Ifthereisnoexistingchimneythenaprefabricatedblockchimneyor
atwinwalledinsulatedstainlesssteelfluetoBSEN15287-1:2007can
beusedeitherinternallyorexternally.Thesechimneysmustbefitted
inaccordancewiththemanufacturersinstructionsandBuilding
Regulations.
Singlewallfluepipeissuitableforconnectingthestovetothe
chimneybutisnotsuitableforusingforthecompletechimney.Ifitis
foundthatthereisexcessivedrawinthechimneythenadraught
stabilisershouldbefitted.
Itisimportantthatthereissufficientdrawinthechimneyandthat
thechimneydoesnotsufferfromdown-draught.Whenthechimney
iswarmthedrawshouldbenotlessthan2.5mm(0.10")watergauge
(25Pa).Ifindoubtaboutthechimneyseekexpertadvice.
HEARTHANDFIRESURROUND
Thestovemuststandonafireproofhearthandmustnotbesituated
closerthantheminimumdistancefromcombustiblematerials(see
specificationtable)tothesidesorrearabovehearthlevelunless
adequatelyfireproofedinaccordancewithlocalbuildingregulations.
Thehearthmustbeoffireproofmaterialandatleast12mm(1/2in.)
thick.Thepositioningofthestoveandthesizeofthehearthare
governedbybuildingregulationsforClass1appliances.These
buildingregulationsstatethatthehearthmustextendinfrontofthe
stovebyatleast300mm(12in.)andtothesidesofthestovebyat
least150mm(6in.).
Ifindoubtastothepositioningofthestove,expertadviceshouldbe
soughteitherfromthesupplierorthelocalbuildinginspector.The
fireplacemustallowgoodcirculationofairaroundtheapplianceto
ensurethatmaximumheatistransferredtotheroomandalsoto
preventthefireplacefromoverheating.Agapof150mm(6")each
sideand300mm(12")abovetheapplianceshouldgivesufficientair
circulation.Ifawoodenmantelpieceorbeamisusedinthefireplaceit
shouldbeaminimumof460mm(18"),andpreferably600mm(24")
fromtheappliance.Insomesituationsitmaybenecessarytoshield
thebeamormantelpiecetoprotectit.
Inorderforthefiretooperatecorrectlyandtoallowforaccess,
theremustbeanairgapbehindtheapplianceofatleast75mm,but
beawarethatthisdistancewillneedtobegreaterinsomecasesto
meetBuildingRegulationrequirements.
Whenthefiredoorisopen,itextendsbeyond
theflatfrontofthestovebythefollowingamounts:
C-Four&C-Six365mm,C-Five436mm,C-Seven515mm,andC-
Eight450mm.
10
®
INSTALLATIONINSTRUCTIONS
RegisterPlate
SootDoor
InSideorRear
OfChimney
RegisterPlate
WithSootDoor
Alternative
SootDoorPositions
Fig.4.VerticalRegisterPlateWithBrickedUpFireplace
RegisterPlate
WithSootDoor
Alternative
SootDoorPositions
Fig.5.HorizontalRegisterPlateWithRearFlueConnection
Fig.6HorizontalRegisterPlateWithTopFlueConnection