Tranquility® Vertical Stack (TSM) Series Submittal Data Models TSM09 - 36 60Hz - HFC-410A SUBMITTAL DATA - I-P UNITS Unit Designation: English Language/I-P Units Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: Btuh EER: Heating Capacity: Btuh COP: Ambient Air Temp: °F Entering Water Temp (Clg): °F Entering Air Temp (Clg): °F Entering Water Temp (Htg): °F Entering Air Temp (Htg): °F Airflow: CFM Fan Speed or Motor/RPM/Turns: Revised: 3 July, 2013 Operating
Tranquility® Vertical Stack (TSM) Series Submittal Data Models TSM09 - 36 60Hz - HFC-410A SUBMITTAL DATA - S-I UNITS Unit Designation: English Language/S-I Units Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: kW EER: Heating Capacity: kW COP: Ambient Air Temp: °C Entering Water Temp (Clg): °C Entering Air Temp (Clg): °C Entering Water Temp (Htg): °C Entering Air Temp (Htg): °C Airflow: l/s Fan Speed or Motor/RPM/Turns: Revised: 3 July, 2013 Operating Weig
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Table of Contents Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TSM Series Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Performance Data – AHRI/ASHRAE/ISO 13256-1 . . . . . . . . . . . . . . . . . . . . Performance Data – Selection Notes . . . . . . . . . . .
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features UNIT FEATURES TRANQUILITY® VERTICAL STACK (TSM) SERIES WITH EARTHPURE® REFRIGERANT The Tranquility® Vertical Stack (TSM) Series offers an innovative, labor-saving solution for spaces where individual, quiet control of the heating and cooling system is important. TSM units’ consist of 2 major components - cabinet behind finished wall and slide in refrigeration chassis.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Reference Calculations Heating Cooling HE LWT = EWT GPM x Constant LAT = EAT + HC CFM x1.08 LWT = EWT + HE GPM x Constant LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.08 S/T = SC TC Constant = 500 for water, 485 for antifreeze.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 500 CFM per ton.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Series Nomenclature Cabinet 1 2 3 C1 G 4 5 0 N 11 12 13 14 15 0 A 1 0 0 0 0 0 0 A 6 7 8 9 10 REVISION LEVEL CABINET SIZE A = CURRENT REVISION 1 = 09 2 = 12 3 = 15 4 = 18 5 = 24 6 = 30 7 = 36 STANDARD 0 = STANDARD A, B, C etc.... = SPECIAL 1, 2, 3 etc....
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Series Nomenclature Chassis 1 2 3 TSM 4 5 6 7 8 9 10 11 12 13 09 G S A S S C S S S A 15 14 Revision Level Series A = Current Revision Level TSM = TRANQUILITY® HIGH RISE CHASSIS Standard S = Standard A = Special #1 B = Special #2 Etc.....
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Series Nomenclature Hose Kit 1 2 3 4 5 6 7 8 AH H 0 5 0 3 B Group Revision Level B = Current Revision AHH = Accessory Hose Kit Hi-Rise Hose Size Length 050 = 1/2” Nominal 075 = 3/4” Nominal 100 = 1” Nominal 3 = Length in Feet Return Air Panel 1 2 3 4 5 6 7 AVHSG 1 S 8 9 10 11 F S M S STANDARD S = STANDARD ACCESSORY VHS RETURN AIR PANEL AVHSG = G-PANEL REVISION LEVEL M = CURRENT REVISION TSM (”G” PANEL) UNIT SIZE OPTION TSM
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1. English (I-P) Units Model Model with with ECM PSC Motor Motor TSM09 TSM09 TSM12 TSM12 Model TSM15 TSM15 with PSC TSM18 TSM18 Motor TSM24 TSM24 TSM09 TSM30 TSM30 TSM12 TSM36 TSM36 Water Water Loop Loop Heat Heat Pump Pump Cooling 86°F Heating Cooling 86°F Heating 68°F 68°F Capacity EER Capacity Capacity EER Capacity COP COP Btuh Btuh/W Btuh Btuh Btuh/W Btuh 10,000 10,100 11,800 11,600 15.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – Selection Notes For operation in the shaded area to determine if water can be used in lieu of an antifreeze solution, the Leaving Water Temperature (LWT) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 42°F [5.6°C] when the CXM/DXM JW3 jumper is not clipped (see example below).
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM09 with PSC Motor 400 CFM Nominal Airflow Heating, 350 CFM Nominal Airlfow Cooling EWT °F 20 30 40 50 60 70 80 90 100 110 120 WPD* GPM PSI FT TC Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F Sens/Tot SC kW HR Ratio Heating - EAT 70°F EER *WPD Adder for Motorized Valve, TSM09 (Cv = 4.9, MOPD = 150 psi) HC kW HE LAT COP 6.33 0.65 3.96 75.6 2.8 PSI FT 7.36 0.66 4.95 76.9 3.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM12 with PSC Motor 500 CFM Nominal Airflow Heating, 400 CFM Nominal Airlfow Cooling *WPD Adder for Motorized Valve, TSM12 (Cv = 4.9, MOPD = 150 psi) WPD Adder GPM PSI FT 1.8 0.4 0.8 2.6 0.5 1.2 3.5 0.7 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM15 with PSC Motor 600 CFM Nominal (Rated) Airflow EWT °F 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh WPD* GPM PSI FT Cooling - EAT 80/67°F TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP 8.99 0.98 6.15 81.8 2.7 *WPD Adder for Motorized Valve, TSM15 (Cv = 10.3, MOPD = 150 psi) 2.3 2.4 3.5 5.8 4.5 8.8 20.3 PSI FT 2.3 2.3 5.4 17.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM18 with PSC Motor 700 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TSM18 (Cv = 10.3, MOPD = 150 psi) Performance capacities shown in thousands of Btuh WPD* EWT °F Cooling - EAT 80/67°F GPM PSI FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP 3.4 2.6 5.1 4.7 6.8 7.2 16.7 10.67 1.18 7.16 82.1 2.7 3.4 2.2 5.1 23.79 15.72 0.66 0.77 25.90 31.0 12.64 1.21 9.01 84.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM24 with PSC Motor 850 CFM Nominal (Rated) Airflow Performance capacities shown in thousands of Btuh WPD* EWT °F 20 30 40 50 60 70 80 90 100 110 120 Cooling - EAT 80/67°F GPM PSI FT TC SC Sens/Tot Ratio Heating - EAT 70°F kW HR 4.0 0.8 6.0 2.5 8.0 5.2 12.1 4.0 0.9 2.1 33.57 21.59 0.64 1.06 36.72 6.0 2.3 5.3 34.11 21.76 0.64 0.99 8.0 5.0 11.4 34.31 21.80 0.64 4.0 0.7 1.6 32.53 21.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM30 with PSC Motor 1000 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TSM30 (Cv = 10.3, MOPD = 150 psi) GPM WPD Adder PSI FT 4.0 0.4 0.9 6.0 0.6 1.3 8.0 0.8 1.8 Performance capacities shown in thousands of Btuh WPD* EWT °F 20 30 40 50 60 70 80 90 100 110 120 Cooling - EAT 80/67°F GPM PSI FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP 17.82 1.93 11.96 84.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM36 with PSC Motor 1200 CFM Nominal (Rated) Airflow Performance capacities shown in thousands of Btuh WPD* EWT °F 20 30 40 50 60 70 80 90 100 110 120 Cooling - EAT 80/67°F GPM PSI 4.5 3.7 6.0 5.0 9.0 8.6 FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP Operation not recommended *WPD Adder for Motorized Valve, TSM36 (Cv = 10.3, MOPD = 150 psi) GPM 19.8 23.28 2.31 15.72 85.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data Correction Tables Air Flow Correction Table Airflow Cooling Heating % of Nominal (Rated) SCFM Total Capacity 70 0.921 0.8 0.969 0.943 0.942 1.077 0.934 75 0.934 0.833 0.974 0.952 0.952 1.062 0.947 80 0.946 0.866 0.979 0.961 0.961 1.048 0.958 85 0.958 0.899 0.985 0.97 0.971 1.035 0.969 90 0.971 0.932 0.99 0.979 0.980 1.023 0.979 95 0.985 0.966 0.995 0.989 0.990 1.011 0.989 100 1.000 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P PSC Blower Performance Data TSM with PSC Motor Airflow in CFM with wet coil and clean 1" (25mm) fiberglass air filter. Size Fan Speed Rated CFM High 09 Medium 400H/350C 284 Low Medium 500H/400C 310 Low High 15 18 36 0.10 0.15 0.20 425 415 400 380 360 0.25 0.30 0.35 Operation not recommended 330 320 360 345 325 320 300 * * 400 375 0.40 0.45 0.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Physical Data Model 09 12 15 Compressor (1 Each) Factory Charge HFC-410A (oz) [kg] 18 24 Rotary 34 [.07] 34 [.97] 30 36 Scroll 43 [1.22] 53 [1.51] 71 [2.01] 66 [1.87] 75 [2.13] PSC Motor & Blower Wheel (2 Speeds) Motor (hp) [W] Blower Wheel Size (dia x w) (in) [mm] 1/30 [25] 1/15 [50] 1/6 [124] 1/6 [124] 1/5 [149] 1/2 [373] 1/2 [373] 6.75 x 7.25 [174 x 184] 6.75 x 7.25 [174 x 184] 9.50 x 7.12 [241 x 181] 9.50 x 7.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data - PSC Motor Standard Unit Model # Rated Voltage Min/ Max Voltage Compressor Fan Motor FLA Total FLA With Pump SCCR SCCR MCA kA rms Symetrical Volts Maximum Max Fuse Amps Total FLA SCCR SCCR MCA kA rms Symetrical Volts Maximum Max Fuse / HACR 15 RLA LRA TSM09G 208-230/60/1 197/254 3.7 22.0 0.4 4.1 5.0 NA NA 15 4.6 5.5 NA NA TSM09E 239/292 3.5 24.0 0.3 3.8 4.7 NA NA 15 4.3 5.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Series Wiring Diagram Matrix All current diagrams can be located online at climatemaster.com. Click ‘Commercial’ (go to ‘Quick Links’ in the upper right) using the part numbers presented below. Model Refrigerant Wiring Diagram Part Number TSM09-36 PSC EarthPure® 96B0173N32 (HFC-410A) 96B0173N33 Electrical 208-230/60/1, 265/60/1 Control CXM DXM ACO/MCO Agency ETL DXM MPC Connections NOTE 2 Notes: 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – TSM09 - 36 CXM with PSC Motor TITLE: PCN HI-RISE 09-36 208-230/60/1, 220-240/50/1, 265/60/1 CXM (N) CONTROLS w/PSC High Pressure Switch Circuit Breaker Field Line voltage Wiring Printed Circuit Trace Ground Solenoid Coil Fuse Wire Nut Relay contacts - N.O. Relay contacts - N.C. Optional Wiring Option MS Moment Switch - N.O.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – TSM09 - 36 DXM with PSC Motor TITLE: PCN HI-RISE 9-12 208-230/60/1, 220-240/50/1, 265/60/1 DXM2 CONTROLS w/PSC Legend Condensate Pan Factory Low voltage Wiring Factory Line Voltage Wiring Field Low voltage Wiring Field Line voltage Wiring Printed Circuit Trace Optional Wiring Option Circuit Breaker Ground Fuse Wire Nut Relay / Contactor Coil Splice Cap Thermistor Mate-N-Lock G LED TSTAT ACO Capacitor L C R G O W1 Y2
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TSM Units with DXM Controller with Night Setback, Emergency Shutdown, & Pump Restart DXM 2 DXM 2 ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Unit - Exploded View Major Components 1C 1D 1E 1G 1F 1. TSM Cabinet (Furred-in) A - floating condensate drain pan B - drain P trap C - supply air plenum D - optional surface mount thermostat 2 x 4 box horizontal location E - optional disconnect / breaker locati terminal blocks optional MPC, Lon) F - upper control box (high voltage term G - blower assembly/motor H - risers (not shown) I - shutoffs (not shown) 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM – Standard Unit, Furred In Cabinet with Risers Top Supply Air KO Optional Remote T/Stat Conduit Power Conduit 2.00(51) Service Area B 1.00 x 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM – Master Unit, Furred In Cabinet Top Supply Air KO Optional Remote T/Stat Conduit Power Conduit 2.00(51) Service Area B 1.00 x 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM – Slave Unit, Furred In Cabinet, No Risers Top Supply Air KO Optional Remote T/Stat Conduit Power Conduit 2.00(51) Service B Area 1.00 x 1.38 (25 x 35) Supply Air Angles Note 8 Note 9 24 (610) A B A Thin Wall Conduit 3/4" (19) Supply Air K.O.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Cabinet Dimensions B B 1.62 [41] 1.50 [38] 1.50 [38] B 2.12 [54] C B 1.25 [32] 88.00 [2235] or 80.00 [2032] (Note 4) 66.75 [1695] OPENING FOR CHASSIS 5.00 [127] 2.50 x 12.00 [64 x 305] 5.00 [127] 2.75 [70] 2.75 [70] 57.00 [1259] 2.75 [70] 5.00 (127) 35.75 [908] 12.00 [305] 12.00 [305] 12.00 [305] 6.00 [152] L.H. SIDE A A FRONT R.H. SIDE Unit Size A B C TSM09 - 18 19.00 [483] 12.00 [305] 6.00 [152] TSM24 - 36 24.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Cabinet Slot Dimensions and Riser Arrangements TOP VIEWS 2.75” (70) 12.00” (305) B S S 5.00” (127) 2.75” (70) STYLE 4 RA R R A D D STYLE 4 STYLE 5 RA SIDE RA SIDE Model 09-18 24-36 A R STYLE 2 RA STYLE 2 RA STYLE 3 RA B STYLE 5 RA 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Cabinet Configurations Cabinet Model Digits 11 and 12 Describe Air Flow Configuration 00 No Supply Air Openings 01 Right Side 02 Left Side 10 Back 11 Back & Right 12 Back & Left 20 Front 21 Front & Right 22 Front & Left 03 Left & Right Sides 23 Front, Left, & Right Notes: 1. Front is return air side and control box location. 2. Risers can be on any side without return or supply air openings.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Cabinet Installation - Flush X B NOTICE ! R.O. Seal between studs and cabinet flanges with weather tight foam material to prevent wall cavity air from infiltrating unit or room. A Supply air grille note 5 flex boot (customer supplied) TSM CABINET FOR SURFACE MOUNTED THERMOSTAT X X A 2x4 nominal studs TOP VIEW Note 4 X OUTSIDE CORNER 1-7/8” (48) - Note 8 from cabinet to front of finished wall X X X 5/8” (16) drywall 1 or 2 layers.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Cabinet Installation - Recessed X 6.00 (152) Note 8 NOTICE! Seal Gap (4) Sides Recessed cabinet requires frame kit. Outside air requires motorized damper. X Frame Outside Drywall G Style Return Air Panel Seal between the frame and cabinet with weather seal material to avoid air being pulled in from the wall cavity. Attach frame to studs not cabinet.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Hinged “G” Style Return Air Panel – AVHSG Series Inner Panel Pivots Open .625 (16) A 1.81 (46) 15 (380 Outer Panel Locks 59.00 (1499) Hinged Inner Panel 4.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P AHH Series – Stainless Steel Braided Hose Kit Specifications: • • • • • • • • • Designed for VHS water-source heat pump applications. Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid. Fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). MPT (External Pipe Thread) fitting at one end; swivel with NPSH thread connector (Internal Thread) at the other end (seals via fiber or EPDM washer, shipped inside connection).
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Supply Air Grille A816G Series Supply Air Grille Standard cabinet openings and grille sizes. 88" (2235) cabinet models 09-18 – front, back, or sides 12 x 12 (305 x 305) or 12 x 6 (305 x 152) and top 12 x 12 (305 x 305). 80" (2032) cabinet models 09-18 – front, back, or sides 12 x 6 (305 x 152) and top 12 x 12 (305 x 305). 88" (2235) cabinet models 24-36 – front, back, or sides 16 x 16 (406 x 406) or 16 x 8 (406 x 203) and top 16 x 16 (406 x 406).
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Thermostats Two types of thermostats are available AT Series - require field to make wiring connections to screw terminals on thermostat. Cabinet construction for remote thermostat with field supplied whip (wires long enough to reach wall thermostat location) use AT Series. A91557 Series - are the AT Series thermostats with a wire harness factory assembled, 6” long wires terminating with 9 pin molex connector.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Options Optional Cabinet Disconnect Switch Located on control box access door. Can be accessed through slot in “G” Panel Frame. Classified as motor disconnect. See Cabinet decoder. Optional Cabinet Circuit Breaker Located on control box access door. Can be accessed through slot in “G” Panel Frame. All 208/230V and 265V 15 and 20 amp classified as HACR breaker. 265V 25 amp and higher classified as supplemental breaker. See Cabinet decoder.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser Definitions Swaged 3” Deep For A Dia. Riser From Above A Dia. A Dia. A A Dia. A Dia. Shutoff Valve Assembly A Dia. B Dia. 3.00 (76) 2.25 (57) 6.12 (133) MAX Runout Into Cabinet Bottom of Cabinet Runout Into Cabinet B Dia. Runout Into Cabinet Runout Into Cabinet C Dia. Runout for Slave Cabinet (Note 8) Bottom Capped Supply and Return Runout Into Cabinet 3.00 (76) 39.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser GPM Definitions and Sizing Riser GPM requirements and individual Unit GPM requirements are necessary to select the proper Riser Piping diameters. Refer to this page to determine GPM requirement, then refer to Riser Diameter Sizing Table to determine Riser Piping diameters. Example is for bottom supply - bottom return system feed loop. GPM's are dependent upon unit load and system loop water temperatures.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser Diameter Sizing Refer to Riser GPM Sizing for the prefix to this example. Each TSM Vertical Stack unit has three riser pipes: supply, return, and drain. The following example will be for one riser pipe (from the top floor to the bottom floor), and will be representative of the remaining two riser pipes. TOP CAP TSM 09 From Table 1 (below) determine the proper riser diameter needed to satisfy the required GPM's at each unit.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser Length Definitions and Sizing Total Riser Length (L) = FF of floor below + 2"(51) FF - (RRH + RT) + 4" (102). THIRD FLOOR Floor To Floor Height (FF): Distance from top of unit slab to top of above slab. Room Riser Height (RRH): Cabinet height + 3" (76). SECOND FLOOR Riser Tail Piece (RT): Length of riser extending down from the cabinet. Riser tail piece must extend a minimum of 5" (127) below slab.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser Extension Definitions and Sizing Joint Overlap Riser Extension Length: Start with the floor to floor Dim. (FF) From this subtract the room riser height and tail piece length. Then add 4" (102) for the two joint overlaps. 2" (51) Unit "B" Riser Extension Length = FF - (RRH + RT) + 4" (102). Slab Thickness Riser Tail Piece (RT): Length of riser extending down from the cabinet. Riser tail piece must extend a minimum of 5" (127) below slab.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Setting Cabinet NOTICE! Before locating riser slab slot in floor, review plans and all information in this submittal regarding cabinet, risers, slab slot, rotation into slot, clear height and the relationship of all. To determine the slab slot size required for the risers and to determine if clear height is OK for unit installation, use the example 2 on riser length page and slab slot charts on the next page.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Slab Slot Chart - 3 Pipe 3 Pipe Standard 88" Cabinet Riser Stack Patterns Slab Slot Size Type of Installation Type 1 Type 2 S Type 3 R D For Cabinet Styles 2 and 5 or W D R S For Cabinet Styles 3 and 4 L WxL WxL WxL Clear Height is Floor to Ceiling Dimension Slab Slot for Cabinets with Risers Model 09-18 24-36 Type of Installing Cabinet Through Slot Clear Height Riser length in mm in mm Type 1 105 2667 115 2921 100 2540 1
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Shipping Units Are Shipped FOB Factory TSM Chassis can be shipped 2 ways. 1. Upright in carton 4 per pallet, see figure 1. 2. Upright inside cabinet (risers shipped separate or customer supplied) 4 per pallet, see figure 1. TSM Cabinet without risers attached can ship upright 4 per pallet, see figure 1. TSM Cabinet with risers attached must be shipped horizontal and normally on dedicated open flat bed trailer either 3 or 6 per pallet, see figure 2 and 3.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 1 General: Furnish and install ClimateMaster Tranquility® “TSM Vertical Stack” Water Source Heat Pumps, as indicated on the plans with capacities and characteristics as listed in the schedule and the specifications that follow. Units shall be supplied completely factory built capable of operating over an entering water temperature range from 20° to 120°F (-6.7° to 48.9°C) as standard.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 2 Full-length supply, return, and insulated condensate water risers shall be type M copper. Supply and return risers have integral internal piping including ball valves (for shut off purposes at unit). Risers and piping shall be factory pressure tested to check for leaks. Field installed hose kits are required to connect the chassis piping to the cabinet ball valve.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 3 Hermetic compressors shall be internally sprung and externally isolated. The compressor shall have a dual level vibration isolation system.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 4 Solid State Control System (CXM): Units shall have a solid-state control system. Units utilizing electro-mechanical control shall not be acceptable. The control system microprocessor board shall be specifically designed to protect against building electrical system noise contamination, EMI, and RFI interference. The control system shall interface with a heat pump type thermostat.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 5 Digital Night Setback with Pump Restart (DXM w/ ATP32U03C/04C, ATC32U01C) The unit will be provided with a Digital Night Setback feature using an accessory relay on the DXM controller with an ATP32U03/04 thermostat and an external, field-provided time clock. The external time clock will initiate and terminate the night setback period.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 6 k. l. m. n. o. p. q. r.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 7 Thermostat shall be electronic communicating LCD 7 Day Programmable (with up to 4 setpoints per day), thermostat shall be provided. The thermostat shall offer three stages of heating and two stages of cooling with precise temperature control and have a four-wire connection to the unit.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 8 mode shall allow thermostat dehumidification mode to operate with ClimaDry® reheat or with ECM fan dehumidification mode via settings changes. Thermostat shall have a blue backlit dot matrix LCD display with temperature, relative humidity, setpoints, mode, and status indication. The temperature indication shall be selectable for ºF or ºC.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Revision History Date: 07/03/13 Item: Action: Created ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.