Network Router User Manual
2-3
Cisco 7609 Internet Router Installation Guide
OL-5079-04
Chapter 2 Preparing for Installation
Site Requirements
Table 2-2 AC Power Requirements and Heat Dissipation
Model Number/
Module Type
AC-Input
Power
(Watts)
DC-Output
Power
(Watts)
Heat Diss.
(BTU/HR)
Input Current
90 VAC
(Amps)
120 VAC
(Amps)
180 VAC
(Amps)
240 VAC
(Amps)
Cisco 7609 Internet Router
chassis (with fans)
155 75 530 1.71 1.29 0.86 0.65
WS-X6K-S2U-MSFC2 181.65 129 549 1.79 1.34 0.89 0.67
OSM-2OC12-POS-MM,
-SI, -SL
OC-12 POS, 2-port
176 141 602 1.96 1.47 0.98 0.74
OSM-4OC12-POS-MM,
-SI, -SL
OC-12 POS, 4-port
251 201 857 2.79 2.09 1.39 1.05
OSM-4OC12-POS-SI+
OC-12 POS, 4-port
239 191 816 2.65 1.99 1.33 1.00
OSM-4OC3-POS-SI
OC-3 POS, 4-port
128 102 437 1.42 1.07 0.71 0.53
OSM-8OC3-POS-MM,
-SI, -SL
OC-3 POS, 8-port
187 150 640 2.08 1.56 1.04 0.78
OSM-16OC3-POS-MM,
-SI, -SL
OC-3 POS, 16-port
267 214 913 2.97 2.23 1.48 1.11
OSM-16OC3-POS-SI+
OC-3 POS, 16-port
252 202 861 2.80 2.10 1.40 1.05
OSM-2OC12-ATM-MM,
-SI
OC-12 ATM, 2-port
190 152 649 2.11 1.58 1.06 0.79
OSM-2OC12-ATM-MM+,
-SI+
OC-12 ATM, 2-port
210 168 717 2.33 1.75 1.17 0.88
OSM-1OC48-POS-SS, -SI,
-SL
OC-48 POS, 1-port
223 179 762 2.48 1.86 1.24 0.93