Unit installation
3
NOTICE – These heaters are designed for wall and ceiling  mount. 
Other modes of mounting void factory warranty.
Vertical Air Flow
1.  Height above floor
  A.  It  is  recommended  that  the  heater  only  be  used  with  ceiling 
heights of 12 feet or greater. Minimum spacing to ceiling is 6 
inches, use 3/8-18” thread stock (supplied by others) as shown 
in Figure 3.
  B. Mimimum mounting height is 10 feet from floor to bottom of 
heater.
2.  Spacing to walls.
  A.  Side of case to wall 6”. Top or bottom of case to back wall is 
10-1/4” (HVH-02 to HVH-05), 13” (HVH-15 to HVH-20) and 
15-1/2” (HVH-25 to HVH-50).
CEILING (Vertical Airflow):
  A.  The heater can be rod mounted to the ceiling by installing four 
(4) threaded mounting rods in the threaded holes located on the 
top of the heater as shown in Figure 3. (Refer to Table C for 
mounting rod thread size.)
  B. Securely attach the four (4) mounting rods to the ceiling. (Re-
fer to Table D for wall and ceiling clearances, and Figure 2 for 
mounting spacing specifications.)
Figure 2 - Wall and Ceiling Clearance
INSTALLATION
XX
L2
L1
CL
CL
3/8-18 THREADED
MOUNTING HOLES
TERMINAL BOX
ACCESS DOOR
Back Wall
Side Wall
ADDITIONAL THREADED
MOUNTING HOLES FOR
HVH-25 TO HVH-50
Figure 3 - Rod Spacing
KO FOR CONTROL WIRING
KO FOR POWER WIRING
TERMINAL BOX
ACCESS DOOR
Figure 4 - Heater Back View
Table C — Rod Thread Type and Spacing Dimensions (inches) for 
Vertical Discharge.
Unit
Rod
Thread Type
Dimensions – (In.)
L1 L2 X
2-5 kW 3/8-16 2-7/8 7-1/8 3-3/4
7-1/2 - 20 kW 3/8-16 4-5/16 9-3/8 5-1/2
25 - 50 kW 3/8-16 8-15/16 14 9-15/16
Table D — Clearance Requirements (Vertical Discharge)
Model
Mounting Limitations (In.)
Back to Wall Side to Wall Top to Ceiling
HVH-02 Thru HVH-05 10-1/4 6 6
HVH-07 Thru HVH-20 13 6 6
HVH-25 Thru HVH-50 15-1/2 6 6
Horizontal Air Flow
1.  Height above floor
  A. 
In areas where ceiling height is more that 12 feet, recommended 
mounting height is approximately 10 feet to underside of heater.
  B. For ceiling  heights  of 12  feet  or less,  maximum mounting 
height is detemined by the use of the mounting bracket offered 
for these heaters. Minimum spacing to ceiling is 7-3/4”. (See 
Figure 5)
  C.  In either  case,  the mimimum mounting height  is  7 feet from 
floor to bottom of heater.
2.  Spacing to adjacent walls.
  A.  Rear of case to back wall 2” minimum.
  B. Side of case to side wall 6” minimum.
CEILING – Horizontal Airflow (See Figure 5):
The ceiling mounting bracket is fastened to the top of the heater using 
the four (4) bolts supplied with the mounting bracket. The bracket is 
then mounted to the ceiling using a 5/8” bolt (by others).
WALL – Horizontal Airflow (See Figure 6):
Wall mounting  necessitates the  use of  both an  adaptor mounting 
bracket and a wall mounting bracket. First, attach the ceiling mounting 
bracket to  the heater. Then, attach  the wall  mounting  bracket to  the 
wall using four 5/16” bolts and six 3/8” bolts (by others). Attach the 
ceiling mounting bracket on the heater to the wall mounting bracket 
using the 5/8” bolt provided.
Knockout Sizes
HVH-02 - 05 1/2” 3/4” (1)
HVH-07 - 20 1/2” 1” (1)
HVH-25 - 50 1-1/4” 2” (1)