Instructions

Table Of Contents
38
MYeBOX 150 - MYeBOX 1500
Instruction Manual
Table 15 (Continued): LED description, MYeBOX 150�
LED Description
Battery
Power on
Green: Battery charge between 70 ... 100 %.
Yellow: Battery charge between 30 ... 70 %.
Red: Battery charge between 5 ... 30 %.
Blinking light (1 s)
Green: Battery not charging, charge between 70 ... 100 %.
Yellow: Battery not charging, charge between 30 ... 70 %.
Red: Battery not charging, charge between 5 ... 30 %.
Blinking light (0�5 s)
Red: Battery not charging, charge < 5%.
USB
Power off
No access to the MicroSD memory; the USB cable does not have to be con-
nected.
Power on
Access to the MicroSD memory is allowed; the USB cable can be connected
to access the memory.
Blinking light (1 s)
Data trafc.
Memory
Power on
Green: Space available in the memory: 55 ... 100 %.
Yellow: Space available in the memory: 25 ... 55 %.
Red: Space available in the memory: 10 ... 25 %.
Blinking light (0�5 s)
Red: Space available in the memory: < 10%.
REC
Power off
Data not being logged.
Power on
Device logging data.
Blinking light (1 s)
Log error or MicroSD memory access error.
U1
U2
U3
UN
Power off
No voltage at the corresponding input. (U1: L1, U2: L2, U3: L3, UN: LN)
Power on
Voltage at the corresponding input. (U1: L1, U2: L2, U3: L3, UN: LN)
Blinking lights U1, U2 and U3 (1 s)
L1-L2-L3 phase sequence error
I1
I2
I3
IN
Power off
Clamp not connected (I1: L1, I2: L2, I3: L3, IN: LN)
Power on
Clamp connected (I1: L1, I2: L2, I3: L3, IN: LN)
Blinking light (1 s)
Negative power or cos < ± 0.6