Full Load Correction Factors
* = Sensible capacity equals total capacity
AHRI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6°F DB/66.2°F WB,
and Heating - 68°F DB/59°F WB entering air temperature
Air Flow Correction Table
Entering Air Correction Table
Air ow Cooling Heating
% of
Rated
Total
Capacity
Sensible
Capacity
Power
Heat of
Rejection
Heating
Capacity
Power
Heat of
Extraction
60%
0.925 0.788 0.913 0.922 0.946 1.153 0.896
69%
0.946 0.829 0.926 0.942 0.959 1.107 0.924
75%
0.960 0.861 0.937 0.955 0.969 1.078 0.942
81%
0.972 0.895 0.950 0.968 0.977 1.053 0.959
88%
0.983 0.930 0.965 0.979 0.985 1.032 0.974
94%
0.992 0.965 0.982 0.990 0.993 1.014 0.988
100%
1.000 1.000 1.000 1.000 1.000 1.000 1.000
106%
1.007 1.033 1.020 1.009 1.006 0.989 1.011
113%
1.012 1.064 1.042 1.018 1.012 0.982 1.019
119%
1.016 1.092 1.066 1.025 1.018 0.979 1.027
125%
1.018 1.116 1.091 1.032 1.022 0.977 1.033
130%
1.019 1.132 1.112 1.037 1.026 0.975 1.038
Cooling
Entering
Air
WB°F
Total
Capacity
Sensible Cooling Capacity Multiplier -
Entering DB °F
Power
Heat of
Rejection
60 65 70 75 80 80.6 85 90 95 100
45
0.832 1.346 1.461 1.603 * ******0.946 0.853
50
0.850 1.004 1.174 1.357 * ******0.953 0.870
55
0.880 0.694 0.902 1.115 1.331 ******0.964 0.896
60
0.922 0.646 0.875 1.103 1.329 1.356 * * * * 0.977 0.932
65
0.975 0.639 0.869 1.096 1.123 1.320 * * * 0.993 0.979
66.2
0.990 0.582 0.812 1.039 1.066 1.262 1.482 * * 0.997 0.991
67
1.000 0.545 0.774 1.000 1.027 1.223 1.444 * * 1.000 1.000
70
1.040 0.630 0.853 0.880 1.075 1.297 1.517 * 1.011 1.035
75
1.117 0.601 0.627 0.821 1.046 1.275 1.510 1.033 1.101
Heating
Entering
Air DB°F
Heating
Capacity
Power
Heat of
Extraction
40
1.052 0.779 1.120
45
1.043 0.808 1.102
50
1.035 0.841 1.084
55
1.027 0.877 1.065
60
1.019 0.915 1.045
65
1.010 0.957 1.023
68
1.004 0.982 1.010
70
1.000 1.000 1.000
75
0.989 1.045 0.974
80
0.976 1.093 0.946