Instructions

Table Of Contents
86
MYeBOX 150 - MYeBOX 1500
Instruction Manual
(Continued) Accuracy of measurements
(19)
Power factor measurement Class 0.5 (IEC 61557-12)
Voltage THD measurement Class I (IEC 61000-4-7)
Voltage harmonics (up to 50th order) Class I (IEC 61000-4-7)
Current THD measurement Class I (IEC 61000-4-7)
Current harmonics (up to 50th order) Class I (IEC 61000-4-7)
Pinst Flicker 3 % (IEC 61000-4-15)
Pst Flicker 5 % (0.2 ... 10Pst) (IEC 61000-4-15)
Voltage unbalance Class A (IEC 61000-4-30)
Voltage asymmetry Class A (IEC 61000-4-30)
Current unbalance Class A (IEC 61000-4-30)
Current asymmetry Class A (IEC 61000-4-30)
(19)
Accuracy is given by the following measurement conditions for input 2V: exclusion of errors produced by the
clamps and external voltage transformers, with a range in temperature of 5 ... 45 ºC and power factor 0 ... 1.
(20)
Depending on model.
Transistor digital outputs (MYeBOX 1500 model)
Quantity 2
Type Transistor
Maximum voltage 48 V
Maximum current 90 mA
Digital inputs (MYeBOX 1500 model)
(21)
Quantity 2
Type Potential-free contact
Insulation 2.7 kV
Maximum short-circuit current 5 mA
Maximum voltage in open circuit
4 ... 9 V
Maximum frequency 100 Hz
(21)
Must be connected to SELV circuit.
Wi-Fi communications
Band 2.4 GHz
Standards IEEE 802.11 b / g / n
Output power 20 dBm
Effective radiated power (ERP) < 57 dBm
Effective isotropic radiated power
(EIRP)
17 dBm
Power of the transmitter 17 dBm
Specic absortion rate (SAR) 0.08 W/Kg
3G Communications (MYeBOX 1500 model)
Networks : MYeBOX 1500-3G
UMTS/HSPA: 850/900/1900/2100 MHz
GSM/GPRS/EDGE: 850/900/1800/1900 MHz
Networks : MYeBOX 1500-3G_CA
UMTS/HSPA/HSPA+: 850/1900/2100 MHz
GSM/GPRS/EDGE: 850/900/1800/1900 MHz
Networks : MYeBOX 1500-3G_XP
UMTS/HSPA/HSPA+: 900/2100 MHz
GSM/GPRS/EDGE: 850/900/1800/1900 MHz
Maximum output power
UMTS/3G (Power Class 3): 24 dBm
GSM850/900 (Power Class 4): 33 dBm
GSM1800/1900 (Power Class 1): 30 dBm