Instructions

Table Of Contents
34
MYeBOX 150 - MYeBOX 1500
Instruction Manual
Transients
Transients are detected by checking that the difference between one sample and the next does
not exceed the maximum nominal slope value multiplied by the distortion level coefcient se-
lected by the user (“6.3.4.- TRANSIENTS, DISTURB”).
In this case 128 samples are checked per cycle.
The maximum nominal slope value is the maximum tangent value calculated using a nominal
value selected by the user. By denition, in a sine wave this maximum slope is given by the zero
crossing, therefore the maximum slope is calculated as the value of the sine wave between
sample point 0 (zero crossing) and point 1 (rst sample).
Transients are checked and saved phase by phase. The 3 voltage phases are checked sepa-
rately and when a transient is detected it saves the 15 wave shape cycles of the variable that
caused it.
Example:
Figure 29 shows the disturbances detected when conguring a distortion coefcient of 5�0
Figure 29: Transients detected with a distortion coefcient of 5.0.
Figure 30 shows the disturbances detected when conguring a distortion coefcient of 90�0