User guide

3
CONTROLLER CONFIGURATION factory settings (T type):
LEVEL 1
tune band int.t der.t dac cyc.t ofst sp.lk set.2 bnd.2 cyc.2
off .1 off off .5 on.of 0.0 off 0.0 .1 on.of
LEVEL 2
sp1.p hand pl.1 pl.2 sp2.a sp2.b disp hi.sc* lo.sc* inpt* unit
100 off 100 100 dv.hi none 0.1º 250 -199.9 t ºC
LEVEL 3
sp1.d sp2.d burn rev.d rev.l span zero** check read data ver rset
ssd rly up.sc 1d2d 1i2n 0.0 #.# off var ct A 3 none
*for Type “K” thermocouple - hi.sc=999.9, lo.sc=-50, inpt=k **zero value is set at factory
Changing Display from °C to °F
The display units can be changed by depressing both the and keys simultaneously. Oncetune” is displayed, the keys may
be released. Then depress the , until “LEVL” is displayed. Depress and hold the * key. Then press the , until the display
reads “2”, then release the * key. Now depress the , until the display reads “unit”. The display will alternate between “°C” and
unit”. Depress and hold the * key. Then press the to display °F”, then release the * button. The change will be saved by
either depressing both the and keys simultaneously and releasing when the measured temperature is displayed. Or, if no
other keys a pressed after about 60 seconds the changes will be saved and the measured temperature will be displayed.
Changing Sensitivity of Alarm set point - Factory set to +.1°C
The alarm set point sensitivity can be changed by depressing both the and keys simultaneously. Oncetune” is displayed,
the keys may be released. Then press the until “bnd.2” is displayed. Depress and hold the * key. Then press the to enter
the desired sensitivity value, then release the * button. The change will be saved by either depressing both the and keys
simultaneously and releasing when the measured temperature is displayed. Or, if no other keys a pressed after about 60 seconds
the changes will be saved and the measured temperature will be displayed.