How to Guide

28
Plastics Technical Manual
Testing with or use of compressed air or gas in PVC / ABS
/ CPVC pipe or fittings can result in explosive failures and
cause severe injury or death.
• NEVER test with or transport/store
compressed air or gas in PVC / ABS / CPVC
pipe or fittings.
• NEVER test PVC / ABS / CPVC pipe or
fittings with compressed air or gas, or air
over water boosters.
• ONLY use PVC / ABS / CPVC pipe for water
or approved chemicals.
• Refer to warnings in PPFA User Bulletin
4-80 and ASTM D 1785.
PRODUCT DATA
PVC4005B**
1
2
”
x10’ 04986 .840 .109 600PSI 2.00 15.9
PVC4005B**
1
2
”
x20’ 03923 .840 .109 600PSI 2.00 15.9
PVC4007B**
3
4
”
x10’ 04987 1.050 .113 480PSI 2.25 21.1
PVC4007B**
3
4
”
x20’ 03926 1.050 .113 480PSI 2.25 21.1
PVC4010B** 1
”
x10’ 04988 1.315 .133 450PSI 2.50 31.3
PVC4010B** 1
”
x20’ 03929 1.315 .133 450PSI 2.50 31.3
PVC 4012B§ 1
1
4
”
x10’ 04989 1.660 .140 370PSI 2.75 42.4
PVC 4012B§ 1
1
4
”
x20’ 03930 1.660 .140 370PSI 2.75 42.4
PVC 4015B§ 1
1
2
”
x10’ 04990 1.900 .145 330PSI 3.00 50.7
PVC 4015B§ 1
1
2
”
x20’ 03931 1.900 .145 330PSI 3.00 50.7
PVC 4020B† 2
”
x10’ 04991 2.375 .154 280PSI 4.00 69.2
PVC 4020B† 2
”
x20’ 03932 2.375 .154 280PSI 4.00 69.2
PVC 4025B‡ 2
1
2
”
x10’ 04992 2.875 .203 300PSI 4.00 110.0
PVC 4025B‡ 2
1
2
”
x20’ 04206 2.875 .203 300PSI 4.00 110.0
PVC 7300B§ 3
”
x10’ 04853 3.500 .216 260PSI 4.00 145.1
PVC 4030B† 3
”
x20’ 03933 3.500 .216 260PSI 4.00 144.5
PVC 7400B§ 4
”
x10’ 04835 4.500 .237 220PSI 4.00 207.9
PVC 9400B† 4
”
x20’ 03964 4.500 .237 220PSI 5.00 206.2
PVC 7600B§ 6
”
x10’ 04850 6.625 .280 180PSI 6.50 371.4
PVC 9600B† 6
”
x20’ 03965 6.625 .280 180PSI 6.50 365.5
PVC 7800B† 8
”
x10’ 09903 8.625 .322 160PSI 7.00 532.3
PVC 9800B† 8
”
x20’ 03967 8.625 .322 160PSI 7.00 552.3
PVC 7910B† 10
”
x20’ 03960 10.750 .365 140PSI 9.00 785.4
PVC 7912B† 12
”
x20’ 03962 12.750 .406 130PSI 10.00 1046.7
PVC 7914B† 14
”
x20’ 04863 14.000 .437 130PSI 10.00 1180.1
PVC 7916B† 16
”
x20’ 04929 16.000 .500 130PSI 10.00 1543.1
>> PVC Schedule 40 Pipe - Bell End*
* Bell dimensions meet either ASTM D 2672 or ASTM F 480, depending upon pipe diameter
** ASTM D 1785
§ Dual Marked ASTM D 1785 & ASTM D 2665
Triple Marked ASTM D 1785 & ASTM D 2665 & ASTM F 480
Dual Marked ASTM D 1785 & ASTM F 480
PVC SCHEDULE 40 (WHITE) BELL END PVC 1120 ASTM D 1785
MAX WORK
PART NO. NOM. SIZE UPC # AVG. OD (IN.) MIN. WALL (IN.) PRESSURE BELL DEPTH WT. PER
611942- AT 23° C OR 73° F (IN.) 100 FT. (LBS.)