Owner’s Operating Manual S SERIES CONTINUOUS POWER SYSTEM MODELS COVERED: S1000 S1250 S1500 S2000 S2400 CLARY SCIENTIFIC INC. 1960 S. Walker Avenue Monrovia, California 91016 Telephone 626-359-4486 800-44 CLARY Fax. 626-305-0254 World Wide Web HTTP: // WWW.CLARY.COM E-Mail SALES @ CLARY.
THE CONTINUOUS POWER COMPANY TABLE OF CONTENTS TITLE PAGE TABLE OF CONTENTS..................................................................................................... 2 INTRODUCTION................................................................................................................ 3 TECHNICAL DESCRIPTION ............................................................................................. 4 PACKAGING ...........................................................................
THE CONTINUOUS POWER COMPANY INTRODUCTION C ongratulations! You have selected the highest quality protection for your continuous power needs. This unit offers a quiet and compact package with superior performance you can depend on. You now own a S Series Continuous Power System (CPS) which is an all Digital Technology product manufactured by Clary Corporation, the first name in uninterruptible power system (UPS) reliability.
THE CONTINUOUS POWER COMPANY TECHNICAL DESCRIPTION T Only after properly rated power is returned, does the microprocessor reconnect the input source back into the system. The microprocessor is directly tied to an external RS232 connector port. This allows the user to monitor and even set some of the operating parameters.
THE CONTINUOUS POWER COMPANY DB-9 CONTACTS DB-9 RS232 UTILITY INPUT INPUT ISOLATION TRANSFORMER MICROPROCESSOR CONTROLLER COMMON MODE CHOKE VOLTAGE WINDOW DETECTOR POWER FACTOR CORRECTOR RECTIFIER EMERGENCY CUTOFF SWITCH + DC RAILS AC INVERTER GENERATOR STANDBY BATTERY CHARGER BYPASS LINE FIGURE 1: S SERIES BLOCK DIAGRAM FIGURE 1:S SERIES BLOCK DIAGRAM COMMON MODE CHOKE LOAD
THE CONTINUOUS POWER COMPANY PACKAGING Y our UPS has been carefully packaged to withstand most abuse sustained during shipment. The packing material has been specifically designed to protect this system for normal handling, using most shipping carriers. If there is significant damage to the carton, or if there is any physical damage to this unit, report this to your carrier. These units are encapsulated in a protective wrap that comes apart once the product is removed from the shipping carton.
THE CONTINUOUS POWER COMPANY PHYSICAL DESCRIPTION T his section will point out and illustrate the various indicators, functions and controls of the S Series UPS. Pictured is the front view of the system, then followed by the rear view. The important attributes of the S Series unit are numbered to assist you in locating them on your machine and also to fully explain its function and how it relates to system operation.
THE CONTINUOUS POWER COMPANY 8 9 10 11 6 7 13 12 UPS COMPARTMENT 14 AIR INTAKE, COOLING 3 2 4 LIFTING HANDLE 5 1 TRANSFORMER COMPARTMENT FIGURE 4: FRONT VIEW, S1000 – S2000 FRONT PANEL CALLOUTS 1 2 3 4 5 6 7 8 SYSTEM POWER SWITCH AC In - Input line indicator Inverter - Inverter operating indicator Battery Level - Charge/discharge indicators Load Level - Output capacity indicators Cold Start - DC start switch COLD START ACKNOWLEDGE INDICATOR Load I - Enable switch for top output receptacles
THE CONTINUOUS POWER COMPANY 19 20 LIFTING HANDLE 23 18 22 15 17 16 21 FIGURE 5: REAR VIEW, S1000 REAR PANEL CALLOUTS 15 16 17 18 INPUT AC Line cord (1000-1500VA) NEMA 5-15P (2000VA-2400VA) NENA 5-20P INPUT LINE FUSE – Input line protection DC INPUT - Auxiliary battery connector 120VAC OUTPUT System output 19 20 21 22 23 Page 9 SIGNAL - Open-collector signal contacts RS232 - Computer communications signals IDENTIFICATION LABEL SNMP – (Optional) Slot for network monitoring OUTPUT FUSES – Output
THE CONTINUOUS POWER COMPANY 20 LIFTING HANDLE 19 AIR EXHAUST, COOLING 18 22 UPS COMPARTMENT 23 16 17 TRANSFORMER COMPARTMENT 15 21 FIGURE 6: REAR VIEW, S1250 – S2000 Page 10
THE CONTINUOUS POWER COMPANY SUMMARY OF INDICATORS AND CONTROLS SYSTEM POWER SWITCH - The main control switch that engages utility power to the entire unit. By activating this switch it initializes normal operation. AC In - The utility input indicator that identifies status of the line voltage. If the line voltage is within the specified range, it will remain lit. If the AC input is out of range, this indicator will flash in 1 to 2 second intervals.
THE CONTINUOUS POWER COMPANY INSTALLATION T he UPS unit is designed for installation in a protected environment. Some important points to consider when positioning a unit for operation: WARNING: This product not intended for providing power to life support equipment. A properly rated (preferably dedicated) outlet is accessible for the six-foot power cord, supplied with the unit. It is not recommended to modify the supplied cord in any way nor should an extension cord of any kind be used.
THE CONTINUOUS POWER COMPANY OPERATION O nce the system has been properly installed, it is ready to operate. The following procedures will explain how to start-up the system while plugged into rated electrical power and also how to start-up with no AC power available. Normal Operation on AC Start-Up: • Verify that the unit is plugged into properly rated electrical power. • Position the System Power Switch to the ON position.
THE CONTINUOUS POWER COMPANY SIGNALS AND INTERFACING t the rear of the unit are two DB-9 subminiature, female connectors. These are provided for communications links to a computer or sophisticated monitoring device. SIGNAL provides open-collector outputs that typically signal Utility Interrupt and Low Battery conditions. A system shutdown feature is also available on this port. Applying a short between Pin 6 and Pin 7 will cause the system to shutdown in battery mode.
THE CONTINUOUS POWER COMPANY SPECIFICATIONS ELECTRICAL DESIGN Input Standard Features Power Factor Corrected, Digital Regenerative™ On-Line, Sinewave Inverter Powers Load Continuously Extended Brownout Protection Designed for Non-linear Loads Continuous Operation on -20%,+12% Line Automatic Bypass RS232 Data Interface Software Selectable Output Frequency AC Output Switch Auxiliary Battery Connector Optional SNMP Interface UL Design FCC Class A IEEE 587/ANSI C62.
THE CONTINUOUS POWER COMPANY MODEL SELECTION GUIDE MODEL NUMBER DESCRIPTION S1000 S1250 S1500 S2000 Nominal VA (Max Watts) Input Current Amps (@120VAC) Output Current Amps Input Plug (Standard) 1000 (700) 1250 (875) 1500 (1050) 2000 (1400) 7.2 8.8 10.7 14.3 8.3 10.4 12.5 16.7 5-15P 5-15P 5-15P 5-20P 5/17 7/21 5/17 5/18 55 (25) 80 (36) 80 (36) 100 (45) NEMA Type Battery Backup Time Minutes @100%/@50% Load Weight lbs(kg) Dimensions HxWxD in(cm) 9.1(23) x 6.9 (17.
THE CONTINUOUS POWER COMPANY CARE AND MAINTENANCE T his device is designed to be maintenance-free. It can be cleaned with a damp cloth or nonabrasive cleanser. WARNING: Do not use ACETONE-BASE cleaning solutions. Keep cleaning solutions out of the electrical receptacles on this device. Be sure filters, vents and fans are kept free from accumulation of dust, dirt or lint.
THE CONTINUOUS POWER COMPANY SERVICE AND REPAIR Y our S Series UPS is backed by one of the finest customer service teams available. Write or call them at any time to obtain more information about your unit. The RMA number issued to you should appear on the outside of the carton, if the unit is returned, or on any correspondence regarding your unit. When shipping a unit back to the factory, try to use the original packing container and shipping materials.
THE CONTINUOUS POWER COMPANY LIMITED WARRANTY SCIENTIFIC LIMITED WARRANTY S1000, 1250, 1500 and 2000 DEPOT REPAIR 1. TIME AND SCOPE OF WARRANTY: 1.1 Clary Scientific, (hereafter referred to as Clary) hereby warrants part shipped under this agreement to be free from defective workmanship for a period as stated below, following the date of shipment /accidental damage, misuse or normal wear shall not be construed as a defect.