Specifications

ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Revised: 3 July, 2013LC994 - 41
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P
B Dia.
A Dia.
Swaged 3” Deep
For A Dia. Riser
From Above
A Dia.
C Dia.
A Dia. A Dia.
3.00
(76)
6.12
(133)
MAX
39.75
(1100)
2.25
(57)
3.00
(76)
3.12
(79)
B Dia.
Drain Runout
Into Cabinet
Supply and Return
Transition Up
Supply and Return
Transition Down
Drain
Transition Up
A Dia.
Shutoff
Valve
Assembly
Supply and Return
Straight
Master Supply and Return
Drain (Runout Lower)
Shown Dotted
Top Capped Supply and Return
Drain (Runout Lower)
Bottom Capped
Supply and Return
Runout
for Slave
Cabinet
Runout
Into
Cabinet
Runout
Into
Cabinet
Runout
Into
Cabinet
Runout
Into
Cabinet
Runout
Into
Cabinet
(Note 8)
A
A
Bottom of
Cabinet
Notes:
1. You must know water fl ow direction to determine if cabinet requires transition up or down.
2. Transitions can only change by one diameter (1" to 1¼", 1¼" to 1½", etc.)
3. Riser transition couplings and runouts are factory brazed.
4. All risers are factory pressure tested.
5. Standard riser diameters are 1", 1¼", 1½", 2", 2½" and 3"nominal water tubing.
6. Copper Type M and L available.
7. Drain riser insulated standard. Supply and return insulated optional.
8. Master riser - contractor provides tubing from runout to slave cabinet if needed.
9. Shutoff has FPT for hose (1/2" for C1 (09), C2 (12); 3/4" for C3 (15), C4 (18); or 1" for C5 (24),
C6 (30), C7 (36).
A 1.00 1.25 1.50 2.00 2.50 3.00
B 1.25 1.50 2.00 2.50 3.00 -
C - 1.00 1.25 1.50 2.00 2.50
Riser Defi nitions
Note: All ClimateMaster units have water high pressure switches. Do not design riser stack where switch will
not reset (trip - 300 PSI; Reset - 250 PSI).