Specifications

ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Revised: 3 July, 2013LC994 - 35
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P
Notes:
1. Cabinet confi guration will determine slab core drilling location and walls surrounding cabinet.
2. Recommend stud walls surrounding cabinet. Drywall and studs should not be attached or contacting cabinet for best
sound attenuation. Where possible fi ll gaps with sound absorbing material. Use iso pad under cabinet. Secure cabinet
to fl oor in two places at back.
3. Return air panel overlaps rough opening, allow minimum of 3 1/2" (89) dry wall to corner. Do not caulk panel to wall.
4. G Panel attaches to frame cross bars. Cabinet must be recessed behind wall.
5. Dimensions are in inches (mm). All studs nominal 2x4, 1.50 (38) x 3.50 (89).
6. For lter access, pivot inner panel, open fi lter access snap. For chassis removal, remove G Panel, remove 2 cross bars,
remove fi lter panel, slide out chassis.
7. When outside air is required, 48A0100N04 motorized damper must be used, mixed air temperature must be
no lower than 45°F (7°C). Contractor must supply air duct, cut hole in stud, remove K.O., assemble and wire
damper assembly.
8. For 2" MERV 13 fi lter set cabinet 6.25" (158) from front of drywall.
B
57-1/2
(1460) R.O.
5-7/8*
(149)
Floor
48A0100N51
48A0100N52
19-5/8
(498)
19
(483)
24
(610)
24-3/8
(620)
09-18
24-36
Frame Kit Panel
BAKit Size
12-1/4
(311)
28-5/8
(727)
Optional motorized damper (order
seperately) 48A0100N04 may be
installed on left or right side. Note 7
C
59
(1599)
4.50
* (114)
Front View
Frame Installed
G Panel
Perimeter
Panel
Mounting
Bracket
4 Panel
Mounting
Nuts
* Dimension if cabinet is on floor.
Add if cabinet is on stand/pad.
9.00 x 2.00 KO (228 x 51)
Outside air opening,
left or right side
to suit installation.
“G” Frame
24.12
.38
(10)
(612)
4.75
(120)
Upper cross bar
Lower cross bar
R.O.
C
21.50
(546)
25.50
(648)
2
3
Frame1
2
3
Upper Cross Bar
Lower Cross Bar
1
1
1
Description
Kit Part
Qty
1
FRONT VIEW
Typical Cabinet Installation - Recessed
G Style
Return Air Panel
6.00
(152)
Note 8
DRYWALL
5/8"
(16)
CABINET
TOP VIEW
3-1/2
(89)
It is recommended to leave 2” (51) minimum clearance
on both sides for removing panel
X
Seal Gap (4) Sides
X
Frame
Outside
Drywall
A
A
Cabinet
Flange
1.25 (32)
Frame
Crossbars
(Note 4)
XX
NOTICE!
Recessed cabinet requires frame kit.
Outside air requires motorized damper.
Seal between the frame and cabinet with
weather seal material to avoid air being pulled
in from the wall cavity. Attach frame to studs
not cabinet.
Do not distort frame shim sides if required.