12454 as identied in ASTM D 1784.
PVC Schedule 40 pipe shall be Iron Pipe Size (IPS) conforming to ASTM D 1785. Injection molded PVC Schedule 40
ttings shall conform to ASTM D 2466. Pipe and ttings shall be manufactured as a system and be the product of one
manufacturer. All pipe and ttings shall be manufactured in the United States. Pipe and ttings shall conform to NSF
International Standard 61 or the health-effects portion of NSF Standard 14.
Installation:
Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry and shall
conform to all applicable plumbing, re, and building code requirements. Buried pipe shall be installed in accordance
with ASTM F 1668. Solvent cement joints shall be made in a two-step process with primer conforming to ASTM F 656
and solvent cement conforming to ASTM D 2564. The system shall be protected from chemical agents, re-stopping
materials, thread sealant, plasticized-vinyl products or other aggressive chemical agents not compatible with PVC
compounds. The system shall be hydrostatically tested after installation. WARNING! Never test with or transport/store
compressed air or gas in PVC pipe or ttings. Doing so can result in explosive failures and cause severe injury or
death.
Referenced Standards:
ASTM D 1784: Rigid Vinyl Compounds
ASTM D 1785: PVC Plastic Pipe, Schedule 40
ASTM D 2466: PVC Plastic Fittings, Schedule 40
ASTM D 2564: Solvent Cements for PVC
Pipe and Fittings
SUBMITTAL FOR CHARLOTTE PIPE
®
PVC SCHEDULE 40 PRESSURE PIPE AND FITTING SYSTEM
Charlotte Pipe and Charlotte Pipe and Foundry Company are registered trademarks of Charlotte Pipe and Foundry Company.
FO-SUB-PVC-40 (6-18-18)
Date: ________________
Job Name: ______________________________ Location: _______________________________
Engineer: _______________________________ Contractor: ______________________________
Not all tting
patterns shown
Bushing
Plug
Cap
Street Quarter
Bend
Cross
Eighth Bend
Quarter Bend
Male Adapter
Charlotte Pipe and Foundry Company • P.O. Box 35430 Charlotte, NC 28235 • (800) 438-6091 • www.charlottepipe.com
ASTM F 1668: Procedures for Buried Plastic Pipe
NSF Standard 14: Plastic Piping Components & Related Materials
NSF Standard 61: Drinking Water System Components –
Health Effects
Tee Coupling
Female Adapter
Schedule 40
Tapered Socket Dimensions
PVC SCHEDULE 40 - ASTM D 2466
Sizes Available
Product
1
⁄
2
3
⁄
4
1
1
1
⁄
4
1
1
⁄
2
2
2
1
⁄
2
3
4
5
6
8
10
12
14
16
PVC Schedule 40
• • • • • • • • • • • • • • • •
PIPE REFERENCE GUIDE
M
A
D
E
I
N
U
.
S
.
A
.