C H A P T E R 2 Preparing for Installation Note This publication describes the following Cisco 7600 series routers: • Cisco 7603 Router—CISCO7603 • Cisco 7603-S Router—CISCO7603-S • Cisco 7604 Router—CISCO7604 • Cisco 7606 Router—CISCO7606 • Cisco 7606-S Router—CISCO7606-S • Cisco 7609 Router—CISCO7609 • Cisco 7609-S Router—CISCO7609-S • Cisco 7613 Router—CISCO7613 Information on the Cisco 7609 Router (product number OSR-7609) is in the Cisco 7609 Router Installation Guide, located at th
Chapter 2 Preparing for Installation Site Requirements Warning This unit is intended for installation in restricted access areas. A restricted access area can be accessed only through the use of a special tool, lock and key, or other means of security. Warning Only trained and qualified personnel should be allowed to install, replace, or service this equipment. Warning Read the installation instructions before connecting the system to the power source.
Chapter 2 Preparing for Installation Site Requirements • Caution Never attempt to remove the printed circuit board from the metal carrier. For safety, periodically check the resistance value of the antistatic strap. The measurement should be between 1 and 10 megohm (Mohm). Environmental Requirements Insure adequate spacing between racks using the information in Table 2-1.
Chapter 2 Preparing for Installation Site Requirements Note Table 2-2 • Switch fabric modules—Table 2-6 • 10-Gigabit Ethernet modules—Table 2-7 • Gigabit Ethernet modules—Table 2-8 • 10/100/1000 Ethernet modules—Table 2-9 • Fast Ethernet switching modules—Table 2-10 • 10/100 Ethernet switching modules—Table 2-11 • 10BASE Ethernet switching modules—Table 2-12 • FlexWAN and Enhanced FlexWAN modules—Table 2-13 • Service modules—Table 2-14 • SPA Interface Processors (SIPs)—Table 2-15 •
Chapter 2 Preparing for Installation Site Requirements Table 2-2 Power Requirements and Heat Dissipation—Chassis and Fan Trays (continued) AC Model Number/ Module Type DC Module Module Current (A) Power (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) 7.10 372.75 1272.94 400.81 1368.75 Cisco 7613 chassis WS-C6K-13SLOT-FAN2 fan tray Note 298.20 The module power values are based on 42 VDC.
Chapter 2 Preparing for Installation Site Requirements Table 2-3 Power Requirements and Heat Dissipation—Supervisor Engines (continued) AC DC Model Number/ Module Type Module Module Current (A) Power (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) WS-SUP32-10GE-3B Supervisor Engine 32 with PFC3B and MSFC2A daughter cards 4.19 175.98 219.98 751.21 236.53 807.76 WS-SUP32-GE-3B Supervisor Engine 32 with PFC3B and MSFC2A daughter cards 3.
Chapter 2 Preparing for Installation Site Requirements Table 2-4 Power Requirements and Heat Dissipation—Policy Feature Cards (PFCs) AC DC Model Number/ Module Type Module Module Current (A) Power (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) VS-F6K-PFC3C Policy Feature Card 3C 1.90 79.80 99.75 340.65 107.26 366.29 VS-F6K-PFC3CXL Policy Feature Card 3CXL 2.50 105.00 131.25 448.22 141.13 481.
Chapter 2 Preparing for Installation Site Requirements Table 2-5 Power Requirements and Heat Dissipation—Distributed Forwarding Cards (DFCs) (continued) AC Model Number/ Module Type Module Module Current (A) Power (Watts) DC AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) WS-F6700-DFC3A 3.00 Distributed Forwarding Card 3A 126 157.5 537.86 169.35 578.35 WS-F6700-DFC3B 2.7 Distributed Forwarding Card 3B 113.40 141.75 484.08 152.42 520.
Chapter 2 Preparing for Installation Site Requirements Table 2-7 lists the power and the heat numbers for the 10-Gigabit Ethernet modules. Note Table 2-7 For all WS-X67xx modules, the values shown are for the baseboard only. When the baseboard has a CFC or DFC3 daughter card installed, you must add the daughter card power to the baseboard power to get the total slot power.
Chapter 2 Preparing for Installation Site Requirements Table 2-8 Power Requirements and Heat Dissipation—Gigabit Ethernet Modules (continued) AC DC Model Number/ Module Type Module Module Current (A) Power (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) WS-X6416-GE-MT 8-port 1000BASE-SX Gigabit Ethernet module 2.50 105.00 131.25 448.22 141.13 481.96 WS-X6516-GBIC 16-port 1000BASE-X Gigabit Ethernet module 3.40 142.80 178.50 609.58 191.
Chapter 2 Preparing for Installation Site Requirements Table 2-9 Power Requirements and Heat Dissipation—10/100/1000 Ethernet Switching Modules (continued) AC Model Number/ Module Type Module Module Current (A) Power (Watts) DC AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) 2.68 WS-X6148A-GE-45AF 48-port 10/100/1000 Ethernet module with WS-F6K-GE48-AF PoE daughter card 112.56 140.70 480.49 151.29 516.
Chapter 2 Preparing for Installation Site Requirements Table 2-10 Power Requirements and Heat Dissipation—Fast Ethernet Switching Modules AC DC Model Number/ Module Type Module Module Current (A) Power (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) WS-X6324-100FX-SM 24-port 100BASE-FX Ethernet module, SMF 1.52 63.84 79.8 272.52 85.81 293.03 WS-X6524-100FX-MM 24-port 100BASE-FX Ethernet module 1.90 79.8 99.75 340.65 107.3 366.
Chapter 2 Preparing for Installation Site Requirements Table 2-11 Power Requirements and Heat Dissipation—10/100 Ethernet Switching Modules (continued) AC Model Number/ Module Type Module Module Current (A) Power (Watts) DC AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) WS-X6148X2-RJ-45 2.65 96-port 10/100 Ethernet module 111.30 139.13 475.11 149.60 510.87 3.07 WS-X6148X2-45AF 96-port 10/100 Ethernet module with WS-F6K-FE48X2-AF PoE daughter card 128.
Chapter 2 Preparing for Installation Site Requirements Table 2-13 lists the power and the heat numbers for the FlexWAN and the enhanced FlexWAN modules. Table 2-13 Power Requirements and Heat Dissipation—FlexWAN and Enhanced FlexWAN Modules AC DC Model Number/ Module Type Module Module Current (A) Power (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) WS-X6182-2PA FlexWAN module 2.38 99.96 125 426.7 134.35 458.
Chapter 2 Preparing for Installation Site Requirements Table 2-14 Power Requirements and Heat Dissipation—Service Modules (continued) AC DC Model Number/ Module Type Module Module Current (A) Power (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) WS-SVC-NAM-1 Network Analysis Module 1 2.89 121.38 151.73 518.14 163.15 557.14 WS-SVC-NAM-2 Network Analysis Module 2 3.47 145.74 182.18 622.13 195.89 668.
Chapter 2 Preparing for Installation Site Requirements Table 2-16 Power Requirements and Heat Dissipation—Ethernet Services AC DC Model Number/ Module Type Module Module Current (A) Power @ 42 VDC (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) 7600-ES20-GE3CXL 8.11 341 426 1454 458 1563 7600-ES20-GE3C 8.11 341 426 1454 458 1563 7600-ES+2TGCXL 7.06 297 371.25 1267.81 399.19 1363.24 7600-ES+2TG3C 6.38 268 335 1144.02 360.
Chapter 2 Preparing for Installation Site Requirements Table 2-17 Power Requirements and Heat Dissipation—OSMs AC DC AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) 203 254 868 271 925 3.61 152 190 649 204 698 4.00 168 210 717 226 771 OSM-1OC48-POS-SS, -SI, -SL 4.26 OC-48 POS, 1-port 179 223 762 240 819 OSM-1OC48-POS-SS+, -SI+, -SL+ OC-48 POS, 1-port 3.90 164 205 699 220 752 OSM-12CT3/DS0 Channelized T-3 to DS-0, 12-port 2.
Chapter 2 Preparing for Installation Site Requirements Table 2-18 Power Requirements and Heat Dissipation—Miscellaneous Modules AC DC Model Number/ Module Type Module Module Current (A) Power @ 42 VDC (Watts) AC-Input Power (Watts) Heat Diss. (BTU/HR) DC-Input Power (Watts) Heat Diss. (BTU/HR) WS-X6066-SLB-APC Content Switching Module 3.0 157.5 537.9 169.35 578.35 126.
Chapter 2 Preparing for Installation Power Connection Guidelines • In some systems, you might use an uninterruptible power supply (UPS) to protect against power failures at your site. Avoid UPS types that use ferroresonant technology. These UPS types can become unstable with systems like the Cisco 7600 series router, which can have substantial current draw fluctuations due to bursty data traffic patterns.
Chapter 2 Preparing for Installation Power Connection Guidelines Warning This product requires short-circuit (overcurrent) protection, to be provided as part of the building installation. Install only in accordance with national and local wiring regulations. Table 2-20 lists the AC-input power cord options, specifications, and Cisco product numbers for the 950 W, 1400 W, 1900 W, 3000 W, 4000 W, and the 6000 W AC-input power supplies. Table 2-20 also references power cord illustrations.
Chapter 2 Preparing for Installation Power Connection Guidelines Table 2-20 AC-Input Power Cord Options (continued) Locale Part Number Length Plug Rating Power Cord Reference Illustration North America (locking) CAB-GSR16-US(=) 14 feet (4.3m) 250VAC, 20A Figure 2-17 Europe CAB-GSR16-EU(=) 14 feet (4.3m) 250VAC, 16A Figure 2-17 International CAB-AC16A-90L-IN(=) 14 feet (4.3m) 250VAC, 16A Figure 2-17 China CAB-AC16A-CH= 14 feet (4.
Chapter 2 Preparing for Installation Power Connection Guidelines Table 2-20 AC-Input Power Cord Options (continued) Plug Rating Power Cord Reference Illustration Locale Part Number Length Japan, North America 100–120VAC operation3 CAB-7513AC= 14 feet (4.3 m) 20 A, 125 VAC Figure 2-12 Switzerland CAB-ACS-16= 14 feet (4.3 m) 16 A, 250 VAC Figure 2-15 China CAB-AC16A-CH= 14 feet (4.3 m) 16 A, 250 VAC Figure 2-23 Australia, New Zealand CAB-AC-16A-AUS= 14 feet (4.
Chapter 2 Preparing for Installation Power Connection Guidelines AC Power Cord Illustrations This section contains the AC power cord illustrations. Note that an AC power cord may be used with several power supplies. See the power supply specifications tables for the correct AC power cord illustrations for your power supply. Figure 2-1 CAB-AC15A-90L-US(=) Plug: NEMA 5-15 Cordset rating: 15 A, 125 V Length: 8 ft 2 in. (2.
Chapter 2 Preparing for Installation Power Connection Guidelines Figure 2-3 CAB-AC10A-90L-UK(=) Cordset rating: 10 A, 250 V Length: 8 ft 2 in. (2.5 m) Plug: BS 1363 Connector: IEC 60320 C15 113345 13 A fuse Figure 2-4 CAB-AC10A-90L-IT(=) Plug: CEI 23-16/7 Cordset rating: 10 A, 250 V Length: 8 ft 2 in. (2.5 m) 113343 Connector: IEC 60320 C15 Figure 2-5 CAB-AC10A-90L-AU(=) Plug: SAA AS 3112 Cordset rating: 10 A, 250 V Length: 8 ft 2 in. (2.
Chapter 2 Preparing for Installation Power Connection Guidelines Figure 2-6 CAB-7513ACR= Plug: IRAM 2073 Cordset rating: 10 A, 250 V Length: 14 ft 0 in. (4.26 m) 113352 Connector: IEC 60320 C19 Figure 2-7 CAB-7513ACA= Plug: SAA AS 3112 Cordset rating: 15 A, 250 V Length: 14 ft 0 in. (4.26 m) 113353 Connector: IEC 60320 C19 Figure 2-8 CAB-7513ACE= Plug: CEE 7/7 Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.
Chapter 2 Preparing for Installation Power Connection Guidelines Figure 2-9 CAB-2500W-EU= Plug: CEE 7/7 Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) 113360 Connector: IEC 60320 C19 Figure 2-10 CAB-AC-2500W-INT= Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) Plug: IEC 309 113361 Connector: IEC 60320 C19 Figure 2-11 CAB-7513ACI= Plug: CEI 23-16/7 Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.
Chapter 2 Preparing for Installation Power Connection Guidelines Figure 2-12 CAB-7513AC= Plug: NEMA 5-20 Cordset rating: 20 A, 125 V Length: 14 ft 0 in. (4.26 m) 113356 Connector: IEC 60320 C19 Figure 2-13 CAB-AC-C6K-TWLK= Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) Connector: IEC 60320 C19 113363 Plug: NEMA L6-20 Figure 2-14 CAB-7513ACSA= Plug: IEC 884 Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.
Chapter 2 Preparing for Installation Power Connection Guidelines Figure 2-15 CAB-ACS-16= Connector: IEC 60320 C19 113364 Plug: SEV 5934-2 Type 23 Cordset rating: 16 A, 250 V Length: 8 ft 2 in. (2.5 m) Figure 2-16 CAB-7513ACU= Plug: BS 1363 113359 13A replaceable fuse Cordset rating: 13 A, 250 V Length: 14 ft 0 in. (4.
Chapter 2 Preparing for Installation Power Connection Guidelines Figure 2-18 CAB-AC-2500W-EU= Plug: CEE 7/7 Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) 113360 Connector: IEC 60320 C19 Figure 2-19 CAB-AC-2500W-US1= Plug: NEMA 6-20 Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) 113362 Connector: IEC 60320 C19 Cordset rating: 30 A, 250 V Length: 12 ft 0 in. (3.
Chapter 2 Preparing for Installation Power Connection Guidelines Figure 2-21 WS-CAC-4000W-INT= Hardwired to power supply 113365 Cordset rating: 32 A, 250 V Length: 12 ft 0 in. (3.65 m) Plug: IEC 60309 Figure 2-22 CAB-ACS-10= Plug: SEV 1011 Cordset rating: 10 A, 250 V Length: 7 ft 0 in. (2.13 m) 113358 Connector: IEC 60320 C19 Figure 2-23 CAB-AC16A-CH= Connector: IEC 60320-1 C19 126792 Plug: GB16C Cordset rating: 16A, 250V Length: 14 ft 0 in. (4.
Chapter 2 Preparing for Installation Power Connection Guidelines Figure 2-24 CAB-AC-2500W-ISRL= Plug: SI16S3 Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) 130113 Connector: IEC 60320 C19 Figure 2-25 CAB-AC-16A-AUS Plug: AU20S3 Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) 140586 Connector: IEC 60320 C19 Connector: IEC 60320 C20 Connector: IEC 60320 C19 Cordset rating: 16 A, 250 V Length: 9 ft 0 in. (2.
Chapter 2 Preparing for Installation Site Planning Checklist Caution • The circuit breaker is considered the disconnect device and should be easily accessible. • The system ground is the power supply and chassis ground. Do not connect the DC-return wire to the system frame or to the system grounding equipment. Site Planning Checklist Table 2-21 lists the site planning activities that you should perform prior to installing the Cisco 7600 series router.