Specifications
Step 1. Insert collector sensor (RED high temp wire) into collector  sensor well on the solar return side 
of the collector.   Route the wire along the return pipe to the pump station avoiding direct contact with 
the pipe.
Step 2. Insert storage tank  sensor (GRAY wire) into storage tank sensor well.  Route the wire along the 
return pipe to the pump station avoiding direct contact with the pipe.
Step 3. Remove the wire strain relief bar on sensor terminal side of controller.
Step 4. Connect the red collector sensor wire to T1 terminals (red and white wires). 
Connect grey storage tank sensor to T2 terminals (brown and white wires).
Step 5. Replace wire strain relief bar. 
 NOTICE
Do not install the sensor  wires in direct  contact with system  pipes.   Route sensor wires on 
the outside of system pipe insulation when ever possible.
d) Sensors  wires  can be fed through the pump station and out the top to run along the collector return pipe 
or out the bottom along the tank return pipe (OUTSIDE THE INSULATION). 
e) Once all wires  are connected to the controller and the strain relief bar  screwed into place the cover can 
be replaced. 
8.7. Pump Operation
a) Fixed Speed Operation: The Apricus  direct flow pump station is  supplied standard with a single speed 
Grundfos  pump.  In most domestic installs  this  standard pump will have sufficient head pressure.  See the 
performance curve to the right. 
See pump specification sheet in Appendix 8. 
i) Measuring Flow  Rate: By utilizing the flow meter above the pump, the flow can be monitored. The 
system flow rate can be adjusted by turning the flow restrictor screw (5/32” or  4mm Allen) on the flow 
meter. 
ii)  Nominal  Flow  Rate:  The  recommended  nominal   flow  rate for  Apricus  evacuated  tube solar 
collectors is 0.026 G/tube/min or 0.1 L/tube/min. Refer also to section 3.5. 
b) Variable Speed Operation (recommended): The Apricus  Controller allows  for variable speed control of 
the Grundfos pump. Refer to section 6.4 for programming details. 
i)  Flow  Rate: When using variable speed control the full  speed flow rate should be no more than 1.3 
gpm / 5 lpm per 30 tube collector.   The restrictor  screw on the flow meter  can be used to adjust the 
flow rate to a suitable level. 
ii) Speed Setting: Initially set the “Min rev pump” value to 50%, then manually test the pump operation 
(Operation Menu) at this  level and monitor  the flow rate.  The flow rate at the slowest pump operation 
level should be around 40-50% of the full flow rate. Adjust the “Min rev pump” until a suitable flow rate 
is achieved. 30% is the minimum possible setting. 
ii)  Operation: The pump will operate between the dTMax and dTMin temperature range, switching on 
at 100% when dTMax is reached, and reaching minimum pump speed at dTMin. If dTMin is under-run, 
the pump will switch off.   If a slow enough flow rate is  not able to be achieved with the “Min rev pump” 
setting, reducing the dTMin down to 2-3
°
F (if not already) will help to prevent the pump cycling on and 
off throughout the day. 
c) Check Valve: All Apricus pump stations are supplied with the pump check valve installed. 
8.8. Fill System
a) The Apricus direct flow pump station is designed to fill using the domestic water system pressure. 
Apricus Solar Collector Installation & Operation Manual - USA
Copyright © 2011 – Apricus Inc Doc: A7-05.4.12-PB Page 66 of 129










