Chapter 3 Installing the Switch
Connecting DC-Input Power to the Catalyst 4900M Switch
Caution To prevent short circuit or shock hazard after wiring the DC-input power supply, you must reinstall the
terminal block cover.
Figure 3-9 Reinstalling the Terminal Block Cover
Step 10 Remove any safety flag and loc kout devices or any tape from the sou rce DC circuit breake r switch
handle, and restore power by moving the circuit breaker switch handle to the on (|) position.
Step 11 Turn the 1000 W DC-input suppl y on/off switch to ON.
Step 12 Verify that the power supply operation is correct by looking at the power supply front panel power supply
LEDs:
• The INPUT OK LED is green when the source DC voltage measured at the power supply is within
specifications.
• The OUTPUT OK LED is green when the voltages pr ovided by the power supply a re within
specifications.