November 13, 2020 
Mr. John Ruprecht 
Clear View Glass Railings 
737 Quentin Avenue South 
Lakeville, MN 55043 
Re:  Code Requirements & Static Test of Clear View Glass Railings “Hercules Glass” guardrail panel 
AET Project #: 05-20608 
Dear Mr. Ruprecht, 
This letter reports building code requirements for guardrails; it also reports test methods and results for 
static tests performed on Clear View’s Hercules Glass panel. 
The  International  Building  Code  (IBC)  and  International  Residential  Code  (IRC)  are  “model  codes” 
created by the International Code Council, intended to be used by states and municipalities as they publish 
their own building codes. Section 1607.8 of the IBC requires that “handrails and guards shall be designed 
to resist a linear load of 50 plf.” It also requires the system to resist a 200# concentrated load that produces 
the “maximum load effect” on any element within the system. The 2018 IRC Table R201.5 extends this 
requirement into residential construction. It is understood within the building design industry that laterial 
loads applied to the top of the panel create the maximum load effect; structural design assumes this 
loading condition. 
Section 1607.8 of the IBC also refers to IBC section 2407 Glass in Handrails and Guards that adds a 
requirement for all-glass handrails and guards to “be laminated glass constructed of fully tempered or 
heat-strengthened glass”; this requirement was added in the 2015 IBC code cycle. Section 2407.1.1 
adds the significant requirement: “a design factor of four shall be used for safety”. This addition bumps 
up the linear load to 200 plf and the concentrated load to 800#.. 
Exterior glass guardrail panels are designed to resist two load types: wind loads, and “live” loads such 
as a person or object pushing on or striking the panel from the side or from above. Wind loading on a 
panel can vary greatly based on location, terrain (wooded vs open) and elevation above ground; these 
are governed by publication ASCE 7 (American Society of Civil Engineers) Minimum Design Loads 
for Buildings and Other Structures. Wind speeds of 115 psf are used to calculate wind pressures against 
the glass, which generally vary from 17 psf (2
nd
 story in wooded area) to 35 psf (30 stories tall in open 
terrain). The wind speeds required to match the stresses created by the 800# point load are 192 mph for 
the 42” tall panel and 215 mph for the 36” tall panel; these are only seen in a Category 5 hurricane or a 
tornado. Therefore, the 800# horizontal point load requirement is the worst-case scenario for the panels. 
Calculation methods to arrive at these values include computer modeling using finite element analysis, 