Instructions

Table Of Contents
61
Instruction Manual
MYeBOX 150 - MYeBOX 1500
If from any setup menu screen no key is pressed for 5 minutes, the device quits the setup menu
and returns to the Phase-Neutral Voltages screen of the Measure display menu.
Note: Setup menu changes must be made while data logging is off.
6.1.- SETUP MENU: MEASURE SETUP
Figure 50 shows the main screen of the Measure setup menu, where the device’s measurement
parameters are congured.
MEASURE SETUP
Figure 50:Measure setup menu, main screen�
Press the key to enter the setup menu.
6�1�1�- RATED VOLTAGE
This screen is used to congure the rated phase - neutral voltage value.
OOO230.50
NOMINAL VOLTAGE
Press the key to enter edit mode.
Use the and keys to write or change the value of the blinking digit.
When the value on the screen is as desired, use the and keys to move the editing cur-
sor.
Minimum conguration value: (Rated Voltage / Voltage Ratio) ≥ 50.
Maximum conguration value: (Rated Voltage / Voltage Ratio) ≤ 1000.
Maximum possible voltage ratio: 9999.
Note: The voltage ratio is the ratio between the primary and secondary voltage.
Press the key to conrm.
Use the and keys to toggle between the menu’s setup screens.