Instructions

Table Of Contents
62
MYeBOX 150 - MYeBOX 1500
Instruction Manual
6�1�2�- PRIMARY VOLTAGE
This screen is used to congure the primary winding of the voltage transformer.
000001
PRIMARY VOLTAGE
Press the key to enter edit mode.
Use the and keys to write or change the value of the blinking digit.
When the value on the screen is as desired, use the and keys to move the editing cur-
sor.
Minimum conguration value: 1 V.
Maximum conguration value: 500000 V.
Press the key to conrm.
Use the and keys to toggle between the menu’s setup screens.
6�1�3�- SECONDARY VOLTAGE
This screen is used to congure the secondary winding of the voltage transformer.
001.5
SECONDARY VOLTAGE
Press the key to enter edit mode.
Use the and keys to write or change the value of the blinking digit.
When the value on the screen is as desired, use the and keys to move the editing cur-
sor.
Minimum conguration value: 1.0 V.
Maximum conguration value: 999.9 V.
Press the key to conrm.
Use the and keys to toggle between the menu’s setup screens.