Specifications

5
1/2" Max
13mm
1/2" Max
13mm
Figure 3
Maximum Out of Plane Allowance
The heaters may be mounted at any convenient height above
floor. The minimum spacings shown in Figure 4 should be
maintained to adjacent walls and ceiling. If floor heat is de-
sired, do not mount higher than 8 to 10 feet above floor.
Controlling thermostats to individual heaters should be
mounted at shoulder height on inside walls or columns and
clear of the discharge air stream of the unit. Allow at least 4 in
front of heater for air stream to discharge freely.
Do not mount mercury type thermostat directly on unit, vibra-
tion could cause malfunction.
Heater may be mounted on a shelf or stand from the bottom.
Be sure that mounting clearances are maintained and that
bottom of unit has at least 1 clearance underneath it. This
is necessary for good air circulation and servicing of heat
exchanger. All mounting methods must allow for removal of
front cover.
The mounting and anchoring provisions must take into ac-
count the unit vibration and cantilevered loading when wall or
pole mounted. One of the Chromalox mounting kits shown in
Figures 5, 6 and 7 must be used whenever possible.
102mm Min. (4")
204mm
Min.
(8")
102mm
Min.
(4")
2"
5/8 NC (2)
Thds. For
Mounting
Figure 4
Installation Clearances