Electrical Data UCR
Rated Min.Cir. MaxFuse Rec. Discon. Rated Min.Cir. Locked MaxFuse Rec.
Load Amps Size Fuse Switch Load Amps Rotor Size
Fuse
4
Amps
1
(MCA)
2
(MOP)
3,8
Size
4,8
Size
9
Amps
1
(MCA)
2
(LRA)
5
(MOP)
3
Size
UCR030 UCR030AHASAC00S 208V-230V/ 3PH/ 60HZ
114 128 175 150 175 57.0 71.2 425 125 90
UCR030 UCR030AFASAC00S 460V/ 3PH/ 60HZ
52 58 80 70 80 25.8 32.2 173 50 40
UCR030 UCR030ANASAC00S 575V/ 3PH/ 60HZ
41 46 60 60 70 20.6 25.8 128 45 35
UCR050 UCR050AHASAC00S 208V-230V/ 3PH/ 60HZ
188 211 300 250 300 94.0 117.5 605 200 150
UCR050 UCR050AFASAC00S 460V/ 3PH/ 60HZ
85 96 125 110 150 42.5 53.1 272 90 70
UCR050 UCR050AFASAC00S 575V/ 3PH/ 60HZ
68 76 110 90 110 34.0 42.5 238 70 60
UCR070 UCR070AFASAC00S 208V-230V/ 3PH/ 60HZ
246 277 400 325 400 123.1 153.9 599 250 200
UCR070 UCR070AFASAC00S 460V/ 3PH/ 60HZ
111 125 175 150 175 55.7 69.6 310 125 90
UCR070 UCR070AFASAC00S 575V/ 3PH/ 60HZ
89 100 125 125 150 44.5 55.7 239 100 70
NOTES:
1. RLA - Rated Load Amps are calculated as per UL1995.
2. MCA - Minimum Circuit Ampacity is: [ 125% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent motors and/or electrical loads].
3. MOP - Maximum Overcurrent Protection or Max.Fuse Size is rounded down from: [ 225% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent electrical loads].
4. Recommended Dual Element Fuse Sizing: Rounded up from 150% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent electrical loads.
5. LRA - Locked Rotor Amps are instantaneous starting amperage per compressor.
6. Module internal wiring is per NEC.
7. Voltage Tolerance Range
208-230V / 60 Hz: Min. 187V Max. 253V
460V / 60 Hz: Min. 414V Max. 506V
575V / 60 Hz: Min. 518V Max. 632V
8. MOP Device or Recommended Fusing Device for Module Power Wiring supplied by others. These are recommended values for electrical power protection of Modules selected.
9. Disconnect Switch for Module Power Wiring supplied by others. These are recommended values for electrical power protection of Modules selected.
Power Wiring - per Module
Voltage
Ultimate Model #
Ultimate Model Typ
e
Internal Wiring - per Compressor