Wire Routing
Methods of Wire Routing
Floor Trench: Typically 1.3cm [.5in.] wide by 3.8cm [1.5in.], but an increase in
dimensions is recommended for more than two antennas.
Wiremold: 1500 or 2600 series wire mold can be utilized. Typically wire mold is not
used within customer traffic areas, so a typical placement is from the outside of the
antennas to the doorframe.
Conduit: 2.5cm [1in.] diameter conduit can be utilized in new construction situations. It is
recommended that swept 90 degree angles are used, and that pull-strings are provided by
the conduit installer.
Wall / Mullion: Wires can be contained within mullions, and hollow walls for vertical
wire runs.
Dek-Duct / Panduit: Wires can be contained within surface mount Dek-Duct or Panduit
for vertical wire runs.
W
ARNING
: Any wiring in plenum areas must be plenum rated. Additionally, ensure that the
wire is installed in accordance with applicable (local/national) electrical codes.