Specifications
d) Pressure Relief:  The pressure relief valve is included as a safety device,  designed to open at 75 psi 
should the system pressure rise to that level.  This  may occur if for  example the expansion tank  is  not big 
enough or some blockage occurs that prevent normal operation or extreme overheating occurs.
e)Drain Pipe: The pressure relief valve drain pipe fitting is  a 3/4” FPT connection. Install and tighten drain 
pipe fitting with two wrenches taking special care not to stress the pressure relief valve support pipe.
 WARNING
- Pressure relief valve must NOT be blocked. 
- A drain pipe must be connected to the relief valve. 
- The drain pipe diameter must be no smaller than 3/4” and be able to withstand 
temperature of up to 230
° 
F (110
°
C).
- Pressure relief piping must meet local codes
7.6. Controller Connections
a) The Apricus controller comes pre-installed on the left side of the pump station. 
b) Remove the controller cover by removing the screw with a small straight blade or star screwdriver.  Pull 
the cover straight off to expose the electrical (left) and sensor (right) terminal connections.
c) Install system temperature sensors. (See section 6.4)
Step 1. Insert collector sensor (RED high temp wire) into collector  sensor well on the solar return side 
of the collector. Route the wire along the return pipe to the pump station avoiding direct contact with 
the pipe.
 NOTICE
Do not install the sensor  wires in direct  contact with system  pipes.   Route sensor wires on 
the outside of system pipe insulation whenever possible.
Step 2. Insert storage tank  sensor (GRAY wire) into storage tank sensor well.  Route the wire along the 
return pipe to the pump station avoiding direct contact with the pipe.
Step 3. Remove the wire strain relief bar on sensor terminal side of controller.
Step 4. Connect the red collector sensor wire to T1 terminals (red and white wires). 
Connect grey storage tank sensor to T2 terminals (brown and white wires).
Step 5. Replace wire strain relief bar. 
d) Sensors  wires  can be fed through the pump station and out the top to run along the collector return pipe 
or out the bottom along the tank return pipe (OUTSIDE THE INSULATION). 
e) Once all wires are connected to the controller the cover can be replaced. 
7.7. Pump Operation
a) Fixed  Speed  Operation:  The Apricus Closed Loop Pump  station is supplied standard with a 3 speed 
Grundfos  pump.  The  speed used  will  depend  on  the  system  head  (line  pressure  losses).    See  pump 
specification sheet in Appendix 7. 
i)  Measuring Flow  Rate:  By utilizing the flow meter  above the pump the flow can be monitored and 
Apricus Solar Collector Installation & Operation Manual - USA
Copyright © 2011 – Apricus Inc Doc: A7-05.4.12-PB Page 57 of 129










