Instructions

Table Of Contents
70
MYeBOX 150 - MYeBOX 1500
Instruction Manual
Minimum conguration value: 50%
Maximum conguration value: 97%
Note: Set the value to 0 to stop recording gaps.
Press the key to conrm.
Use the and keys to toggle between the menu's setup screens.
6�3�3�- OUTAGE, INTERRUPTION
This screen is used to congure the threshold value for logging outages, as a percentage of the
rated voltage value.
010%
CORTE / INTERRUPTION
Press the key to enter edit mode.
Use the and keys to write or change the value of the blinking digit.
When the value on the screen is as desired, use the and keys to move the editing cur-
sor.
Minimum conguration value: 1%
Maximum conguration value: 20%
Note: Set the value to 0 to stop recording outages.
Press the key to conrm.
Use the and keys to toggle between the menu's setup screens.
6�3�4�- TRANSIENTS, DISTURB
This screen is used to congure the distortion level coefcient for the detection of transients.
002.0
TRANSITORIO/DISTURB
Press the key to enter edit mode.
Use the and keys to write or change the value of the blinking digit.
When the value on the screen is as desired, use the and keys to move the editing cur-
sor.
Minimum conguration value: 1.0
Maximum conguration value: 100.0
Note : Recommended value 5.0
Note: Set the value to 0 to stop detecting transients.