Brochure
Serie MN
Pinces ampèremetriques pour courant AC
Non-contractual document
906131102A - Ed 1
1.06 (3/4)
Current clamp for AC current
MINI 100 series
•
Output:
Double-insulated cable 1.5 m long, terminated
by 2 insulated elbowed male banana connectors
Ø4mm
•
Bandwidth:
48 Hz .. 10 000 Hz
•
Clamping capacity:
Cable Ømax 16mm
ELECTRICAL SPECIFICATIONS
•
Load impedance:
≥ 10 kΩ
•
Infl uence of load impedance:
See curves
•
Maximum currents:
350 A permanent at a frequency ≤ 1 kHz.
200 A permanent at a frequency ≤ 8 kHz
(limitation proportional to the reciprocal of the
frequency beyond that)
•
Infl uence of temperature:
≤ 0.2 % per 10 °K
•
Infl uence of adjacent conductor:
≤ 2 mA / A at 50 Hz
•
Infl uence of conductor position in jaws:
≤ 0.08 % at 50/60 Hz
•
Infl uence of frequency:
≤ 1 % typique
MECHANICAL SPECIFICATIONS
•
Operating temperature:
-10 °C to +50 °C
•
Storage temperature:
-40 °C to +80°C
•
Relative humidity for operation:
From 0 to 85% RH with a linear decrease above
35°C
•
Operating altitude:
0 to 2,000 m
•
Casing protection rating (leakproofi ng):
IP20
(2)
(EN60529 Ed. 2001)
•
Drop test:
1 m (IEC 68-2-32)
•
Dimensions:
130.4 x 46 x 34mm
•
Weight:
approx. 250 g
•
Colour:
Black casing
SAFETY SPECIFICATIONS
•
Electrical safety:
Instrument with double insulation or
reinforced insulation between the primary,
the secondary and the grippable part located
under the guard as per EN 61010-1 Ed.2:2001,
EN 61010-2-031 Ed. 2002 & EN 61010-2-032
Ed.2003
- 600 V categoryIII, pollution degree 2
- 300 V category IV, pollution degree 2
•
Electromagnetic compatibility:
CE-certifi ed equipment compliant with standard
EN61326-1: 2006
- Emission: stipulations for class B equipment
(domestic use).
- Immunity: stipulations for equipment used
intermittently on industrial sites.
Calibre
200 A AC
Sensitivity
1 mV / A
DESCRIPTION
The MINI 103 current clamp is the ideal companion for any multimeter to
measure AC currents in tertiary or industrial applications.
When used with an AC voltmeter, it enables you to read the current
measured directly on the voltmeter.
MAIN SPECIFICATIONS
(1)
Calibre 200 A
Measurement range 0.1 A .. 200 AAC
Accuracy in% ≤ 1.5 % + 0.02 A
Phase shift ≤ 3°
Output signal
1 mVAC / AAC
(200 mV for 200 A)
Model MINI 103