Specifications

4
2.2.10 The appliance shall be provided with a wrap around 22-gauge, galvaneal steel jacket with
a baked on powder coat finish.
2.2.11 The size, capacity, and operation of t he appliance shall be designed as shown in the
following:
¾ 170,000 BTU/hr input rating
¾ 136,000 BTU/hr output rating
¾ 1.20 gph oil consumption
¾ Dedicated spst 20 amp electrical circuit rated @ 115vac / 60hz / 1 ph, requiring the
installation of a 12/2 copper power supply wire
¾ Dedicated spst 30 amp electrical circuit rated @ 115vac / 60hz / 1 ph (optional –
used when i nstalling a d raft inducer or on-board air compressor), requiring the
installation of a 10/2 copper power supply wire
¾ 2.0 cfm compressed air requirement @ 20 psig
¾ 8” stack size
¾ Cabinet dimensions (from burner end without the burner and the blower assembly
installed) 53” long x 29 ¼” wide x 29 ¼” high
¾ Overall dimensions (from burner end with both the burner and the blower assembly
installed) 83” long x 29 ¼” wide x 29 ¼” high
¾ Approximate shipping weight – 310 lbs
2.3 INSTALLATION:
The ap pliance shall be ceiling hung, mounted on an approved stand,
or installed on a raised platform constructed on a non-combustible (concrete) floor, and
shall be installed as per the Codes and Regulations that are listed in Part 1 – Section 1. 4
through 1.4.4 of this bid specification as applicable.
2.3.1 Appliances that are installed in repair garages shall be installed at least 8 feet above the
floor level a s per the Codes and Regulations that are listed in Part 1 Se ction 1.4
through 1.4.4 of this bid specification as applicable.
2.3.2 The appliance is designed to be installed as either a unit heater without ductwork
installed, or as a central furnace with the properly sized ductwork installed. (Refer to the
CB-1750 Operator’s Manual for the proper static pressure for the sizing of the ductwork).
2.3.3 The appliance shall be supplied with the proper amount of combustion air to permit the
satisfactory combustion of the oil, the prop er venting of the com bustion gases, and to
maintain a safe ambient temperature within the space that the appliance is installed in as
per the Codes and Regulations that are listed in Part1 – Section 1.4 through 1.4.4 of this
bid specification as applicable.
2.3.4 When installing this appliance in a n unconfined space, the minimum amount of
combustion air supplied to this appliance shall be from one permanent opening, installed
within 12” of the ceiling of the room, totaling 39 square inches at a rate of 94 cfm of free
air for a single appliance application as per the Codes and Regulations that are listen in
Part 1 – Section 1.4 through 1.4.4 of this bid specification as applicable. When installing
more than one appliance into the same unconfined space, you must adjust these
minimum requirements to accept all of the appliances within that space.