Tranquility 27™ (TT) Series TWO-STAGE HORIZONTAL, VERTIC AL, AND DOWNFLOW EARTHPURE ® SYSTEMS SIZES 026 - 072 [7.0 - 19.
Tranquility 27™ (TT) Series Table of Contents TT 50 What’s New With The Tranquility 27™? ...............................51 Dimensions — Vertical Downflow .........................................74 Design Features ...................................................................................52 Dimensions — Horizontal ...........................................................76 Unit Model Key....................................................................................54 Electrical Data...
ClimateMaster Geothermal Heat Pump Systems What's New with ClimateMaster's Tranquility 27™? EarthPure® Refrigerant EarthPure® is a non-chlorine based (HFC-410A) refrigerant, that with R-407C and R-134A, is seen as the future of all refrigerants used worldwide. HFC 410A characteristics compared to R-22 are: • Binary and near azeotropic mixture of 50% R-32 and 50% R-125. • Higher efficiencies (50-60% higher operating pressures) • Zero ozone depletion potential and low global warming potential.
Tranquility 27™ (TT) Series Tranquility 27™ Design Features The Tranquility 27™ Series has abundant features and ultra high efficiency. Application Flexibility • Five Capacities 026, 038, 049, 064, and 072. • Extended range operation (20-120°F EWT) and flow rates as low as 1.5 gpm per ton. • Vertical packages with either true right or true left return air options. • Internally trapped condensate drain. • Variable speed ECM fan motor adapts to various duct systems.
ClimateMaster Geothermal Heat Pump Systems Tranquility 27™ Design Features Simplified Controls • CXM solid state control module. • ‘CFM’ LED displays airflow. • Dehumidification mode for higher latent cooling. Options & Accessories • Optional hot water generator with internally mounted pump. • Optional cupronickel coaxial heat exchanger. • Electronic thermostat. • Closed loop Flow Controller. • Electronic auto-changeover thermostat with 3-stage heat, 2-stage cool and indicator LED’s. • Hose kits.
Tranquility 27™ (TT) Series Unit Model Key 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TT V 0 2 6 A G C 0 1 A L K S Series Standard TT = Tranquility Two-Stage Scroll S = Standard Supply Air Flow & Motor Configuration Configuration V = Vertical Up H = Horizontal D = Vertical Down Supply Configuration Top TTV TTD Down TTH Back TTH Straight K N P W Unit Size 026, 038, 049, 064, 072 Motor ECM ECM ECM ECM Return Air Flow Configuration Revision Level L = Left Return R = Right Return A = Current
ClimateMaster Geothermal Heat Pump Systems About AHRI/ISO/ASHRAE 13256-1 About AHRI/ISO/ASHRAE 13256-1 AHRI/ASHRAE/ISO 13256-1 (Air-Conditioning and Refrigeration Institute/American Society of Heating, Refrigerating and Air Conditioning Engineers/International Standards Organization) is a certification standard for water-source heat pumps used in the following applications: • WLHP (Water Loop Heat Pump – Boiler/Tower) • GWHP (Ground Water Heat Pump – Open Loop) • GLHP (Ground Loop Heat Pump – Geothermal) Th
Tranquility 27™ (TT) Series AHRI/ISO/ASHRAE/ANSI 13256-1 Performance ASHRAE/AHRI/ISO 13256-1.
ClimateMaster Geothermal Heat Pump Systems Reference Calculations & Legend Heating HE LWT = EWT GPM x 500 LAT = EAT + HC CFM x1.08 Cooling HR LWT = EWT + GPM x 500 LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.08 S/T = SC TC Hot Water Generator capacities (HWC) are based on potable water flow rate of 0.4 gpm per nominal equipment ton and 90°F entering potable water temperature.
Tranquility 27™ (TT) Series Full Load Correction Factors Air Flow Correction Table Airflow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 60% 0.925 0.788 0.913 0.922 0.946 1.153 0.896 69% 0.946 0.829 0.926 0.942 0.959 1.107 0.924 75% 0.960 0.861 0.937 0.955 0.969 1.078 0.942 81% 0.972 0.895 0.950 0.968 0.977 1.053 0.959 88% 0.983 0.930 0.965 0.979 0.985 1.032 0.974 94% 0.992 0.
ClimateMaster Geothermal Heat Pump Systems Part Load Correction Factors Air Flow Correction Table Airflow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 60% 0.920 0.781 0.959 0.927 0.946 1.241 0.881 69% 0.942 0.832 0.964 0.946 0.960 1.163 0.915 75% 0.956 0.867 0.696 0.959 0.969 1.115 0.937 81% 0.969 0.901 0.975 0.970 0.978 1.076 0.956 88% 0.981 0.934 0.982 0.981 0.986 1.043 0.
Tranquility 27™ (TT) Series Performance Data — Tranquility 27™ Model 026 - Part Load 725 CFM Nominal (Rated) Airflow Cooling, 825 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.0 3.5 3.5 5.8 5.8 7.0 7.
ClimateMaster Geothermal Heat Pump Systems Performance Data — Tranquility 27™ Model 026 - Full Load 850 CFM Nominal (Rated) Airflow Cooling, 950 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.
Tranquility 27™ (TT) Series Performance Data — Tranquility 27™ Model 038 - Part Load 1000 CFM Nominal (Rated) Airflow Cooling, 1000 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.0 4.0 4.0 6.0 6.0 8.0 8.
ClimateMaster Geothermal Heat Pump Systems Performance Data — Tranquility 27™ Model 038 - Full Load 1250 CFM Nominal (Rated) Airflow Cooling, 1250 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.
Tranquility 27™ (TT) Series Performance Data — Tranquility 27™ Model 049 - Part Load 1300 CFM Nominal (Rated) Airflow Cooling, 1400 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.3 8.3 11.0 11.0 5.5 5.5 8.
ClimateMaster Geothermal Heat Pump Systems Performance Data — Tranquility 27™ Model 049 - Full Load 1550 CFM Nominal (Rated) Airflow Cooling, 1650 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.
Tranquility 27™ (TT) Series Performance Data — Tranquility 27™ Model 064 - Part Load 1500 CFM Nominal (Rated) Airflow Cooling, 1650 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.5 14.0 14.0 7.0 7.0 10.5 10.
ClimateMaster Geothermal Heat Pump Systems Performance Data — Tranquility 27™ Model 064 - Full Load 1825 CFM Nominal (Rated) Airflow Cooling, 2050 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.
Tranquility 27™ (TT) Series Performance Data — Tranquility 27™ Model 072 - Part Load 1500 CFM Nominal (Rated) Airflow Cooling, 1600 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 15 15 7.5 7.5 11.25 11.25 15.0 15.0 7.5 7.5 11.25 11.25 15.0 15.0 7.5 7.5 11.25 11.25 15.0 15.0 7.5 7.5 11.25 11.25 15.0 15.0 7.5 7.5 11.25 11.25 15.0 15.0 7.5 7.5 11.25 11.25 15.0 15.0 7.5 7.5 11.25 11.25 15.0 15.0 7.5 7.5 11.25 11.25 15.0 15.0 7.5 7.5 11.25 11.25 15.0 15.0 7.
ClimateMaster Geothermal Heat Pump Systems Performance Data — Tranquility 27™ Model 072 - Full Load 1950 CFM Nominal (Rated) Airflow Cooling, 2100 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 85 90 100 110 120 GPM 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.5 8.5 12.8 12.8 17.0 17.0 8.
Tranquility 27™ (TT) Series Performance Data Selection Notes For operation in the shaded area when water is used in lieu of an anti-freeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 40°F [4.4*C] when the JW3 jumper is not clipped (see example below). This is due to the potential of the refrigerant temperature being as low as 32°F [0°C] with 40°F [4.
ClimateMaster Geothermal Heat Pump Systems Physical Data Model 026 Compressor (1 Each) Factory Charge R410a, oz [kg] 038 049 064 072 Copeland UltraTech Two-Stage Scroll 58 [1.64] 78 [2.21] 81 [2.30] 144 [4.08] 156 [4.
Tranquility 27™ (TT) Series Dimensions — Vertical Upflow Tranquility 27™ Overall Cabinet Vertical Upflow Model A Width B Depth C Height 026 in cm 22.4 56.8 25.6 65.1 48.5 123.2 038 in cm 25.4 64.5 30.6 77.8 50.5 128.3 049 in cm 25.4 64.5 30.6 77.8 54.5 138.4 064 in cm 25.4 64.5 30.6 77.8 58.5 148.6 072 in cm 25.4 64.5 30.6 77.8 58.5 148.
ClimateMaster Geothermal Heat Pump Systems Dimensions — Vertical Upflow Tranquility 27™ Return Connection Standard Deluxe Filter Rack (+/- 0.10 in, +/- 2.5mm) Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm) Vertical Upflow Model M Left Return N O Supply Width P Supply Depth Q Right Retuen R S Return Depth T Return Height U 026 in cm 7.8 18.3 5.8 14.8 14.0 35.6 14.0 35.6 4.9 12.4 1.7 4.2 22.2 56.4 26.2 66.4 1.5 3.9 038 in cm 6.4 16.1 6.3 16.0 18.0 45.7 18.0 45.
Tranquility 27™ (TT) Series Dimensions — Vertical Downflow Tranquility 27™ Vertical Downflow Model Overall Cabinet A Width B Depth C Height 026 in cm 22.4 56.8 25.6 65.1 52.5 133.4 038 in cm 25.4 64.5 30.6 77.8 54.5 138.4 049 in cm 25.4 64.5 30.6 77.8 58.5 148.6 064 in cm 25.4 64.5 30.6 77.8 62.5 158.8 072 in cm 25.4 64.5 30.6 77.8 62.5 158.
ClimateMaster Geothermal Heat Pump Systems Dimensions — Vertical Downflow Tranquility 27™ Return Connection Standard Deluxe Filter Rack (+/- 0.10 in, +/- 2.5mm) Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm) Vertical Downflow Model M Left Return N O Supply Width P Supply Depth Q Right Return R S Return Depth T Return Height U 026 in cm 6.7 17.1 8.4 21.4 9.9 25.3 9.1 23.0 10.8 27.4 1.7 4.2 22.2 56.4 26.2 66.4 21.2 53.9 038 in cm 7.4 18.7 9.0 22.9 13.1 33.3 12.
Tranquility 27™ (TT) Series Dimensions — Horizontal Tranquility 27™ Horizontal Model Overall Cabinet A Width B Depth C Height 026 in cm 22.4 56.8 62.2 158.0 19.3 48.9 038 in cm 25.4 64.5 71.2 180.8 21.3 54.0 049 in cm 25.4 64.5 76.2 193.5 21.3 54.0 064 in cm 25.4 64.5 81.2 206.2 21.3 54.0 072 in cm 25.4 64.5 81.2 206.2 21.3 54.0 Water Connections Horizontal Model 1 2 3 4 5 D In E Out F HWG IN G HWG Out H Condensate Loop Water IPT HWG IPT 026 in cm 2.1 5.2 10.
ClimateMaster Geothermal Heat Pump Systems Dimensions — Horizontal Tranquility 27™ Return Connection Standard Deluxe Filter Rack (+/- 0.10 in, +/- 2.5mm) Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm) Horizontal Model M Left Return N O Supply Width P Supply Depth Q Right Return R S Return Depth T Return Height U V 026 in cm 3.6 9.3 2.0 5.1 12.5 31.8 15.5 39.4 3.6 9.2 2.0 5.2 33.8 85.8 16.2 41.0 2.3 5.8 1.5 3.9 038 in cm 3.1 8.0 1.2 3.1 19.0 48.3 17.5 44.
Tranquility 27™ (TT) Series Electrical Data All TT Units with ECM Fan Motor TT Units (ECM) Standard Compressor Ext Loop Pump FLA Fan Motor FLA Total Unit FLA Min Circuit Amps Max Fuse/ HACR (2) RLA LRA Qty HWG Pump FLA 026 10.3 52.0 1 0.40 4.0 4.3 19.0 21.6 038 16.7 82.0 1 0.40 4.0 4.3 25.4 049 21.2 96.0 1 0.40 4.0 7.0 32.6 064 25.6 118.0 1 0.40 4.0 7.0 072 27.2 150.0 1 0.40 4.0 7.
ClimateMaster Geothermal Heat Pump Systems Tranquility 27™ Electrical Wiring Diagram - 96B0005N37 All Products Technical Guide: 2008 TT 79
Tranquility 27™ (TT) Series Tranquility 27™ with ClimaDry™ Electrical Wiring Diagram 96B0005N38 TT 80 ClimateMaster : Smar t. Responsible. Comfor table.
ClimateMaster Geothermal Heat Pump Systems Tranquility 27™ ECM Control Features The ECM fan is controlled by an interface board that converts thermostat inputs and field selectable CFM settings to signals used by the ECM motor controller. Units manufactured before July 2005 have version I (P/N 69243707). Units manufactured between July 2005 and May 11, 2009 have version II (P/N 17B0019N01). Fan speeds are selected with jumpers for version I or via a nine position DIP switch for version II and III.
Tranquility 27™ (TT) Series Tranquility 27™ ECM Control Features ECM Board Tap Settings Cooling settings: TT, TS Units Version I Version II and III 69243707 (17B0019N01 & 17B0034N01) Tap HP CFM DIP Switch Setting Jumper SW1 SW2 1 1 ON ON 2 2 ON OFF 3 3 OFF ON 4 4 OFF OFF Heating settings: TT, TS Units Version I Version II and III 69243707 (17B0019N01 & 17B0034N01) Tap DIP Switch DELAY Setting Jumper SW3 SW4 1 1 ON ON 2 2 ON OFF 3 3 OFF ON 4 4 OFF OFF CFM Adjust settings: TT, TS Units Version I Version II
ClimateMaster Geothermal Heat Pump Systems Blower Performance Data Residential Units Only Airflow in CFM with wet coil and clean air filter Model 026 038 049 064 072 Cooling Mode Dehumid Mode Heating Mode Fan AUX CFM Aux/ Emerg Mode 1060 475 4 1060 950 425 3 950 Max ESP (in. wg) Fan Motor (hp) Tap Setting Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 0.50 1/2 4 810 950 475 630 740 475 920 0.50 1/2 3 725 850 425 560 660 425 825 0.
Tranquility 27™ (TT) Series Auxiliary Electric Heat Auxiliary Heat Ratings 230V 208V 230V 208V Minimum CFM Required AGM5A 4.8 3.6 16300 12300 500 AGM8A 7.6 5.7 25900 19400 650 AGM10A 9.6 7.2 32700 24600 650 AGM12A 11.4 8.6 38900 29200 750 AGL10A 9.6 7.2 32700 24600 1300 AGL15A 14.4 10.8 49100 36900 1350 AGL20A 19.2 14.
ClimateMaster Geothermal Heat Pump Systems Engineering Guide Specifications General The water source heating/cooling units shall be vertical upflow air discharge. Units shall be AHRI/ISO/ASHRAE 13256-1 (ground-source closed-loop) performance cer tified and listed by a nationally recognized safety-testing laboratory or agency. Each unit shall be water run-tested at the factory. Each unit shall be pallet mounted and shipped with appropriate protective packaging to help avoid damage in transportation.
Tranquility 27™ (TT) Series Accessories & Warranty Accessories & Options Warranty Information ClimaDry™ Whole House Dehumidification An optional internal whole house dehumidifier shall be factory installed, which allows the unit to operate in one of three modes, heating, cooling, or dehumidification. Operation must include modulating controls to provide neutral air (72°F) regardless of entering water temperature. Requires ATP32U04 thermostat or separate humidistat.
ClimateMaster Geothermal Heat Pump Systems Notes All Products Technical Guide: 2008 TT 87
Tranquility 27™ (TT) Series Revision History TT 88 Date Page # Description 8 June, 09 Various Edits to pages 49, 52, 53, 79-82, and 86 05 June, 08 All Reformatted Document Size 03 Mar, 08 37 Updated Specifications 03 Mar, 08 26 Updated Downflow Dimensional Data 01 Mar, 07 30 Added New Notes to Electrical Data 01 Mar, 07 All Added Model 072 Information 01 Oct, 06 All First Published ClimateMaster : Smar t. Responsible. Comfor table.