Unit installation
5
WIRING
ELECTRIC  SHOCK  HAZARD.  Be  sure  electricity  is 
turned off at main switch first before wiring. Any  in-
stallation involving electric heaters must be effective-
ly grounded in accordance with the National Electrical 
Code to eliminate shock hazard.
1.  Use heater only on the voltage and frequency specified on the name-
plate.
2.  All wiring should be done in accordance  with  local  codes and the 
National Electrical Code by a qualified person as defined in the NEC.
3.  Two knockouts are provided on the back of the heater for wire entry. 
See Figure 4 for location of knockouts.
4.  Branch circuit wire for connection to heater must be at least 60˚C 
wire.
5.  The bottom access door is hinged. There are two screws that must be 
removed to gain access (Figure 3).
6.  A ground wire or ground lug is provided near the power connection 
point (ground Wire on HVH-02 to HVH-20 and ground lug on HVH-
25 to HVH-50).
7.  Terminals on contactor or on line voltage terminal block are supplied 
to be connected to accept the correct size power supply wire. Copper 
rated at 600V and 60˚C is satisfactory for the heater branch circuit.
8.  Electrical  accessories,  either kits  or  factory-installed options,  are 
shown connected by a dash line on the heater wiring diagram.
9.  Wiring connections  are to  be made  on designated  wire leads  as 
shown in the wiring diagrams located inside the access door.
10. Louver adjustment (Do not attempt to adjust while heater is op-
erational): Louvers have been preset at factory with the minimum 
open angle.  Decreasing the 45˚  angle may result  in high tempera-
tures and functioning of the over temperature control. To increase the 
opening angle, grasp the left end of louver with the left hand using 
the index finger and thumb. Grasp right end of louver with right hand 
in the same manner. Twist louver to the desired position.
Top of Heater
45˚ Min.
All Louvers
Figure 7 - Louver Adjustment
POWER DISCONNECT SWITCH
(Available as a kit or factory installed option). This switch discon-
nects the power to the power leads when the handle is turned to its off 
position. Refer to Instruction Sheet PF207.
1.  Use  copper conductor  supply  wire  only  when connecting  to  the 
power line. (See Figure 8.)
2.  Connection to the switch pigtails should be made with compres-
sion connectors and the joint should be then well insulated.
3.  Consult the local wiring code in your area.
SUMMER FAN SWITCH - Refer to Instruction sheet PF205 with-
out relay, PF206 with relay.
(MOUNTED ON FRONT OF HEATER). When the switch handle is 
pointing toward the Summer (Fan ON) position, the fan will run continu-
ously. When the switch handle is pointing toward the WINTER (HEAT) 
position, the fan will run only when the heating elements are hot.
REMOTE SUMMER FAN SWITCH
(MANUAL  SWITCH-LINE  VOLTAGE). The  wall  switch  is 
packed in the wiring compartment. The remote fan switch is mounted 
external and remote from the HVH unit heater. The voltage of the re-
mote fan switch is the same as the supply voltage to the HVH heater.
1.  Use  14 gauge  copper,  NEC  Class  1,  600V rated  insulated  wire. 
Wiring  must  meet all Local  and NEC requirements  for 480-volt 
service.
2.  Install the remote fan switch in standard wall box in any conve-
nient location that is protected from traffic or other accidental dam-
age.
3.  Connect the 14 gauge copper field wire to the  switch  lead wires 
with suitable connectors.
Power
Disconnect
Switch
L1
L2
L3
S1
S2
S3
See Notes
Contactor
or Terminal
Block
To
Power
Supply
See
Note 2
Notes:
1. This illustration shows wiring hook up for three phase service. Remove lead
 wires marked L3 and S3 when using single phase power service.
2. For units without contactors, disconnect switch is to be wired to terminal block 
 on heater power.
3. Use copper supply wire only with this switch.
Figure 8 - Power Disconnect Switch Wiring Diagram
REMOTE FAN SWITCH
480V + Heaters require an additional fan relay. (Available as a kit 
or factory installed option and standard on heaters 20kW and above). 
The wall switch is packed in the wiring compartment.
1.  Use 18 gauge (min.) NEC Class 1, 600V wiring that meets all Lo-
cal and NEC requirements.
2.  Install the  wall  switch in a  standard  wall box in  any  convenient 
location that is protected from traffic or other accidental damage.
3.  Connect the field wire to the switch lead wires with suitable con-
nectors.
OPTIONAL  THERMOSTAT  (HVH-TK)  Refer  to  Instruction 
Sheet PF204.
Heaters can be equipped with an optional thermostat of the Bulb 
and Capillary type for automatic temperature control (Figure 8). The 
thermostat  controls  the  heating  elements  and  fan  simultaneously  to 
achieve set temperature.
The “Lo” setting of the thermostat is approximately 40˚F, and the 
“Hi” setting is approximately 90˚F.
Chromalox
Figure 9 — Thermostat Location, Front View









