Specifications
Edition 3.0E, 2011/05
8. Trouble shooting 
In most situations, the inverter requires very little service. However, if inverter 
is not able to work perfectly, please refer to the following instructions before 
calling your local dealer. 
z  Should any problems arise, the red (Fault) LED on the front panel turns 
on and the LCD d isplays the relevant information. Please refer to the 
following table for a list of potential problems and their solutions. 
Display  Possible actions 
Isolation fault 
1. Check the impedance is between PV (+) & PV 
(-) and the PV-Inverter is earthed. The 
impedance must be greater than 2MΩ 
2. If the problem persists please call service 
Ground I fault 
1. The ground current is too high. 
2. Unplug the inputs from the PV generator and 
check the peripheral AC system 
3. After the cause is cleared, re-plug the PV panel 
and check PV-Inverter status. 
4. If the problem persists please call service. 
Grid fault 
1. Wait for 30 seconds, if the grid returns to 
normal, PV-Inverter automatically restarts. 
2. Make sure grid voltage and frequency meet the 
specifications 
3. If the problem persists please call service 
System 
Fault 
No Utility 
1. Grid is not connected. 
2. Check grid connection cables. 
3. Check grid usability. 
PV over 
Voltage 
1. Check the open PV voltage, see if it is greater 
than or too close to 500V (450V for CPS 
SC1.5KTL). 
2. If PV voltage is less than 500
 VDC (450 VDC,) and 
the problem still occurs, please call local service
Inverter 
Failure 
Consistent 
Fault 
1. Disconnect PV (+) or PV (-) from the input, 
restart the PV-Inverter 
2. If it does not work, call service 