Instruction manual

CLIMATEMASTER WATER-SOURCE HEAT PUMPS
D (ERV) Series
Rev.: 04 April, 2014
14
ClimateMaster Water-Source Heat Pumps
Mist Eliminator Filter in Intake Hood (1.5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
300 N/A N/A 1175 1350 1450 1605 1730
500 N/A 1170 1340 1540 1655 1725 1840
700 1295
1425 1600 1625 1795 1960 2035
900 1540
1660 1720 1790 2030 2110 2195
1100 1785 1915 2025 2185 N/A N/A N/A
Barometric Hood, 2" Pleated Filters (1.5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
300 N/A N/A 1030 1225 N/A N/A N/A
500 N/A 1025 1180 1265 1425 1535 N/A
700 1120 1190 1340 1445 1540 1645 1720
900 1285
1525 1500 1575 1670 1785 1865
1100 1570
1665 1670 1775 1860 1920 N/A
SUPPLY
EXHAUST
Low 1000-1300 Standard Unit
Medium 1300-1700 Optional Kit
High 1750-2200 Optional Kit
RPM Range
Mist Eliminator Filter in Intake Hood (2HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 1055 1135 1295 1420 1540 1650 1725
1400 1
140 1240 1340 1490 1600 1690 1795
1600 1200
1330 1460 1565 1645 1740 1830
1800 1320
1405 1525 1615 1705 1785 1885
2000 1415
1515 1605 1690 1775 1875 1960
Barometric Hood, 2" Pleated Filters (2HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 1010 1195 1350 1445 1580 1685 1735
1400 1
125 1315 1435 1545 1620 1730 1800
1600 1
185 1370 1500 1610 1695 1790 1965
1800 1305
1485 1600 1685 1781 1955 2030
2000 1410
1550 1670 1765 1855 N/A N/A
SUPPLY
EXHAUST
RPM Range
Low 1000-1300 Standard Unit
Medium 1300-1700 Optional Kit
High 1700-2080 Optional Kit
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Blower RPM for DB
Blower RPM for DC