User's Manual
SIDEP
Page 15 of 19
□ Reduce the system sensitivity with VR5 until this problem stops.
□ Then switch the system back to the automatic level control mode (switch 7
position ON)
□ Press SW1 to reset system.
□ The detection will decrease, but functioning will be more stable and false
alarm less frequent.
• External Synchro Mode is not working even if cables are properly
connected (EXT SYN LED ON except Master System): A slave system must
have been powered on before its Master.
□ Switch off all systems
□ Switch on each system individually and in order starting from the Master
system.
• Labels are deactivated when passing near the MONO system:
□ Set Switch 8 in the position ON.
□ Press SW1 to reset system
To protect the label against deactivation due to high transmission Level, the
system will automatically decrease the output Transmission Level when a tag is
detected
System reaction may be slower and detection performance reduced.
7. Advanced adjustment of system parameters
7.1 LEDs DS11-18:
Press the SW2 button while holding it , you can see the signal number
corresponding the list below. When you release it you can see the value.
Number of LEDs being ON simulates the output of a particular signal .
• input signal (default after powering the system on)
• filtered input signal
• level of resonance caused by tags, metal construction, loops of wire,
etc)
• resultant input signal
• signal detection on each frequency (there are 8 frequencies transmitted)
• not yet used
• not yet used
• indication of sensitivity level reduction in automatic regime (DIP 7 ON).
(Example: 6 LEDs ON…80% of maximum or reduction by 20%)