Specifications
 WARNING
Any  electrical  work  must be  performed  by   a licensed electrician and  adhere  to  local 
electrical safety regulations, as required.
Do not connect controller to power  supply  until all wires are connected and the front case is 
closed.  Also, make sure the controller  does not turn on the pump until it is flooded.   Take 
care when working near electricity, especially in wet areas.
b) In North America, Apricus  controllers  are 110 Volts, 60 Hz. They should not be used with higher voltage 
power supplies.
c)  It  is  highly  recommended  that  the solar  loop (copper  or  stainless steel)  be grounded  to avoid lighting 
related  damage.  In  areas  prone  to  lightning  strikes,  the  power supply  to  the  controller  should  also  be 
suitably protected.
d) The Apricus controllers  are supplied with a standard North American plug. No cutting or extension of the 
cable is permitted unless completed by a qualified electrician.
e) The Apricus  controller is suitable for INDOOR use only.  Also, ensure the operating temperature is  within 
the acceptable range 32
°
F - 122
°
F and the unit is not exposed to high humidity or condensation.
6.5. Controller Functions
a) Controller Purpose:  The primarily purpose of the Apricus controller  is  to regulate the operation of the 
solar  circulation  pump(s).    Many  additional  functions  are  also  available,  including:  regulating  tank 
temperature, providing freeze protection, measuring energy output and more. 
b)  Basic  Operation:  In a  solar  water  heating system,  maximum efficiency  is  attained by  extracting  heat 
from  the  collector  as  quickly  as  possible,  thus  allowing  the  collector  to  run  at  the  lowest possible 
temperature.  The controller achieves  this  by measuring the temperature at the outlet of the solar collector 
and also the bottom of the solar storage tank.   This  temperature difference is  referred to as  a delta-t, often 
written as ∆t.  When the collector is  hotter than the bottom of the tank  by a set amount, usually between 8°F 
and 20°F (5°C and 11°C)  the controller  will supply  power  to the pump which circulates  water through the 
collector.   Once the temperature difference drops  below a minimum the pump turns  off again.   This  cycle 
continues  throughout  the day.  The  frequency and  duration of pump  operation is  dependent  on  solar 
radiation levels.
If  the  variable  speed function  is  activated  (recommended), the  speed  of the  pump  will be  automatically 
regulated by the controller  to maintain an optimum flow rate and keep the collector between the maximum 
and minimum delta-t set levels. This maximizes the system efficiency and also reduces electricity usage. 
c) Basic Functions: Basic functions  for closed loop and direct flow system are presented in sections 7.11.2 
and 8.10.2 respectively. Also, refer  to the system schematics  in the Apricus OG-300 Systems  Manual for 
recommended settings for each system configuration. 
d) Pump Run Times with ON/OFF Pump Control:  The correct delta-t setting (dTMax tank1 & dTMin  tank1) 
will vary  slightly from system to system depending on the flow rate and length of the pipe run.   Optimally, 
each time the pump operates, the heat in the collector is  transferred all the way back to the tank  and is not 
allowed to sit in the Return Line, where it would otherwise loose heat. 
For example: A 16 ft (5 m) pipe run in ½”  copper has  a fluid content of about 0.24 gallons, plus  0.2 gallons 
for  an AP-30 collector.   With a total of 0.44 gallons, a flow  rate of 0.8 gpm would take 20-25 seconds to 
transport the hot fluid in the collector back  to the tank.  A longer  pump run time would waste electricity and 
promote heat loss from the pipes. 
A more common pipe run length of 40 ft (12 m) in ½”  copper has  a fluid content of 0.48 gallons, plus  0.2 
gallons  for  an AP-30 collector.   With a total of 0.68 gallons, a flow  rate of 0.5 gpm would take about 60 
seconds to transport the fluid in the collector back to the tank. 
This  basic calculation can help to  determine how long the pump should be running for  each cycle.   See 
below for  recommended controller settings.   The operation of the pump can be tested by feeling the flow 
and return lines (or using temperature probes if too hot). The pump should turn off shortly after the heat has 
returned back down the return line and the temperature drops to a similar level as the flow line.
Apricus Solar Collector Installation & Operation Manual - USA
Copyright © 2011 – Apricus Inc Doc: A7-05.4.12-PB Page 47 of 129










