Specifications
1
Updated – October 2013
4109 Capital Circle
Janesville, WI
USA 53546
www.cleanburn.com
SPECIFICATIONS FOR CLEAN BURN WARM AIR FURNACE
MODEL CB-1750 CENTRAL FURNACE
PART 1 – GENERAL
1.1 DEFINITIONS: Throughout this bid specification the word “shall” appears frequently. The
word “shall” indicates a mandatory requirement as per the Codes and Regulations that
are listed in Part 1 – Section 1.4 through 1.4.4 of this bid specification as applicable.
1.2 REQUIREMENTS:
General provisions of the purchase specifications, including general
and other conditions, delivery requirements, shipping and demurrage charges will be
under separate cover and shall apply.
1.3 SCOPE:
This specification covers but is not limited to the furnishing of a CB-1750,
170,000 BTU/hr (input) Central Furnace Package. Thi s package will include the
following:
¾ One (1) CB-1750, 170,000 BTU/hr input central furnace (136,000 BTU/hr output)
¾ One (1) CB-525-S2 used-oil firing burner
¾ One (1) F-180 fan switch
¾ One (1) L-200 high limit switch
¾ One (1) L-290 auxiliary high limit switch (automatic reset)
¾ One (1) Lux Pro PSD Series 45 to 90
o
F 24 vac wall mounted digital thermostat with
positive off position (non mercury)
¾ One (1) Suntec used oil pump assembly (Refer to Part 1 – Sectio n 2.5 for the listed
pump options)
¾ One (1) Oil pump relief valve assembly
¾ One (1) Lenz # DH750-100 canister filter with a washable 100-mesh stainless steel
screen filter element
¾ One (1) Oil vacuum gauge
¾ One (1) ¾” x ¾” in-line brass check valve
¾ One (1) ¾” in-line washable 50-mesh stainless steel screen filter eleme nt for the
check valve
¾ One (1) CB-1750 blower kit with a 3/4 h p motor @ 1,075rpm, semi enclosed, ODP,
PSC, sleeve bearing, cw-se rotation, 48YZ frame, direct drive (resilient) mounted,
5
5
/
8
” diameter fan motor, with a 10 uf (mfd) / 370 vac capacitor, delivering 1,700 cfm
of free air when used as a unit heater (no ductwork added). When adding ductwork
with the louvers fully ope ned and in stalled inside of the ductwork, you si ze the
ductwork fro 0.25” W.C. to deliver 1,550 cfm of d ucted air, or when you remove the
louvers and add ductwork, you size the ductwork for 0.40” W.C. to deliver 1,400 cfm
of ducted air