Specifications
Refer to section 11.3 for more details on tube replacement.
✖ Hail related damage to the collector is not eligible for warranty claims.
3.17. Lightning Protection
It is  advisable to earth-ground the copper circulation loop of the collector to avoid lightning related damage, 
or  electrical safety  issues.    It  may  also help to prevent galvanic  corrosion  of the copper  pipe which can 
result in blue staining of basins/baths etc.
3.18. Thermo-siphoning
a) Thermo-siphoning (convection) can occur if the solar  loop pump is  off and a low outside air temp makes 
the collector manifold colder than the fluid or water in the mechanical room. Thermo-siphoning occurs when 
hot fluid rises up the Return Lines toward the cooler collector and external piping. After it dissipates  its  heat 
and cools, it falls back down the Supply  (Feed)  Line and cools the tank.   This can occur with direct flow 
systems  or closed loops  with a coil heat exchanger inside the tank.   Thermo-siphoning only occurs  when 
the collector  is  cooler than the tank, so normally at night.  If not controlled it can cause considerable heat 
loss. 
The following methods can be employed to stop thermo-siphoning:
i)  Normally, a check  valve can be installed on the Supply (feed) Line after  the pump and is  enough to 
stop thermo-siphoning. Some pumps have integral check valves, which provide the same benefit.
ii)  If  thermo-siphoning occurs  even with a check  valve installed, a heat trap should be formed in the 
return line (line back  from collector)  close to the tank. The heat trap should be a U-shaped section of 
pipe, extending downward 8-10” and then back  up. Since heat rises, this  downward section of pipe will 
trap hot water and prevent migration of heat up the piping. This  section of pipe in particular should be 
well-insulated. 
3.19. Pressure and Temperature Control and Relief
a) Direct Flow Max Incoming Pressure: For direct flow systems, the normal operating pressure should be 
no greater  than 72.5 psi (500 kPa), if necessary  a pressure limiting (pressure reduction) valve should be 
installed on the main cold feed line. 
b)  Closed  Loop  Max Incoming  Pressure:  For  closed  loop systems,  the  solar  loop must  operate at  no 
greater  than 50 psi (350 kPa) and have an  expansion tank  installed to accept fluid expansion. If  a single 
wall heat exchanger is  used, the solar loop operating pressure must be below the water main pressure. The 
solar  controller  should have a “max  tank temp”  function  to protect the  tank from being overheated.   All 
Apricus controllers provide such this function as standard. Refer to section 6 for more information. 
c) Maximum Allowable Pressure: The maximum allowable operating pressure for the solar collector in any 
system configuration (domestic or  commercial)  is  116 psi  (800 kPa)  with  pressure relief  valve  discharge 
rating at no more than 123 psi (850 kPa) or lower as  specified by local codes  and regulations. Also, check 
the maximum pressure ratings  for all components  of the system and only use products  that can handle the 
operational temperatures and pressures of the system design. 
d)  Stagnation:  For  direct  flow  systems and  closed  loop  systems  with  suitable  heat  transfer fluid,  it  is 
acceptable for  the system design to allow the  solar  collector  to  stagnate (i.e. stop the  pump)  to  prevent 
overheating of the  storage  tank above  ~177
°
F  (~80
°
C). An expansion  tank must  be properly  sized and 
installed to accept the increase in fluid volume due to thermal expansion and potential steam formation, in 
order to minimize or prevent release of fluid from the pressure relief valve.  
e) Heat Transfer Fluid: In a closed loop system, it is  important to use a heat transfer fluid that is  rated to at 
least 320
°
F (160
°
C)  to minimize fluid degradation during periods  of stagnation (see above).  Depending on 
the pressure of the closed loop the fluid may vaporize (boil) during stagnation causing some degradation of 
the fluid. If stagnation happens on a regular basis  due to excessive heat production (heat supply > demand) 
or  power  outages,  an  inspection  of  the  fluid  should  be  completed.  Contact  the  manufacturer  for  more 
information on how to check  the  fluid.  Refer  to Section 3.31 and Appendices  11-17 for heat transfer  fluid 
information.
✖ System pressures that exceed those requirements outlined above will void the warranty.
Apricus Solar Collector Installation & Operation Manual - USA
Copyright © 2011 – Apricus Inc Doc: A7-05.4.12-PB Page 25 of 129










