Brochure
Serie MN
Pinces ampèremetriques pour courant AC
Non-contractual document
906131102A - Ed 1
1.02 (1/2)
MINI series
Current clamp for AC current
•
Output:
Double-insulated cable 1.5 m long, terminated
by 2 insulated elbowed male banana connectors
Ø4mm
•
Bandwidth:
48 Hz .. 10 000 Hz
•
Clamping capacity:
Cable Ømax 10mm
ELECTRICAL SPECIFICATIONS
•
Load impedance:
≤100 Ω
•
Infl uence of load impedance:
See curves
•
Maximum currents:
I <100 A permanent from 48 Hz .. 10,000 Hz
•
Infl uence of temperature:
≤0.2% per 10 °K
•
Infl uence of adjacent conductor:
≤2 mA / A at 50 Hz
•
Infl uence of conductor position in jaws:
≤0.1% at 50/60 Hz
•
Infl uence of frequency:
≤2% from 65 Hz to 10kHz
•
Maximum output voltage
(secondary open):
≤30 V
MECHANICAL SPECIFICATIONS
•
Operating temperature:
-10 °C to +50 °C
•
Storage temperature:
-40 °C to +80°C
•
Relative humidity for operation:
From 0 to 85% RH with a linear decrease above
35°C
•
Operating altitude:
0 to 2,000 m
•
Casing protection rating (leakproofi ng):
IP40
(2)
(EN60529 Ed. 1992)
•
Drop test:
1.5 m (IEC68-2-32)
•
Shock resistance:
100 g / 6 ms / half-period (IEC68-2-27)
•
Vibration resistance
(3)
:
5-15 Hz (1.5 mm), 15-25 Hz (1 mm), 25-55 Hz
(0.25mm) (IEC68-2-6)
•
Self-extinguishing capability:
Casing UL94 V2
•
Dimensions:
130 x 37 x 25mm
•
Weight:
Approx. 180 g
•
Colour:
Black casing
SAFETY SPECIFICATIONS
•
Electrical safety:
Instrument with double insulation or reinforced
insulation between the primary, the secondary and
the grippable part located under the guard as per
EN61010-1 Ed.2:2001,
EN61010-2-031 Ed.2002 &
EN61010-2-032 Ed.2003
- 600 V categoryIII, pollution degree 2
- 300 V category IV, pollution degree 2
•
Electromagnetic compatibility:
CE-certifi ed equipment compliant with standard
EN61326-1 (Ed. 97) + A1 (Ed. 98) + A2 (Ed. 01)
- Emission: stipulations for class B equipment
(domestic use).
- Immunity: stipulations for equipment used
intermittently on industrial sites.
Calibre
100 A AC
Sensitivity
1 mA / A (1000 / 1)
DESCRIPTION
The MINI 02 current clamp, whose jaws are equipped with a high-
performance magnetic material and a double coil, offers excellent
linearity and improved performance.
Small and compact, it is ideal for measuring AC currents in low-power
tertiary or industrial applications.
If a current is present in the conductor being clamped, the MINI 02
clamp is protected against voltage surges when it is disconnected from
the measurement instrument.
MAIN SPECIFICATIONS
(1)
Calibre 100 A
Measurement range
50 mA .. 100 A (load 1 Ω)
50 mA .. 90 A (load 10 Ω)
Accuracy of primary current in%
(48 Hz to 10 kHz)
≤1% + 0.02 A (load 1 Ω)
≤1.5% + 0.01 A (load 10 Ω)
Phase shift (50 Hz to 60 Hz)
≤3° (load 1 Ω)
≤6° (load 10 Ω)
Output signal
1 mAAC / A AC (1000 / 1)
(100 mA for 100 A)
Model MINI 02