Instruction Manual
Table 20 (Continued) : List of variables that can be included in the STD le
Variables Unit
Phases
L1-L2-L3
N
Total
III
Record
Period
(15)
Direct current -
5 min
Inverse current -
5 min
Current maximum demand A
15 min
Active power maximum demand kW
15 min
Aparent power maximum demand kVA
15 min
Variables Unit Tariff T1 - T2
Record
Period
(5)
Cost
COST
5 min
CO
2
Emissions
kgCO
2
5 min
(15)
Default recording period.
The variable recording period can be congured by the user.
Note: Only 32 variables can be saved at once with a recording period of 1 second.
For example:
Table 21:Example of saving 32 variables with a recording period of 1 second�
Variables L1 L2 L3 Total III
Phase-neutral voltage 1 1 1 1
Phase-phase voltage 1 1 1 1
Current 1 1 1 1
Active power 1 1 1 1
Inductive and Capacitive reactive power 2 2 2 2
Power factor 1 1 1 1
Frequency
1
Flicker
1 1 1
Total off variables 32
Some of the variables in the STD le require an explanation:
Instant Flicker and PST Flicker:
The device will record the instant Flicker and the value obtained during the recording period
(Flicker PST). The PLT value is calculated by the Mobil applications.
Harmonics:
MYeBOX measures and records the average individual harmonic distortion up to the 50th har-
monic, and the voltage and current THD value up to the 40th harmonic. Each record corre-
sponds to a block of 10 cycles, within the recording period.
Unbalance:
The device calculates the coefcients for asymmetry and unbalance in the voltages and cur-
rents of the three-phase system.