Console (CCE) Series Submittal Data Models CCE07 - 19 60Hz - R22 English Language/I-P Units Geothermal Heat Pump Systems SUBMITTAL DATA - I-P UNITS Unit Designation: Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: Btuh EER: Heating Capacity: Btuh COP: Rev.
Console (CCE) Series Submittal Data Models CCE07 - 19 60Hz - R22 English Language/S-I Units Geothermal Heat Pump Systems SUBMITTAL DATA - S-I UNITS Unit Designation: Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: kW EER: Heating Capacity: kW COP: Rev.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Table of Contents *Page Number Unit Features 4 Selection Procedure 5 CCE Series Nomenclature 7 Performance Data - ARI/ASHRAE/ISO 13256-1 8 Performance Data Selection Notes 9 Performance Data - CCE07 10 Performance Data - CCE09 11 Performance Data - CCE12 12 Performance Data - CCE15 13 Performance Data - CCE19 14 Performance Data Correction Tables 15 Blower Performance & Electrical Data 16 Physical Data 17 Console Cabinet Dimensions
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems THE CONSOLE (CCE) SERIES UNIT FEATURES The CCE series console unit provides a high efficiency WSHP “ductless” solution for spaces where individual, quiet control of the heating and cooling system is important. CCE units are especially ideal where ceiling height and space are limited, or when preserving the integrity of an existing structure. The CCE series meets ASHRAE 90.1 efficiencies, yet maintains small cabinet dimensions.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Selection Procedure Reference Calculations Heating HE LWT = EWT GPM x 500 LAT = EAT + HC CFM x1.08 Cooling HR LWT = EWT + GPM x 500 LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems CCE Series Nomenclature 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 CCE 0 7 B G C A S S C S R S Model Type Standard CCE = Console S = Standard Piping Connections Unit Size R = Right Piping L = Left Piping 07 09 12 15 19 Water Circuit Options None Motorized Water Valve Autoflow (2.25 Gpm/Ton) Autoflow (3.0 Gpm/Ton) Motorized Water Valve & Afr (2.25) Motorized Water Valve & Afr (3.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data ARI/ASHRAE/ISO 13256-1 ASHRAE/ARI/ISO 13256-1. English (IP) Units Water Loop Heat Pump Model Cooling 86°F Capacity Btuh CCE07 Ground Water Heat Pump Heating 68°F EER Btuh/W Capacity Btuh 7,800 12.1 CCE09 9,300 CCE12 Cooling 59°F COP Capacity Btuh 10,400 4.9 12.0 12,000 12,300 11.6 CCE15 13,800 CCE19 16,000 Ground Loop Heat Pump Heating 50°F EER Btuh/W Capacity Btuh 8,900 19.5 4.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data Selection Notes For operation in the shaded area when water is used in lieu of an anti-freeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 42°F [5.6°C] when the JW3 jumper is not clipped (see example below). This is due to the potential of the refrigerant temperature being as low as 32°F [0°C] with 40°F [4.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data CCE07B 240 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, CCE07 (Cv = 4.9, MOPD = 150 psi) GPM WPD* EWT °F GPM 20 WPD Adder Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F TC SC Sens/ Tot Ratio PSI FT 1.9 3.7 8.5 1.0 1.4 3.2 9.7 6.9 0.71 0.36 10.9 1.4 2.2 5.1 9.8 6.9 0.70 0.33 kW HR Heating - EAT 70°F EER HC kW HE LAT COP 5.5 0.50 3.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data CCE09B 300 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, CCE09 (Cv = 4.9, MOPD = 150 psi) GPM WPD* EWT °F GPM 20 WPD Adder Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F TC SC Sens/ Tot Ratio PSI FT 2.5 6.2 14.3 1.3 1.8 4.2 11.3 7.6 0.67 0.48 13.0 1.9 3.2 7.4 11.7 7.7 0.66 0.44 kW HR Heating - EAT 70°F EER HC kW HE LAT COP 7.2 0.63 5.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data CCE12B 350 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, CCE12 (Cv = 4.9, MOPD = 150 psi) GPM EWT °F GPM 20 WPD Adder 30 Performance capacities shown in thousands of Btuh WPD* Cooling - EAT 80/67°F TC SC Sens/ Tot Ratio PSI FT 3.1 9.1 21.0 1.6 2.5 5.8 14.8 9.8 0.66 0.60 16.8 2.3 4.4 10.2 14.9 9.9 0.66 0.55 kW HR Heating - EAT 70°F EER HC kW HE LAT COP 8.7 0.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data CCE15B 400 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, CCE15 (Cv = 4.9, MOPD = 150 psi) GPM WPD* EWT °F GPM 20 WPD Adder Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F TC SC Sens/ Tot Ratio PSI FT 3.6 4.9 11.3 1.8 1.2 2.8 16.5 11.2 0.67 0.68 18.8 2.7 2.6 6.0 16.6 11.1 0.67 0.62 kW HR Heating - EAT 70°F EER HC kW HE LAT COP 9.9 0.93 6.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data CCE19B 460 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, CCE19 (Cv = 4.9, MOPD = 150 psi) GPM WPD* EWT °F GPM 20 WPD Adder Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F TC SC Sens/ Tot Ratio PSI FT 4.8 7.9 18.2 2.4 2.1 4.9 20.1 13.2 0.66 0.81 22.8 3.6 4.2 9.7 20.5 13.4 0.66 0.76 kW HR Heating - EAT 70°F EER HC kW HE LAT COP 11.2 1.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data Correction Tables Air Flow Correction Table Airflow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 75% 0.951 0.860 0.963 0.952 0.990 1.054 0.966 81% 0.964 0.894 0.973 0.965 0.993 1.035 0.977 88% 0.979 0.936 0.984 0.979 0.996 1.019 0.987 94% 0.990 0.969 0.992 0.990 0.998 1.008 0.994 100% 1.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Blower Performance & Electrical Data Blower Performance Model Rated CFM CCE07 SCFM Low Speed High Speed 240 190 240 CCE09 300 240 300 CCE12 350 300 350 CCE15 400 340 400 CCE19 460 400 460 Fan speed is user selectable All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Physical Data Model 07 09 12 16 [0.454] 16 [0.454] 21 [0.595] Compressor (1 Each) Factory Charge R22 (oz) [kg] 15 19 27 [0.765] 24 [0.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console Cabinet Dimensions Bottom Return - Left Hand Piping Left Hand Bottom Return 12.6 (320) 3.5 (88.9) Discharge Air 1.5 (38) 30ϒ Control Access Door Filter located inside and at top of air inlet area. Push tabs back and down to release filter for replacement. SIDE VIEW FRONT VIEW *23.9 (607) 1.9 (48) Air Inlet AIR INLET AREA 33.5 (851) 1.75 (44.5) 11.5 (292) 12.0 (305) 48.0 (1219) *2.9 (74) 48.0 (1219) L.H.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console Cabinet Dimensions Bottom Return - Right Hand Piping Right Hand Bottom Return 16 (406) 5 (127) 3.5 (88.9) Discharge Air 30ϒ Control Access Door Filter located inside and at top of air inlet area. Push tabs back and down to release filter for replacement. SIDE VIEW FRONT VIEW *23.9 (607) 1.9 (48) Air Inlet AIR INLET AREA 33.5 (851) 1.75 (44.5) 11.5 (292) 12.0 (305) 48.0 (1219) 2.9* (79) 48.0 (1219) R.H.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console Cabinet Dimensions Front Return - Left Hand Piping Left Hand Front Return 12.6 (320) 1.5 (38.1) 3.5 (88.9) Discharge Air 30ϒ Control Access Door FRONT VIEW SIDE VIEW 21.0 (533) 21.0 (533) Air 7.9 (201) Inlet 48.0 (1219) 43.7 (1110) 12.0 (305) Filter located behind return air grille and requires removal of cabinet front for access. 48.0 (1219) L.H. Pipe & Electric Area 12.0 (305) BOTTOM VIEW 1 (25) 4.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console Cabinet Dimensions Front Return - Right Hand Piping Right Hand Front Return 16.0 (406) 5.0 (127) 3.5 (89) Discharge Air 30˚ Control Access Door FRONT VIEW SIDE VIEW 21.0 (533) 21.0 (533) 7.9 Air (201) Inlet 48.0 (1219) 43.7 (1110) 12.0 (305) Filter located behind return air grille and requires removal of cabinet front for access. 48.0 (1219) 12.0 (305) .50 (13) BOTTOM VIEW 11.50 (292) R.H.
LC291 - 22 Rev.: 20 May, 2009B 0.75 (19) Optional Disconnect Box (mounted to cabinet not chassis) Water Connections 5/8" (15.9 mm) OD Copper, 1/2" IPT or 1/2" EPT Optional Motorized Water Valve Optional Autoflow Valve Blower Access Panel 3.56 (90) 7.5 (191) 0.87 (22) 3.22 (82) 3.42 (87) 5.36 (136) 3.01 (76) 4.46 (113) 0.75 (19) 3.28 (83) 5/8" (15.9 mm) ID Vinyl Hose Condensate *1.94 (49) *7.06 (179) *16.66 (423) Water Out Water In 3.88 (99) 30° Power Supply 11.54 (293) 3.43 (87) 5.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Piping Detail 3.28 (83) 5.36 (136) 3.01 (76) Power Supply 1.84 (47) 30° Water Out Water In Control Box 0.87 (22) Optional Autoflow Valve *16.66 (423) Compressor Access Panel 7.5 (191) 4.46 (113) 0.75 (19) *1.94 (49) *7.06 (179) Condensate 3.56 (90) 3.88 (99) 5/8" (15.9 mm) ID Vinyl Hose Optional Motorized Water Valve 11.54 (293) 3.43 (87) Water Connections 5/8" (15.9 mm) OD Copper, 1/2" IPT or 1/2" EPT 0.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems CCE Series Wiring Diagram Matrix Only CXM and DXM diagrams, with a representative diagram of LON and MPC Options are presented in this submittal. Other diagrams can be located online at climatemaster.com using the part numbers presented below.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram Manual & Auto Change Over CCE Units (Rev. B) With CXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram Remote Mounted Thermostat CCE Units (Rev. B) With CXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram CCE Units (Rev. B) With CXM & LON Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram CCE Units (Rev. B) With CXM & MPC Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram Manual & Auto Change Over CCE Units (Rev. B) With DXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram Remote Mounted Thermostat CCE Units (Rev. B) With DXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram CCE Units (Rev. B) With DXM & LON Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram CCE Units (Rev. B) With DXM & MPC Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console (CCE) Series 60Hz Engineering Specifications Rev.: 05/20/09 Page 1 General: Furnish and install ClimateMaster “Console” Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console (CCE) Series 60Hz Engineering Specifications Rev.: 05/20/09 Page 2 induced high noise levels associated with “hard wire belly band” motor mounting. The airflow rating of the unit shall be based on a wet coil and a clean filter in place. Ratings based on a dry coil and / or no filter shall NOT be acceptable.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console (CCE) Series 60Hz Engineering Specifications Rev.: 05/20/09 Page 3 Option: Threaded EPT copper fittings (sweat connections are standard). Option: Threaded IPT copper fittings (sweat connections are standard). Drain Pan: The drain pan shall be constructed of galvanized steel and have a powder coat paint application to further inhibit corrosion.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console (CCE) Series 60Hz Engineering Specifications Rev.: 05/20/09 k. l. m. n. o. p. Page 4 Light emitting diode (LED) on circuit board to indicate high pressure, low pressure, low voltage, high voltage, low water/air temperature cut-out, condensate overflow, and control voltage status. The low-pressure switch shall not be monitored for the first 120 seconds after a compressor start command to prevent nuisance safety trips.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console (CCE) Series 60Hz Engineering Specifications Rev.: 05/20/09 Page 5 The following points must be available at a central or remote computer location: a. Space temperature b. Leaving water temperature c. Discharge air temperature d. Command of space temperature setpoint e. Cooling status f. Heating status g. Low temperature sensor alarm h. Low pressure sensor alarm i. High pressure switch alarm j. Condensate sensor alarm k.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console (CCE) Series 60Hz Engineering Specifications Rev.: 05/20/09 Page 6 Option: Extended 4-year control board warranty covers the CXM/DXM control board for a total of 5 years. FIELD INSTALLED OPTIONS Hose Kits: Hoses shall be 1 foot (31cm) long, braided stainless steel; fire rated hoses complete with adapters. Only fire rated hoses will be accepted.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Console (CCE) Series 60Hz Engineering Specifications Rev.: 05/20/09 Page 7 g. h. Thermostat shall be 5 day/2 day programmable (with up to 4 set points per day), multi-stage (2H/1C), automatic or manual changeover with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, set-point(s), mode, and status indication.
CCE Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Revision History Date: Item: Action: 26 Aug, 2008 Engineering Specifications Thermostat & Electrical Sections Updated 26 Aug, 2008 Stand-Alone and Big Book Submittals Consolidated 26 Aug, 2008 Physical Data Table Max Working Pressure Table Added 12 June, 2008 Wiring Diagram Matrix ETL Information Added 30 May, 2008 WMV Pressure Drop Data Update 19 April, 2007 Table of Contents Added Table of Contents 19 April,