Instructions
Table Of Contents
- Safety precautions
- DISCLAIMER
- CONTENTS
- Revision log
- SYMBOLS
- 1.- VERIFICATION UPON RECEPTION
- 2.- Product description
- 3.- DEVICE installation
- 3.1.- PRELIMINARY RECOMMENDATIONS
- 3.2.- BATTERY INSTALLATION
- 3.4.- MYeBOX 480V ~ PSU ADAPTER : POWER SUPPLY ADAPTER
- 3.5.- VOLTAGE CABLES
- 3.6.- CURRENT CLAMPS
- 3.7.2.- MYeBOX 1500
- 3.8.- CONNECTION DIAGRAMS
- 3.8.1.- Three-phase network measuring with a 4-wire connection,
- MYeBOX 150.
- 3.8.2.- Three-phase network measuring with a 4-wire connection,
- MYeBOX 1500.
- 3.8.3.- Three-phase network measuring with a 3-wire connection, MYeBOX 150 and MYeBOX1500.
- 3.8.4.- Three-phase network measuring with a 3-wire connection and ARON connection, MYeBOX 150 and MYeBOX 1500.
- 3.8.5.- Two-phase network measuring with a 3-wire connection,
- MYeBOX 150.
- 3.8.6.- Two-phase network measuring with a 3-wire connection,
- MYeBOX 1500.
- 3.8.7. - Single-phase network measurement, phase to phase, with a 2-wire connection, MYeBOX 150 and MYeBOX 1500.
- 3.8.8.- Single-phase network measurement, phase to neutral, with a 2-wire connection, MYeBOX 150.
- 3.8.9.- Single-phase network measurement, phase to neutral, with a 2-wire connection, MYeBOX 1500.
- 3.8.10.- Detail of the current measurement connection.
- 3.8.11.- Leakage current connection, ILeak. (MYeBOX 1500 model)
- 3.9.- REGISTERING AND UPDATING THE DEVICE
- 4.- OPERATION
- 5.- display
- 6.- CONFIGURATION
- 6.2.2.- Measurement name
- 6.2.1.- Name of the device
- 6.1.12.- Exit
- 6.1.11.- Save
- 6.1.10.- Frequency
- 6.1.9.- Primary winding of the leakage current transformer
- 6.1.7.- Primary winding of the neutral current transformer
- 6.1.6.- Neutral clamp scale
- 6.1.5.- Primary winding of the current transformer
- 6.1.4.- Phase clamp scale
- 6.1.3.- Secondary voltage
- 6.1.2.- Primary voltage
- 6.3.2.- Gap, Sag
- 6.3.1.- Overvoltage, swell
- 6.2.5.- Exit
- 6.2.4.- Save
- 6.2.3.- Type of installation
- 6.4.1.- Wi-Fi Configuration
- 6.3.6.- Exit
- 6.3.5.- Save
- 6.3.4.- Transients, Disturb
- 6.3.3.- Outage, Interruption
- 6.4.9.- PIN
- 6.4.8.- APN, password
- 6.4.7.- APN, user
- 6.4.6.- APN, access point name
- 6.4.5.- Enabling 3G communications
- 6.4.4.- Password
- 6.4.3.- WPS
- 6.4.2.- SSID
- 6.5.- SETUP MENU: MEMORY SETUP
- 6.6.- SETUP MENU: RESET FACTORY SETUP
- 6.1.1.- Rated voltage
- 6.1.8.- Clamp scale for measuring the leakage current, ILeak
- 7.- WIRELESS COMMUNICATIONS
- 8.- MOBILE APPLICATION MYeBOX
- 9.- mYeBOX Cloud
- 10.- software UPDATE
- 11.- TECHNICAL FEATURES
- 12.- Maintenance AND TECHNICAL SERVICE
- 13.- GUARANTEE
- 14.- CE CERTIFICATE
46
MYeBOX 150 - MYeBOX 1500
Instruction Manual
Table 20 (Continued) : List of variables that can be included in the STD le
Variables Unit
Phases
L1-L2-L3
N
Total
III
Record
Period
(15)
Direct current -
5 min
Inverse current -
5 min
Current maximum demand A
15 min
Active power maximum demand kW
15 min
Aparent power maximum demand kVA
15 min
Variables Unit Tariff T1 - T2
Record
Period
(5)
Cost
COST
5 min
CO
2
Emissions
kgCO
2
5 min
(15)
Default recording period.
The variable recording period can be congured by the user.
Note: Only 32 variables can be saved at once with a recording period of 1 second.
For example:
Table 21:Example of saving 32 variables with a recording period of 1 second�
Variables L1 L2 L3 Total III
Phase-neutral voltage 1 1 1 1
Phase-phase voltage 1 1 1 1
Current 1 1 1 1
Active power 1 1 1 1
Inductive and Capacitive reactive power 2 2 2 2
Power factor 1 1 1 1
Frequency
1
Flicker
1 1 1
Total off variables 32
Some of the variables in the STD le require an explanation:
Instant Flicker and PST Flicker:
The device will record the instant Flicker and the value obtained during the recording period
(Flicker PST). The PLT value is calculated by the Mobil applications.
Harmonics:
MYeBOX measures and records the average individual harmonic distortion up to the 50th har-
monic, and the voltage and current THD value up to the 40th harmonic. Each record corre-
sponds to a block of 10 cycles, within the recording period.
Unbalance:
The device calculates the coefcients for asymmetry and unbalance in the voltages and cur-
rents of the three-phase system.