Manual

Remote Infrastructure Management System - Version 1.0 / July 2014
212 www.chatsworth.com
Table I.1 Technical Specifications (continued)
Expansion Cards
CPI P/N 60103-001
1U accommodates 1 expansion card; 2U accommodates up
to 4 expansion cards
12 analog inputs (jumper selectable for 4-20mA, 0-5VDC or 0-10VDC) and
digital inputs (non-isolated, individual ground only);
8 Form C Relay Outputs, 1A @ 24VDC, 0.5A resistive @ 120VAC
CPI P/N 60103-002 (24 VDC)
or
CPI P/N 60103-003 (48 VDC)
24 Digital Inputs, 3000VAC RMS optically isolated (common
ground or individual ground)
24V requires P/N 60103-002 option cards; 48V requires CPI P/N 60103-003
option cards
Communications Ports
Ethernet 10/100BaseT, RJ45 connector; 500VAC RMS isolation
EIA-232
DB9 female connector; 9600 baud; 3000VAC RMS optically
isolated; 15kV ESD protection
EIA-485
(selectable as EIA-232)
Two-wire half duplex; terminal block (selecting EIA-232 switches to DB9 male
connector); 1200, 2400, or 9600 baud configurable; 3000VAC RMS
optically isolated
Modem (RJ11 Telco) –
Optional
V.34bis/33.6 kbps; DTMF capable; PPP-Enabled; FCC Part 68 approved; 1500VAC
RMS isolation barrier; 2100V peak surge protection
Protocols
TCP/IP, UDP/IP, ICMP/IP,
FTP, NTP
IPv4
HTTP/HTML, SNPP, Telnet
1.1/4.0; up to 10 URL links to other IP addressable cameras/devices; webpages
comply with Rehabilitation Act of 1973, sections 504 and 508, US Dept of
Education (website accessibility for computer users with disabilities)
SNMP
V1: MIB-2 compliant; NMS Manageable with Get, Set, and
Traps; V2c: Traps or Informs
SMTP (Email)
Supports Client Authentication (plain and login); compatible
with ESMTP Servers
Modbus
RTU transmission protocol; function codes: Slave - 03;
Master - 01,02,03,04
Modus/IP Modbus Slave; TCP/IP transmission protocol
BACnet/IP Reads up to 106 instances and converts to SNMP and Modbus
Terminal Emulation VT100 compatible
TAP (Pager) Telocator Alphanumeric Protocol Ver1.8