Data Sheet

Type 2 surge protector for Photovoltaic
PV voltage: 600 Vdc
In: 15 kA
Imax: 40 kA
Pluggable module
Remote signaling (option)
UTE C61-740-51, EN 50539-11 compliance
V: High-energy varistor
Ft: Thermal fuse
t°: Thermal disconnection system
MI: Disconnection indicator
Caractéristiques Électriques
SPD type (followingIECtests) 2
Network PV network 600 Vdc
Nominal PV voltage Uocstc 600 Vdc
Max. PV operating voltage Ucpv 720 Vdc
Residual Current(LeakagecurrenttoGround) Ipe < 0.1 mA
PV Permanent Operating current
(CurrentconsumptionatUcpv)
Icpv < 0.1 mA
Follow current If None
Nominal discharge current (15x8/20µsimpulses) In 15 kA
Max. discharge current(max.withstand@8/20µsbypole) Imax 40 kA
Total Maximal discharge current
(max.totalwithstand@8/20µs)
Imax Total 60 kA
Current withstand short circuit PV Iscpv 15000 A
Connection mode(s) +/-/PE
Protection mode(s) Common mode
Protection level +/PE (-/PE)(@In(8/20µs)) Up 2.8 kV
Caractéristiques Mécaniques
Technology MOV
Connection to Network Screw terminals: 2.5-25 mm²
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (DIN 60715)
Housing material Thermoplastic UL94-V0
Operating temperature Tu -40/+85°C
Protection rating IP20
Failsafe mode Disconnection SPD of the PV line
Disconnection indicator 2 mechanical indicators - Green/Red
Spare module(s) DSM50PV-600/51
Remote signaling of disconnection Option DS50PVS-600/51 - output on changeover contact
Dimensions See diagram
Weight 0.249 kg
Déconnecteurs associés
Thermal disconnector internal
Fuses Without
Normes
Standards compliance EN 61643-31 / NF EN 50539-11
Certification EAC
Code article
480421
Type 2 PV surge protector
DS50PV-600/51
PHOTOVOLTAIC
1 / 1