Tranquility® 30 Two-Stage (TT) Series Submittal Data Models TTD/H/V 026 - 072 60Hz - HFC-410A English Language/I-P Units Submittal Data - I-P Units Unit Designation: Job Name: Architect: Engineer: Contractor: Performance Data Cooling Capacity: Btuh EER: Revised: 17 July, 2013 Heating Capacity: Btuh COP: Ambient Air Temp: °F Entering Water Temp (Clg): °F Entering Air Temp (Clg): °F Entering Water Temp (Htg): °F Entering Air Temp (Htg): °F Airflow: CFM Fan Speed or Motor/RPM/Turns: Operati
Tranquility® 30 Two-Stage (TT) Series Submittal Data Models TTD/H/V 026 - 072 60Hz - HFC-410A English Language/S-I Units Submittal Data - S-I Units Unit Designation: Job Name: Architect: Engineer: Contractor: Performance Data Cooling Capacity: kW EER: Revised: 17 July, 2013 Heating Capacity: kW COP: Ambient Air Temp: °C Entering Water Temp (Clg): °C Entering Air Temp (Clg): °C Entering Water Temp (Htg): °C Entering Air Temp (Htg): °C Airflow: l/s Fan Speed or Motor/RPM/Turns: Operating W
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Table of Contents Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TT Series Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features The tranquility® 30 TWO-STAGE (TT) Series Unit Features As the highest efficiency water-source heat pump on the planet, the Tranquility® 30 Series raises the bar for watersource heat pump efficiencies, features and application flexibility. Not only does the Tranquility® 30 Series far exceed ASHRAE 90.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Reference Calculations Heating Cooling LWT = EWT - HE GPM x 500 LWT = EWT + LAT = EAT + HC CFM x1.08 LAT (DB) = EAT (DB) - HR GPM x 500 LC = TC - SC SC CFM x1.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Example Equipment Selection For Cooling Step 1 Load Determination: Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P TT Series Nomenclature 1 2 Model Type 3 4 5 6 7 8 9 10 11 12 13 14 15 TT V 0 2 6 B G C 3 0 C L K S TT = Tranquility® Two-Stage Scroll Standard S = Standard Supply Air & Motor Option Configuration Option Supply Configuration Top K TTV N TTD Down P TTH Back W TTH Straight V = Vertical Upflow H = Horizontal D = Vertical Downflow Unit Size 026 - E,F,G,H 038 - F,G,H 049 - F,G,H 064 - F,G,H 072 - F,G,H Return Air L = Left Return R = Right Re
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – Selection Notes For operation in the shaded area when water is used in lieu of an antifreeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such WPD Cooling - EAT that the LWT is maintained above 40°F [4.4°C] when the80/67°F EWT GPM is not clipped (see Sens/ JW3 jumper example below).
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 026 (Part Load) 850 CFM Nominal Airflow Heating, 750 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 4.5 2.5 5.8 2.3 0.7 3.4 Sens/Tot Ratio TC SC 1.7 23.3 17.9 0.77 1.3 3.0 23.1 18.0 4.5 2.0 4.6 22.9 2.3 0.5 1.2 3.4 1.0 4.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 026 (Full Load) 950 CFM Nominal Airflow Heating, 850 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 6.0 3.7 8.6 3.0 1.1 4.5 Sens/Tot Ratio TC SC 2.5 30.7 21.8 0.71 2.0 4.6 30.7 21.7 6.0 3.1 7.1 30.7 3.0 0.9 2.0 4.5 1.6 6.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 038 (Part Load) 1,000 CFM Nominal Airflow Heating, 1,000 CFM Nominal Airflow Cooling EWT °F 20 30 40 50 60 70 80 90 100 110 120 WPD GPM Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT TC SC Sens/Tot Ratio Heating - EAT 70°F kW HR EER Operation not recommended HC kW HE LAT COP 6.0 4.9 11.2 17.4 1.49 12.3 84.1 3.4 3.0 1.5 3.4 33.3 22.5 0.68 0.83 36.2 39.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 038 (Full Load) 1,250 CFM Nominal Airflow Heating, 1,250 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 9.0 8.3 19.1 4.5 2.6 6.8 Sens/Tot Ratio TC SC 6.0 45.6 29.7 0.65 4.5 10.5 44.9 29.5 9.0 6.9 16.0 44.4 4.5 2.0 4.7 6.8 3.8 9.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 049 (Part Load) 1,350 CFM Nominal Airflow Heating, 1,350 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 9.0 3.2 7.4 4.5 0.6 6.8 Sens/Tot Ratio TC SC 1.4 45.3 33.4 0.74 1.6 3.6 46.1 33.7 9.0 2.7 6.4 46.4 4.5 0.5 1.1 6.8 1.3 9.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 049 (Full Load) 1,650 CFM Nominal Airflow Heating, 1,550 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 12.0 5.2 12.1 6.0 1.2 9.0 Sens/Tot Ratio TC SC 2.8 59.6 42.6 0.72 2.7 6.4 59.4 43.8 12.0 4.7 10.8 59.0 6.0 1.0 2.3 9.0 2.4 12.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 064 (Part Load) 1,650 CFM Nominal Airflow Heating, 1,500 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 12.0 5.2 11.9 6.0 0.9 9.0 Sens/Tot Ratio TC SC 2.1 57.1 41.6 0.73 2.5 5.7 56.9 42.3 12.0 4.1 9.6 56.5 6.0 0.5 1.1 9.0 1.9 12.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 064 (Full Load) 2,050 CFM Nominal Airflow Heating, 1,850 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 15.0 7.3 16.8 7.5 1.7 11.3 Sens/Tot Ratio TC SC 3.9 76.6 53.4 0.70 3.7 8.6 76.2 54.0 15.0 6.1 14.1 75.5 7.5 1.2 2.7 11.3 3.0 15.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 072 (Part Load) 1,650 CFM Nominal Airflow Heating, 1,550 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 14.0 6.5 15.1 7.0 1.4 10.5 Sens/Tot Ratio TC SC 3.3 66.4 43.8 0.66 3.3 7.6 66.7 44.2 14.0 5.4 12.5 66.7 7.0 0.9 2.2 10.5 2.6 14.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TT H/V/D 072 (Full Load) 2,050 CFM Nominal Airflow Heating, 1,850 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67 °F PSI FT 17.0 8.9 20.6 8.5 2.2 12.8 Sens/Tot Ratio TC SC 5.1 83.8 53.9 0.64 4.6 10.6 83.7 53.8 17.0 7.6 17.6 83.3 8.5 1.6 3.8 12.8 3.9 17.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Part Load Performance Data – Correction Tables Air Flow Correction Table Airflow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 60% 0.920 0.781 0.959 0.927 0.946 1.241 0.881 69% 0.942 0.832 0.964 0.946 0.960 1.163 0.915 75% 0.956 0.867 0.696 0.959 0.969 1.115 0.937 81% 0.969 0.901 0.975 0.970 0.978 1.076 0.956 88% 0.981 0.934 0.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Full Load Performance Data – Correction Tables Air Flow Correction Table Airflow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 60% 0.925 0.788 0.913 0.922 0.946 1.153 0.896 69% 0.946 0.829 0.926 0.942 0.959 1.107 0.924 75% 0.960 0.861 0.937 0.955 0.969 1.078 0.942 81% 0.972 0.895 0.950 0.968 0.977 1.053 0.959 88% 0.983 0.930 0.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Antifreeze & Water Pressure Drop Adder for Options – Correction Tables Antifreeze Correction Table Cooling Heating EWT 90°F EWT 30°F Antifreeze Type Antifreeze % Total Cap Sens Cap Power Htg Cap Power WPD Corr. Fct. EWT 30°F Water 0 1.000 1.000 1.000 1.000 1.000 1.000 5 0.995 0.995 1.003 0.989 0.997 1.070 Propylene Glycol 15 0.986 0.986 1.009 0.968 0.990 1.210 25 0.978 0.978 1.014 0.947 0.983 1.360 5 0.997 0.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P ECM Control The ECM fan is controlled by an interface board that converts thermostat inputs and field selectable CFM settings to signals used by the ECM motor controller. Units manufactured after July 2005 have version II (P/N 17B0019N01). Fan speeds are selected with a nine position DIP switch for version II. To take full advantage of the ECM motor features, a multi-stage thermostat should be used (2-stage heat/2-stage cool or 3-stage heat/2-stage cool).
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P ECM Control The ECM motor includes “soft start” and “ramp down” features. The soft start feature is a gentle increase of motor rpm at blower start up. This creates a much quieter blower start cycle. The ramp down feature allows the blower to slowly decrease rpm to a full stop at the end of each blower cycle. This creates a much quieter end to each blower cycle and adds overall unit efficiency.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P ECM Control Dehumidification Mode Settings: The dehumidification mode setting provides field selection of humidity control. When operating in the normal mode, the cooling airflow settings are determined by the cooling tap setting above. When dehumidification is enabled there is a reduction in airflow in cooling to increase the moisture removal of the heat pump.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Blower Performance Data Standard Unit - No Reheat Airflow in CFM with wet coil and clean air filter Model Max ESP (in. wg) 026 038 049 064 072 Fan Motor (hp) Tap Setting Cooling Mode Stg 1 Stg 2 Fan Dehumid Mode Stg 1 Stg 2 Heating Mode Fan Stg 1 Stg 2 Fan 0.50 1/2 4 810 950 475 630 740 475 920 1060 475 0.50 1/2 3 725 850 425 560 660 425 825 950 425 0.50 1/2 2 620 730 370 490 570 370 710 820 370 0.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P ClimaDry® II Option - Benefits and Application ClimaDry® II Modulating Reheat Option ClimateMaster’s patented ClimaDry® II Dehumidification option is an innovative means of providing modulating reheat without the complication of refrigeration controls. ClimaDry® II is hot gas generated reheat, which utilizes one of the biggest advantages of a Water-Source Heat Pump (WSHP), the transfer of energy through the water piping system.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P ClimaDry® II Option - Benefits and Application With the ClimaDry® II option, return air from the space is cooled by the air-to-refrigerant (evaporator) coil, and then reheated by the water-to-air (reheat) coil to dehumidify the air, but maintain the same space temperature (thus operating as a dehumidifier). The moisture removal capability of the heat pump is determined by the unit’s latent capacity rating.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P ClimaDry® II Option - Sequence of Operation ClimaDry® II Sequence of Operation - A heat pump equipped with ClimaDry® II can operate in three modes; cooling, cooling with reheat (dehumidification), and heating. The cooling/heating modes are like any other ClimateMaster WSHP. The reversing valve (“O” signal) is energized in cooling, along with the compressor contactor(s) and blower relay. In the heating mode the reversing valve is de-energized.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P ClimaDry® II Option - Sequence of Operation 1st Stage Heating: A simultaneous call from (G) and (Y1) to the (G) and (Y1) terminals of the DXM control board will bring the unit on in 1st Stage Heating. 2nd Stage Heating: A simultaneous call from (G), (Y1), and (Y2) to the (G), (Y1), and (Y2) terminals of the DXM control board will bring the unit on in 2nd Stage Heating.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Physical Data Model 026 038 049 Compressor (1 Each) Factory Charge (HFC-410A) (oz) [kg] 064 072 Two-Stage Scroll 60 [1.70] 64 [1.81] 81 [2.30] 142 [4.03] 140 [3.97] 1/2 [373] 1/2 [373] 1 [746] 1 [746] 1 [746] 9x7 [229 x 178] 11 x 10 [279 x 254] 11 x 10 [279 x 254] 11 x 10 [279 x 254] 11 x 10 [279 x 254] 3/4 3/4 1 1 1 1/2 1/2 1/2 1/2 1/2 0.76 [2.88] 0.92 [3.48] 1.24 [4.69] 1.56 [5.91] 1.56 [5.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P TT - Horizontal Dimensional Data Horizontal Model Overall Cabinet *A Width B Length C Height 026 in cm 22.4 56.8 62.2 158.0 19.3 48.9 038 in cm 25.4 64.5 71.2 180.8 21.3 54.0 049 in cm 25.4 64.5 76.2 193.5 21.3 54.0 064 & 072 in cm 25.4 64.5 81.2 206.2 21.3 54.0 *Does not include air filter supports. Add 2” (5.1cm) when a 1” (25.4mm) filter is used, add 3” (7.6cm) when a 2” (50.8mm) filter is used.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P TT - Horizontal Dimensional Data Discharge Connection Duct Flange Installed Horizontal Model Return Connection Using Return Air Opening Return Connection Using Optional Air Filter Frame M N O Supply Height P Supply Width Q R S Return Width T Return Height U V S Return Width T Return Height U V 026 in cm 3.6 9.3 2.0 5.1 15.5 39.4 12.5 31.8 3.6 9.2 2.0 5.2 32.1 81.5 17.3 43.9 2.3 5.8 1.0 2.5 33.8 85.8 16.2 41.0 2.3 5.8 1.7 4.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P TT - Vertical Upflow Dimensional Data Vertical Upflow Model Overall Cabinet Water Connections *A Width B Depth C Height Vertical Upflow Model 1 2 3 4 Loop In D Loop Out E HWG In F HWG Out G Water Connections Units with ClimaDry® 5 H Water Loop FPT HWG FPT 1 2 Loop In D Loop Out E 026 in cm 22.4 56.8 25.6 65.1 48.5 123.2 038 in cm 25.4 64.5 30.6 77.8 50.5 128.3 026 in cm 2.1 5.2 10.0 25.4 13.9 35.2 16.9 42.9 7.8 19.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P TT - Vertical Upflow Dimensional Data Discharge Connection Duct Flange Installed Vertical Upflow Model Return Connection Using Return Air Opening Return Connection Using Optional Air Filter Frame M N O Supply Width P Supply Depth Q R S Return Depth T Return Height U R S Return Depth T Return Height U 026 in cm 7.2 18.3 5.8 14.8 14.0 35.6 14.0 35.6 4.9 12.4 2.3 5.8 21.1 53.6 27.7 70.4 1.0 2.5 1.7 4.3 22.2 56.4 26.2 66.5 1.7 4.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P TT - Vertical Downflow Dimensional Data Vertical Downflow Model Overall Cabinet *A Width B Depth C Height 026 in cm 22.4 56.8 25.6 65.1 52.5 133.4 038 in cm 25.4 64.5 30.6 77.8 54.5 138.4 049 in cm 25.4 64.5 30.6 77.8 58.5 148.6 064 & 072 in cm 25.4 64.5 30.6 77.8 62.5 158.8 *Does not include air filter supports. Add 2” (5.1cm) when a 1” (25.4mm) filter is used, add 3” (7.6cm) when a 2” (50.8mm) filter is used.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P TT - Vertical Downflow Dimensional Data Discharge Connection Duct Flange Installed Vertical Downflow Model Return Connection Using Return Air Opening Return Connection Using Optional Air Filter Frame M N O Supply Width P Supply Depth Q R S Return Depth T Return Height U R S Return Depth T Return Height U 026 in cm 6.7 17.1 8.4 21.4 10.1 25.7 9.1 23.0 10.8 27.4 2.2 5.6 21.1 53.6 27.7 70.4 21.2 53.8 1.7 4.3 22.2 56.4 26.2 66.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Corner Weights Corner Weights for TT Series Horizontal Units Model 026 038 049 064 072 Total Left-Front* Right-Front* Left-Back* Right-Back* Lbs 266 78.8 67.2 69.9 50.2 kg 121 35.7 30.5 31.7 22.7 Lbs 327 104.4 74.9 83.7 64.0 kg 148 47.4 34.0 38.0 29.0 Lbs 416 145.0 92.6 98.1 80.3 kg 189 65.8 42.0 44.5 36.4 Lbs 441 182.3 72.5 78.4 107.8 kg 200 82.7 32.9 35.6 48.9 Lbs 441 182.3 72.5 78.4 107.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data Standard Units All TT Units Model Voltage TT 038 TT 049 TT 064 TT 072 Compressor Min/Max Fan Min Circuit Amp Max Fuse/ HACR 30 Voltage QTY RLA LRA Motor FLA Total Unit FLA G 208/230/60/1 197/252 1 11.7 58.3 3.9 15.6 18.5 E 265/60/1 239/292 1 9.1 54.0 3.2 12.3 14.6 20 H 208/230/60/3 197/252 1 6.5 55.4 3.9 10.4 12.0 15 F* 460/60/3* 414/506 1 3.5 28.0 3.2 6.7 7.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P TT Series Wiring Diagram Matrix Only CXM and DXM diagrams, with a representative diagram of LON and MPC Options are presented in this submittal. Other diagrams can be located online at climatemaster.com using the part numbers presented below.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TT Units with CXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TT Units with DXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 208/230V TT Units with CXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 208/230V TT Units with DXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460V TT Units with CXM Controller Note: 460V Units with ECM Motor Require A Neutral Wire. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460V TT Units with DXM Controller Note: 460V Units with ECM Motor Require A Neutral Wire. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TT Units with CXM And MPC Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TT Units with ClimaDry® II ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 30 (TT) Series 60Hz Engineering Specifications – Page 1 General: Furnish and install ClimateMaster Tranquility® “TT” Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped, and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 30 (TT) Series 60Hz Engineering Specifications – Page 2 Cabinets shall have separate holes and knockouts for entrance of line voltage and low voltage control wiring. All factory-installed wiring passing through factory knockouts and openings shall be protected from sheet metal edges at openings by plastic ferrules.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 30 (TT) Series 60Hz Engineering Specifications – Page 3 Refrigerant metering shall be accomplished by thermostatic expansion valve only. Expansion valves shall be dual port balanced types with external equalizer for optimum refrigerant metering. Units shall be designed and tested for operating ranges of entering water temperatures from 20° to 120°F (-6.7° to 48.9°C).
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 30 (TT) Series 60Hz Engineering Specifications – Page 4 i. j. k. l. m. n. o. p. Automatic intelligent reset. Unit shall automatically reset the unit 5 minutes after trip if the fault has cleared. If a fault occurs 3 times sequentially without thermostat meeting temperature, then lockout requiring manual reset will occur. Ability to defeat time delays for servicing.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 30 (TT) Series 60Hz Engineering Specifications – Page 5 Remote Service Sentinel (CXM/DXM): Solid state control system shall communicate with thermostat to display (at the thermostat) the unit status, fault status, and specific fault condition, as well as retrieve previously stored fault that caused unit shutdown. The Remote Service Sentinel allows building maintenance personnel or service personnel to diagnose unit from the wall thermostat.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 30 (TT) Series 60Hz Engineering Specifications – Page 6 This option also provides the upgraded 75VA control transformer with load side short circuit and overload protection via a built in circuit breaker. Warranty: Climate Master shall warranty equipment for a period of 12 months from start up or 18 months from shipping (which ever occurs first). Option: Extended 4-year compressor warranty covers compressor for a total of 5 years.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 30 (TT) Series 60Hz Engineering Specifications – Page 7 e. Multistage Manual Changeover Programmable 5/2 Day (ATP21U01) Thermostat shall be 5 day/2 day programmable (with up to 4 setpoints per day), multi-stage (2H/1C), manual changeover with HEAT-OFF-COOL-EM HEAT system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, setpoint(s), mode, and status indication.
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P Revision History Date: Item: Action: 07/17/13 EAT Minimum Limit ClimaDry® Updated 04/29/13 08/17/12 Size 038 EAT Limits Recommended Minimum Installation Clearances for Vertical Units * All Updates to Revision Level C Updates to Text - ClimaDry® Option Added Updated Tranquility® 27 to Tranquility® 30 08/03/12 Electrical Data Table with ClimaDry® Updated 08/01/12 Unit Performance, Electrical Data Updated 02/20/12 Engineering Specifications U