User Manual

Base Station User Manual Navini Networks, Inc.
General Specifications
Input Power
The BTS requires +21 to 28 VDC power supply rated at 60 amps (combo chassis) and at 50 (RF
shelf) and 20 (Digital shelf) for the split chassis. Installers are referred to industry standards for
power supply installations.
Humidity
The operating environment of the BTS must control relative humidity to 5% to 95% RH, non-
condensing.
Heat Dissipation
The combo BTS chassis, under normal operating conditions, will dissipate a maximum of 1000
Watts or 3415 BTU’s. The split chassis will dissipate a maximum of 1500 watts.
Airflow
Fresh air intake for the BTS chassis is along the lower front vertical panel. Exhaust is out of the
upper rear of the chassis. The I&C crew must ensure there are no obstacles to airflow present in
these areas. Exhaust air from other equipment should not mix with the BTS fresh air intake.
Accessibility
The BTS is intended for installation and use only in a restricted access location.